Residential dual core energy recovery ventilation system for ventilation of northern housing

Authors:

Abstract and Figures

Heat/energy recovery ventilation systems are types of HVAC that can reduce energy consumption and improve the ventilation rate of housing in cold climates. Their performance achieved to date has been inadequate due to equipment failures (freezing of cores, noise, etc.). Freezing of cores is common in extremely cold climates. Single core HRV/ERV units are usually equipped with defrost strategies such as recirculation of exhaust stale air across the heat exchanger and back into the supply air to the house. These defrost strategies can undermine ventilation standards (ventilation rate requirement not being met during recirculation). This paper presents a rigorous investigation on the performance of dual core energy recovery system that provided a continuous ventilation rate at outdoor temperatures below -10°C without frost protection. The dual core ERV had higher apparent sensible effectiveness (up to 12% more) and apparent total effectiveness (up to 9% more) than a conventional single core ERV. It showed no sign of frost problems after four weeks of winter testing, continuously provided outdoor air without stopping to defrost, unlike the conventional single core ERV which required up to 7.5 hours defrosting per day, and also provided a higher supply air temperature (up to 3°C) to indoors with a total whole-house energy saving of 4.7%.
Content may be subject to copyright.
IOP Conference Series: Materials Science and Engineering
PAPER • OPEN ACCESS
Residential dual core energy recovery ventilation system for ventilation
of northern housing
To cite this article: B Ouazia et al 2019 IOP Conf. Ser.: Mater. Sci. Eng. 609 052017
View the article online for updates and enhancements.
This content was downloaded from IP address 158.46.163.51 on 23/10/2019 at 18:28
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution
of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.
Published under licence by IOP Publishing Ltd
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
1
Residential dual core energy recovery ventilation system for
ventilation of northern housing
B Ouazia1,*, D. Won1, C Arsenault1, Y Li1
1 National Research Council Canada, Ottawa, Ontario, Canada
* Boualem.ouazia@nrc-cnrc.gc.ca
Abstract. Heat/energy recovery ventilation systems are types of HVAC that can reduce energy consumption
and improve the ventilation rate of housing in cold climates. Their performance achieved to date has been
inadequate due to equipment failures (freezing of cores, noise, etc.). Freezing of cores is common in extremely
cold climates. Single core HRV/ERV units are usually equipped with defrost strategies such as recirculation of
exhaust stale air across the heat exchanger and back into the supply air to the house. These defrost strategies can
undermine ventilation standards (ventilation rate requirement not being met during recirculation). This paper
presents a rigorous investigation on the performance of dual core energy recovery system that provided a
continuous ventilation rate at outdoor temperatures below -10°C without frost protection. The dual core ERV had
higher apparent sensible effectiveness (up to 12% more) and apparent total effectiveness (up to 9% more) than a
conventional single core ERV. It showed no sign of frost problems after four weeks of winter testing,
continuously provided outdoor air without stopping to defrost, unlike the conventional single core ERV which
required up to 7.5 hours defrosting per day, and also provided a higher supply air temperature (up to 3°C) to
indoors with a total whole-house energy saving of 4.7%.
1. Introduction
The extremes of the Arctic climate pose severe challenges on housing ventilation and heating systems.
In the Arctic and northern regions of Canada, the average temperature during winter is -25°C or
below, and many northern homes are heated to above 25°C resulting in significant loads on systems
(Zaloum, 2010). As a part of the overall effort to reduce space heating requirements, homes are built
air tight to reduce infiltration or exfiltration heat losses. However, airtight homes require energy
efficient, effective and resilient ventilation systems to maintain acceptable indoor air quality and
comfort, and to protect the building envelope from moisture damage. A balanced mechanical
ventilation system with heat or energy recovery is an ideal way to meet both National Building Code
[1] and the ventilation requirements of standards [2, 3]. Heat recovery ventilation (HRV) and energy
recovery ventilation (ERV) are well-known and effective methods to improve energy and ventilation
efficiency of residential heating, ventilating and air conditioning (HVAC) systems when designing
energy efficient homes, because they allow adequate outdoor ventilation air without excessive energy
consumption. The performance of the conventional single core HRV/ERV units achieved to date has
been inadequate due to equipment failures and conventional problems created by the formation of frost
in heat exchangers. Freezing of cores can cause partial or full blockage of air flow passages, increased
pressure drop through the heat exchanger or decreased airflow rate, increased electrical power
consumption for the fans, decreased heat transfer rate between the two airstreams, and cold draughts
within the space due to low supply air temperatures [4]. Conventional single core HRV/ERV units are
usually equipped with frost protection systems such as pre-heating of outdoor air or recirculating of
return air across the heat exchanger and back into the supply air to the house. These defrost strategies
can undermine ventilation standards (ventilation rate requirement not being met) and the energy
saving of the HRV or ERV unit. Surveys conducted in Canada’s North found that at present, there are
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
2
no HRVs/ERVs specifically designed, manufactured and certified to meet rigorous requirements for
operation in the North [5]. This paper presents some results from a project employing an innovative
dual core design heat/energy recovery system and its applicability for housing in the Arctic. One
alternative technology that can overcome problems faced by conventional single core HRV/ERV units
installed in extreme cold climates is a dual core ERV unit designed to address frost protection
concerns and provide continuous ventilation.
2. Method
The rigorous methodology used in this investigation included the following evaluation steps:
Laboratory evaluation using two climatic chambