Conference PaperPDF Available

Control of Inertia in Hybrid Microgrids from a Regulated DC Microgrid System

Authors:

Abstract and Figures

A methodology for controlling the inertia of the interlinking converter of a hybrid AC-DC microgrid working in both grid connected and isolated modes, is presented in this paper. The DC microgrid system is a Photovoltaic Generator (PVG) and a battery based energy storage (BES) based system, with constant impedance loads. The purpose of the DC microgrid is to manage the power within the DC system and to provide the necessary inertial support to the AC system. For the control of the interlinking voltage source inverter, a DC link voltage based virtual inertia strategy is formulated, which is formed as a lead-lag compensator with the change in the DC link voltage as the input, and the frequency as the output. The proposed method serves a two-fold advantage as a unified controller, i.e., the requisite inertial response is provided, as the compensator is the outcome of the swing equation, and the same controller can act as a bus signalling control, therefore managing the power flow to the utility in the grid connected mode of operation. Time domain analysis of the microgrid system verifies the efficacy of the proposed approach for both power flow based on utility command, as well as inertial support in the isolated mode. The compensator tuning is achieved with the help of a small signal analysis of the cascaded inertial controller deployed.
Content may be subject to copyright.
Control of Inertia in Hybrid Microgrids from a
Regulated DC Microgrid System
Somesh Bhattacharya
MCAST Energy Research Group
Institute of Engineering and Transport
MCAST
Malta
Somesh.Bhattacharya@mcast.edu.mt
Sukumar Mishra
Electrical Engineering Department
Indian Institute of Technology Delhi
New Delhi, India
sukumar@ee.iitd.ac.in
Brian Azzopardi
MCAST Energy Research Group
Institute of Engineering and Transport
MCAST
Malta
Brian.Azzopardi@mcast.edu.mt
Abstract—A methodology for controlling the inertia of the
interlinking converter of a hybrid AC-DC microgrid working
in both grid connected and isolated modes, is presented in this
paper. The DC microgrid system is a Photovoltaic Generator
(PVG) and a battery based energy storage (BES) based system,
with constant impedance loads. The purpose of the DC microgrid
is to manage the power within the DC system and to provide the
necessary inertial support to the AC system. For the control
of the interlinking voltage source inverter, a DC link voltage
based virtual inertia strategy is formulated, which is formed as
alead-lag compensator with the change in the DC link voltage
as the input, and the frequency as the output. The proposed
method serves a two-fold advantage as a unified controller, i.e.,
the requisite inertial response is provided, as the compensator is
the outcome of the swing equation, and the same controller can
act as a bus signalling control, therefore managing the power
flow to the utility in the grid connected mode of operation. Time
domain analysis of the microgrid system verifies the efficacy of
the proposed approach for both power flow based on utility
command, as well as inertial support in the isolated mode. The
compensator tuning is achieved with the help of a small signal
analysis of the cascaded inertial controller deployed.
Index Terms—DC microgrid, virtual inertia
I. INTRODUCTION
With increased levels of installations of static inverter based
sources or Distributed Energy Resources (DER), the effective
inertia of the system is reduced. The rotating generators
have sufficient mass to produce a kinetic energy during any
load change or a fault scenario. However, the static inverter
based systems inherently lack this feature and a dedicated
control system is required to mimic the inertia. Popularly, the
inverters deploying such controls are also known as virtual
synchronous generators (VSG) [1]. AC and DC microgrids,
in both isolated and the grid connected modes can emulate
virtual inertia through DC-DC converters and Voltage Source
Inverters (VSI). The emulation of inertial control from the
VSI in the AC side assists in the desired frequency response
and regulation seen from the VSI towards the grid [2]. Virtual
inertia can also be attained from a DC microgrid for a better
This work was supported in part by the European Commission H2020
TWINNING projects namely JUMP2Excel (Joint Universal activities for
Mediterranean PV integration Excellence) and NEEMO (Networking for
Excellence in Electric Mobility Operations under grants 810809 and 857484
respectively
frequency regulation as well as enabling the DC link voltage
regulation [3]. This technique enables a more holistic power
management for both the AC and DC side of the VSI.
Hybrid AC-DC microgrids are advantageous in the sense
that the DC microgrids can easily send or receive power from
the interlinking VSI (IVSI), and the AC microgrid in the
isolated mode has an increased reliability, as the plug and play
capabilities in a DC microgrid is higher. Decentralized power
management within the hybrid microgrid have been discussed
in details in [4-7]. The advantage of using the droop control
in hybrid microgrids is the non reliance on the upper level
controls for the generation of the power dispatch references,
and communication requirements within the local DERs are
very low [5].
The aspect of synthetic inertia in the hybrid microgrid was
detailed in [3], [8] and [9], and the inertial response from
the DC microgrid was based on the power balance equation
analogized from the swing equation of the synchronous ma-
chine. The DC side dynamics pertaining to inertial control
are limited to the control of the DC link voltage, Vdc,andthe
stabilization of Vdc was achieved through a virtual capacitance.
However, the study did not consider the implications of the AC
side of the microgrid, such as a load event or a grid outage.
Also, the power ow aspect from the DC microgrid to the
utility grid have not been described very well. Within the DC
microgrid, the power flow management by sensing the Vdc
and thereby producing power references based on the DC bus
signals was proposed in [10]. The charging and discharging
of the batteries, as well as the de-rating of the PVG was also
based on the bus-signalling method. However, this method
only considered a DC microgrid, and the AC side dynamics
were not taken into account.
In this paper, the idea of controlling the power flow within
the DC microgrid for the BESS, as well as for the utility,
without having to sense the active power from the IVSI,
has been studied. The Vdc is controlled in such a way that
the inertial response from the DC microgrid can also be
harnessed into the AC system, both in the grid connected
and isolated modes. The verification have been made for the
hybrid microgrid system considered in section II. Section III
describes the inertial controller, along with the inner voltage
and current controls. The small signal based tuning method
for the controller is shown in section IV. The efficacy of the
proposed control for various cases is described in section V,
and section VI concludes the paper.
II. THE HYBRID AC-DC MICROGRID ARCHITECTURE
As mentioned previously, a hybrid AC-DC microgrid is a
conglomeration of both AC and DC loads, which are served
by the local AC and DC DERs. In this paper, the generation
(PVG+BESS) is on the DC side of the microgrid, and in
the isolated mode, the entire microgrid system is fed by
the DERs hosted in the DC side. Constant impedance loads
are considered. Fig.1. shows the schematic of the hybrid
microgrid. As mentioned, the microgrid can operate in both
Zac Zac Zac
Distributed AC Loads
(Voltage dependent loads)
Utility grid
Powerflow
AC Bus (230V)
DC bus (Vnom=380V)
Power flow
Power flow
Power flow
DC DC DC DC DC DC
DC DC
AC
DC
Power flow
Power flow
Power flow
Cdc
Rdc Rdc Rdc
230V/11kV
Threephase
Transformer
Fig. 1: Schematic representation of a hybrid AC-DC microgrid
isolated and the grid connected modes. In the grid connected
mode, the IVSI works in the constant current dispatch mode,
even though as a grid forming inverter. Therefore following
the set-points received by the system operator. The active
power set-points help the BESS of the DC microgrid charge/
discharge in accordance with the references, while maintaining
the voltage of the DC system. The batteries operate in the
voltage control mode in the SoC range of 20%to 80%.If
the storage reach their limits in the grid connected mode,
they operate in the floating mode, i.e. no charge or discharge
action from the storage will be performed, and when the hybrid
microgrid enters the isolated mode, the batteries resume their
operation based on the loading scenario. In both the cases, the
PVG continues to operate in the constant dispatch mode.
III. IVSI AS A VIRTUAL SYNCHRONOUS GENERATOR
The interlinking converter (IVSI) operates as a grid forming
inverter, as aforementioned. This scheme can be achieved
easily with the help of adaptive droop control, where the con-
troller is responsible for the provision of frequency response in
the grid connected mode, and regulation in the isolated mode.
A. Formulation of the inertial control with DC link voltage
(Outermost control loop of IVSI)
The swing equation (Eq.(1)) can be described as an energy
balance equation, the difference in the per unit powers is the
acceleration of the machine rotor, which releases the stored
energy (E=0.5.J.ω2), ’J’ being the inertial mass in actual
units. The released energy reflects in the over/ under shoot in
the frequency or the angle of the machine w.r.t the grid or
another machine.
H
π.f
d2δ
dt2=PmPeDar(1)
Where ’H’ is the inertial constant in seconds, and δ’isthe
angle of the inverter w.r.t to the point of common coupling in
radians. The parameters Pm’and’P
eare the mechanical and
electrical powers respectively, which in the case of inverter
based system are the DC and the AC powers. Da’isthe
load damping coefficient, which mimics as the droop control
law for the IVSI. The energy balance provided by the DC
link capacitor, Cdc from the DC side of the IVSI is analogous
to the swing equation of the AC side of the IVSI. Energy
stored by the capacitor, which is released during a transient is
E=0.5.Cdc.V 2
dc. The equation can be described as under-
Cdc.Vdc.dVdc
dt =Pdc Pac Db.Vdc (2)
As seen from Eq.(2), the parameter Db is the coefficient of
damping provided by the capacitor following the transients.
Upon linearizing Eq.(1), i.e. the rotor dynamics, the equations
can be refurbished in the small signal domain as follows-
Δω=Δ.PmΔ.Pe
2Hs +Da
(3)
Re-arranging the equation (3), we get
Δω=Kac
τac.s +1.Δ.P (4)
In Eq.(4), the variables Kac and τac can be defined as 1/Da
and 2H/Darespectively. On similar lines, linearizing Eq.(2)
will give the following expression-
Δ.Vdc =Δ.Pdc Δ.Pac
Cdc0.Vdc.s +Db
(5)
Re-arranging the above equation, we obtain-
Δ.Vdc =Kdc
τdc.s +1.Δ.P (6)
As shown in Eq.(6), the variables Kdc and τac can be
defined as 1/Dband Cdc0.Vdc/Dbrespectively. Upon equating
Eq.(4) and Eq.(6) with Δ.P being the common denominator,
we obtain Δωas a function of Δ.vdc. The same can be
summarized in Eq.(7)-
Δω=Dba.τdc +1
τac +1.Δ.Vdc (7)
Where the parameter Dba is the ratio of the damping factors
of the DC and the AC energy balance equation and swing
equation respectively. The generation of the frequency and
the angular references for the conversion of the three phase
voltages in the dq stationary reference frame (because of
the absence of the PLL in the control loop) can thereby be
obtained as a function of the DC link voltage, as can be seen
in Eq.(8) and (9).
ωref =ωn+Dba.τdc +1
τac +1.(Vref
dc
Vdc)(8)
δref =t
0
ωrefdt (9)
The control structure of the IVSI operating as a VSG has
been shown in Fig.2. The power flow management in the
Dba
dc
ac
.s+1
.s+1
W
W
1
s
Current
Controller
Voltage
controller
0
.1
q
c
K
s
W
V and δ
Processing
Signals
To the
IVSI
Vdc
ref
(Based
On DC bus
Signalling)
Vdc
+-
+-
Qref
Q
Vodq
ref Iidq
ref
Fig. 2: Plots for the state of charge of the BESS
grid connected mode, with the help of the DC bus signalling
method is described in the following equation. It can be stated
that when the reference Vdc is greater than the nominal voltage,
the BESS will be operating in the charging mode, and the net
power flow from the DC microgrid to the utility grid will be
negative, i.e. the grid will supply power to the microgrid. The
scenario is vice-versa when the Vref
dc is lesser than the nominal
Vdc.
Vref
dc <V
dc;P>0(10)
Vref
dc >V
dc;P<0(11)
The reactive power is generally controlled with the help
of a droop based control, where the voltage references are
generated based on proportional coefficients. In both the grid
connected and the isolated mode, because of the presence of
a dedicated voltage controller, no integral term is added.
Vref
d=Vdn
Kq0
τc.s +1 (12)
In Eq.(12), the parameters, Vdn,Kq0and τcare the nominal
p.u. d-axis voltage, normalized proportional droop coefficient
(Kq0=Kqc)and 1crespectively.
B. Inner Voltage and Current Control Loops
In order to control the voltage of the hybrid system in the
isolated mode, the AC voltage controller is deployed, which
is a decoupled controller. Therefore, the d and q axis voltages
can be controlled separately. The governing equations for the
d and q axis voltage controller can be deliberated as-
iref
dq =(Vref
dq
Vdq).Kpv .s +Kiv
sω.Cf.Voqd +F.iodq (13)
The decoupled current controller is deployed for the protection
of the inverter circuits for over-currents, and to generate proper
current references in line with the designed passive filter
topology.
Vref
idq =(iref
dq
idq).Kpc .s +Kic
sω.Lf.iqd (14)
C. Control of BESS in the DC part of the hybrid microgrid
The DC part of the hybrid microgrid, as can be observed
from Fig.1. has two PVGs and two BESSs operating in par-
allel. To achieve a decentralized communication-free control,
the BESS operate in the droop control mode, and the PVGs
operate at their MPPT, i.e., they operate at constant duty.
For the BESS, the governing equations for the droop control
and the inner controls can be summarized in Eq.(15-17).
The reference power (Pref ) is held at 0, in both modes of
operation.
Vref
dc =Vdcn
mb.ωc.P
s+ωc
Pref(15)
iref
b=(Vref
dc
Vdc)Kpvdc .s +Kivdc
s(16)
Duty =(iref
b
ib)Kpcdc.s +Kicdc
s(17)
IV. TUNING OF THE CONTROLLER PARAMETERS
The dynamic analysis for the tuning of the controller
parameters has been shown in this section. The active and
reactive power flows can be described as-
P=V1RlineΔV
Z2
line
+V1V2Xlineδ
Z2
line
(18)
Q=V1XlineΔV
Z2
line
V1V2Rlineδ
Z2
line
(19)
The above obtained Pand Qequations when linearized w.r.t
δand to give a more compatible relationship between Pand
Q, gives an expression to be directly plugged into the small
signal equation equations of inertia and voltage control. The
same can be written in a consize form as under-
Δ.P =KΔδ+Kpv .Δ.V (20)
Δ.Q =KΔδ+Kqv .Δ.V (21)
Revisiting Eq.(7), the expression can be re-written in terms of
Δ.P as below
Δω=Dba.τdc +1
τac +1.Gdc(s.P (22)
Where Gdc is the linearized form of the DC power balance
equation and can be expressed as 1/Cdc0.Vdc.s. Similarly, the
expression for the V-Q(Voltage droop control) loop can be
written as Δ.Vd(s)=Gv(s).Δ.Q(s). Using Eq.(20,21) and
the latter relationship, we can obtain the small signal relation
between Δ.V and δ, which can be shown in Eq.(23).
Δ.V =Gv(s).K
1Gv(s).Kqv
.Δδ(23)
The relationship between Δ.P and Δδcan thus be deduced
as follows-
Δ.P =K +Gv(s).Kqδ.Kpv
1Gv(s).Kqv .Δδ(24)
In a more concise form, the expression can be written as
Δ.P =G(s).Δδ. With the help of the aforementioned
Dba
.1
.1
dc
ac
s
s
W
W
Gdc(s)
1
s
Gpδ(s)
c
c
s
Z
Z
ΔωΔδΔP0 +-
Fig. 3: Block diagram of the transfer function between Δ.Vdc
and Δδ
equations, the I/O relation between Vdc and δcan be deduced,
as can be seen in the following block diagram.
Upon observing the parametric variation of τac between
0.01 rad/W to 0.09 rad/W , keeping τdc constant at 0.05
rad/W, the modal sensitivities of Δ.Vdc and Δωare observed,
and it was seen that the variation of the latter, the oscillatory
modes of Δωwere significantly reduced. The same can be
seen in Fig.4. The values of τac and τdc were therefore held
(sec-1)
-14 -12 -10 -8 -6 -4
j
-50
0
50 Variation in the
Vdc modes when
ac
is varied
Variation in the
modes when
ac
is varied
Fig. 4: Plots for the variation of the modes of Δ.Vdc and Δω-
τac changed
at 0.035 rad/W and 0.065 rad/W for the simulations. The
values of the inner control loops were obtained from the
symmetrical optimum and modulus optimum approach [6],
and the proportional and integral parameters of the voltage
controller were obtained as 3.4 and 20 p.u. respectively. The
values of the current controller were obtained as 1.8 and 22.5
p.u. respectively.
V. R ESULTS AND DISCUSSIONS
A. Base Case Scenario
The simulations are performed on the hybrid AC-DC mi-
crogrid considered in Fig.1. The PVGs considered are Soltech
1STH-215-P, and have their maximum generation of 9.6kW
at 1000W/m2insolation. The BESS considered are a pack of
Li-Ion battery banks, which is a series-parallel combination
produce a total nominal voltage of 200VDC. The rated capacity
of the batteries are set at 2.6Ah, i.e. in over the period of
one hour, the batteries are capable of delivering a DC power
of 520W. However, the charging rate of the battery from
0%SoC to 100 %SoC is much higher than one hour
due to the internal capacitance, and other dynamics of the
battery. The total base case loading at the AC side is 4062
VA and on the DC side is 18,612 W. Alternate meaning of
the base case scenario from the DC bus signalling viewpoint
Time [s]
0246810
PIVSI (W) and QIVSI (VAr)
-2000
0
2000
4000
6000
8000
10000
12000
PIVSI
QIVSI
Fig. 5: Plots for the active and reactive powers measured at
the IVSI terminal
Time [s]
0246810
DC Powers (W)
0
2000
4000
6000
8000
10000
12000
PPVG-1
PPVG-2
PBESS-1
PBESS-2
Fig. 6: Plots of the powers of the PVG and BESS
is that the equivalent power flow to the utility grid will be
minimum, which means that the reference voltage is set at
380V. The proposed controller parameters for which the results
are obtained are τdc =0.045Rad/W ,τac =0.075Rad/W ,
and Dba =0.21p.u. respectively. Fig.5 shows the transition
of the microgrid from the isolated mode to the grid connected
mode. The grid is disconnected at 10th sec, and following that,
a load change of 6082.6VA is simulated at the 16th sec. For
the same scenario, the power flow within the DC microgrid
for the BESS and the PVG can be seen in Fig.6. It is to be
noted that one of the PVGs is working at 90%insolation. The
BESS are operating in the droop control mode, with droop
coefficients as 0.0004p.u. and 0.0008p.u. respectively. The
comparison between the response of the frequency for the
conventional swing equation based inertial control, and the
DC link voltage based inertial control has been demonstrated
in Fig.7. It can be observed that transient response is improved
for the proposed controller. In case of the conventional control,
the load damping coefficient and the inertia constant are fixed
at 20 p.u. and 2.4 seconds respectively.
B. Results for DC bus signalling
In this subsection, the power flow from the DC microgrid
to the utility grid using the DC bus signalling method has
been depicted. Three cases, with reference DC voltage higher,
lower, and equal to the nominal voltage has been shown. Fig.8.
shows the DC link voltage measured at the IVSI terminal.
Three cases were collated together as a step change in the
voltage at the 3rd and the 8th seconds. Fig.9 shows the active
powers measured at the IVSI. It can be seen that when the
Time [s]
024681
0
frequency (Hz)
49.75
49.8
49.85
49.9
49.95
50
50.05
freqconventional
freqproposed
Fig. 7: Plots for the comparison of response of frequency
Time [s]
024681012
VDC (V)
376
377
378
379
380
381
382
383
Fig. 8: Plots for various DC link voltages for bus signalling
reference voltage is 380V, the active power to the grid is
minimum. When the voltage is increased to 382V, the batteries
are in the charging mode, and the latter are in the discharging
mode when the reference voltage is reduced to 378V. The
state of charges of the two participating BESSs are shown
in Fig.10. It can be seen that during the nominal voltage
operation, the BESS are in the floating mode. The charging
and discharging are based on the higher and lower values of
the voltages respectively.
Time [s]
024681012
Active Power at IVSI (W)
-5000
-4000
-3000
-2000
-1000
0
1000
2000
3000
Fig. 9: Plots for active powers following the DC link voltage
commands
Time [s]
024681012
State of charge (%)
39.3
39.4
39.5
39.6
39.7
39.8
39.9
40
SoCBESS-1
SoCBESS-2
Fig. 10: Plots for SoC of the BESS
VI. CONCLUSIONS
This paper presented an alternative way of controlling the
inertial response from an IVSI of a hybrid AC-DC microgrid.
A lead-lag compensator was designed, which also works
as a power flow controller within the IVSI. This way, the
regulation of the voltage regulation of the DC microgrid is
maintained, as well as the unified controller can also provide
necessary variations in power flow by the virtue of DC bus
signalling. The efficacy of the control approach has been
shown through small signal stability and time domain analysis
in MATLAB/SIMULINK.
REFERENCES
[1] H. Bevrani, T. Ise and Y. Miura, “Virtual synchronous generators:
A survey and new perspectives, Renewable and Sustainable Energy
Reviews, Vol. 54, pp. 244-254, 2014.
[2] Yin Sun, E.C.W. De Jong, X. Wang, D. Yang, F. Blaabjerg, V. Cuk and
J.F.G. Cobben, "The Impact of PLL Dynamics on Low Inertia Power
Grid: A Case Study of Bonaire Island Power System," Energies,Vol.
12, No.1259, pp.1-16, April 2019.
[3] D. Chen, Y. Xu, and A.Q. Huang, "Integration of DC Microgrids as
Virtual Synchronous Machines Into the AC Grid," IEEE Transactions
on Industrial Electronics, Vol.64, No.9, pp. 7455-7466, 2017.
[4] A. Gupta, S. Doolla and K. Chatterjee, "Hybrid ACâ ˘
SDC Microgrid:
Systematic Evaluation of Control Strategies," IEEE Transactions on
Smart Grid, Vol.9, No.4, pp. 3830-3843, 2018.
[5] F. Nejabatkhah and Yun Wei Li, "Overview of Power Management
Strategies of Hybrid AC/DC Microgrid," IEEE Transactions on Power
Electronics, Vol.30, No.12, pp. 7072-7089, 2015.
[6] H. Mahmood, D. Michealson and J. Jiang, "Strategies for Independent
Deployment and Autonomous Control of PV and Battery Units in
Islanded Microgrids," IEEE Journal of Emerging and Selected Topics
on Power Electronics, Vol.3, No.3, pp.742-755, 2015.
[7] L. He, Y. Li, J.M. Guerrero, and Y. Cao, "A Comprehensive Inertial
Control Strategy for Hybrid AC-DC Microgrid with Distributed Gener-
ations," IEEE Transactions on Smart Grid, Vol.11, No.2, pp.1737-1747,
2020.
[8] W. Wu, Y. Chen, An Luo, L. Zhou, X. Zhou, L. Yang, Y. Dong and
J.M. Guerrero, "A Virtual Inertia Control Strategy for DC Microgrids
Analogized With Virtual Synchronous Machines," IEEE Transactions
on Industrial Electronics, Vol.64, No.7, pp. 6005-6016, 2017.
[9] C. Wang, J. Meng, Y. Wang and H. Wang, "Adaptive Virtual Inertia
Control for DC Microgrid with Variable Droop Coefficient," 20th In-
ternational Conference on Electrical Machines and Systems, Aug.2017,
Australia.
[10] K. Sun, Y. Xing, and J.M. Guerrero, "A Distributed Control Strategy
Based on DC Bus Signalling for Modular Photovoltaic Generation
Systems with Battery Energy Storage" IEEE Transactions on Power
Electronics, Vol.26, No.10, pp. 3032-3045, 2011.
ResearchGate has not been able to resolve any citations for this publication.
Article
Full-text available
To prepare for the future high penetration level of renewable energy sources, the power grid’s technical boundaries/constraints for the correct operation of powerelectronics interfaced devices need to be further examined and defined. This paper investigates the challenge of integrating Voltage Source Converters (VSC) into low inertia power grids, where the system frequency can vary rapidly due to the low kinetic energy buffer available, which used to be provided by the rotational inertia of synchronous generators. The impact of rate of change of frequency (ROCOF) on the PLL dynamics and its subsequent influence on the VSC power stage output is explained. The Bonaire island network is presented as case study. The performance of the VSC is analyzed under a fast ROCOF event, which is triggered by a short circuit fault. A down-scaled experiment is used to validate the Bonaire island network simulation results. It shows that the phase angle error measured by the synchronous-reference frame phase-locked loop (SRF-PLL) is proportional to the slope of the ROCOF and inversely proportional to its controller integral gain constant.
Article
Full-text available
Today, conventional power systems are evolving to modern smart grids, where interconnected microgrids may dominate the distribution system with high penetration of renewable energy and energy storage systems. The hybrid AC/DC systems with DC and AC sources/loads are considered to be the most possible future distribution or even transmission structures. For such hybrid AC/DC microgrids, power management strategies are one of the most critical operation aspects. This paper presents an overview of power management strategies for a hybrid AC/DC microgrid system, which includes different system structures (AC-coupled, DC-coupled, and AC-DC-coupled hybrid microgrids), different operation modes, a thorough study of various power management and control schemes in both steady state and transient conditions, and examples of power management and control strategies. Finally, discussion and recommendations of power management strategies for the further research are presented.
Article
Lack of inertia is one problem urgent for the stabil-ity of hybrid ac/dc system. In this paper, a comprehensive inertial control strategy is proposed for stability improvement of the hy-brid ac/dc microgrid. The unified inertia index is introduced to evaluate the holistic inertia level of the hybrid microgrid. Besides, the coupling relationship between ac and dc nanogrid is discussed based on the power balance, which serves as the base of mutual inertial support. The characteristics of distributed generations (DGs) are analyzed, based on which the comprehensive inertial support is designed for various DGs respectively and adaptively divided into two responses: the local support and the cross-grid support. The proposed strategy takes full use of the rotational kinetic energy of wind turbine generator (WTG), and exploits the power capacity of distributed hybrid energy storages (HESs), which improves the global stability and dynamic performance of the hybrid microgrid during power disturbance. The perfor-mance of the proposed control strategy is validated by the simu-lation cases with different operating scenarios.
Article
Hybrid ac-dc microgrid architecture is attracting special attention since it combines the benefits of both ac and dc systems. Control of hybrid microgrid presents a significant research and engineering challenge and hence needs increased research efforts. This paper attempts to review control strategies that are reported in the literature for the hybrid ac-dc microgrid. At first, typical and emerging hybrid microgrid power topologies are presented briefly. Various types of interlinking converters proposed for connecting ac and dc subgrids are discussed subsequently. Following this, a detailed discussion on control strategies for satisfying various control objectives is taken up. Control strategies have been systematically reviewed focusing on each of the broad aspects of control namely modeling, power management, coordinated control, stability analysis, power quality and protection strategies. Finally, the research gaps observed during the review process and possible solution approaches are outlined.
Article
A smart and autonomous integration concept for DC microgrids into the legacy AC grid is proposed based on the Virtual Synchronous Machine (VSM) concept. It utilizes a DC-AC converter as a universal VSM Based Interface (VSMBI) between the AC grid and various Distributed Energy Resources (DER) connected on the DC side. The control strategy of it includes: (1) a frequency regulation improved from previous VSM works, which is suitable for the microgrid integration; (2) an improved dual droop control between the AC frequency and the DC side energy storages; (3) a power system stabilizer to enhance the system stability. Under this concept, the VSMBI integrates the DERs, loads and energy storages in the DC microgrid into a VSM. The VSMBI and the DC microgrid together will respond to short-term and long-term requirements of the grid frequency regulation, and achieve autonomous power management for the AC grid and the DC microgrid. It is therefore an important step forward in supporting high DER penetration. The concept, its design and small-signal analysis are presented in this paper. Its effectiveness and functions are verified by simulation and experimental results.
Article
In a DC microgrid (DC-MG), the dc bus voltage is vulnerable to power fluctuation derived from the intermittent distributed energy or local loads variation. In this paper, a virtual inertia control strategy for DC-MG through bidirectional grid-connected converters (BGCs) analogized with virtual synchronous machine (VSM) is proposed to enhance the inertia of the DC-MG, and to restrain the dc bus voltage fluctuation. The small-signal model of the BGC system is established, and the smallsignal transfer function between the dc bus voltage and the dc output current of the BGC is deduced. The dynamic characteristic of the dc bus voltage with power fluctuation in the DC-MG is analyzed in detail. As a result, the dc output current of the BGC is equivalent to a disturbance, which affects the dynamic response of the dc bus voltage. For this reason, a dc output current feed-forward disturbance suppressing method for the BGC is introduced to smooth the dynamic response of the dc bus voltage. By analyzing the control system stability, the appropriate virtual inertia control parameters are selected. Finally, simulations and experiments verified the validity of the proposed control strategy.
Article
In this paper, autonomous control strategies are proposed for Photovoltaic (PV) and battery units operating in a droop-controlled islanded microgrid. Based on the proposed strategies, the PV and battery units can be deployed independently in any droop-controlled microgrid. Both the PV unit and the battery unit are controlled as voltage sources that follow multisegment adaptive power/frequency ( ) characteristic curves. These characteristic curves are adjusted locally in real time based on the available PV power, load demand, and the state of charge of the battery to autonomously coordinate the operation of these units and maintain the power balance in the microgrid. The strategy proposed for the battery unit enables it to autonomously supply power only during peak load periods, to support the droop-controlled units and maintain the power balance in the islanded microgrid. The control strategies are implemented in each unit using multi-loop controllers, without relying on communication, a central management algorithm, or switching logic. Small signal models of the proposed control loops are presented, and the performance of the proposed strategy is validated using simulation and also through experiments on a 3-kVA prototype microgrid.
Article
In comparison of the conventional bulk power plants, in which the synchronous machines dominate, the distributed generator (DG) units have either very small or no rotating mass and damping property. With growing the penetration level of DGs, the impact of low inertia and damping effect on the grid stability and dynamic performance increases. A solution towards stability improvement of such a grid is to provide virtual inertia by virtual synchronous generators (VSGs) that can be established by using short term energy storage together with a power inverter and a proper control mechanism. The present paper reviews the fundamentals and main concept of VSGs, and their role to support the power grid control. Then, a VSG-based frequency control scheme is addressed, and the paper is focused on the poetical role of VSGs in the grid frequency regulation task. The most important VSG topologies with a survey on the recent works/achievements are presented. Finally, the relevant key issues, main technical challenges, further research needs and new perspectives are emphasized.
Article
Modular generation system, which consists of modular power conditioning converters, is an effective solution to integrate renewable energy sources with conventional utility grid to improve reliability and efficiency, especially for photovoltaic generation. A distributed control strategy based on improved dc bus signaling is proposed for a modular photovoltaic (PV) generation system with battery energy storage elements. In this paper, the modular PV generation system is composed of three modular dc/dc converters for PV arrays, two grid-connected dc/ac converters, and one dc/dc converter for battery charging/discharging and local loads, which is available of either grid-connected operation or islanding operation. By using the proposed control strategy, the operations of a modular PV generation system are categorized into four modes: islanding with battery discharging, grid-connected rectification, grid-connected inversion, and islanding with constant voltage (CV) generation. The power balance of the system under extreme conditions such as the islanding operation with a full-charged battery is taken into account in this control strategy. The dc bus voltage level is employed as an information carrier to distinguish different modes and determine mode switching. Control methods of modular dc/dc converters, battery converter, and grid-connected converter are addressed. An autonomous control method for modular dc/dc converters is proposed to realize smooth switching between CV operation and maximum power point tracking operation, which enables the dc bus voltage regulation capability of modular dc/dc converters. Seamless switching of a battery converter between charging and discharging and that of a grid-connected converter between rectification and inversion are ensured by the proposed control methods. Experiments verify the practical feasibility and the effectiveness of the proposed control strategies.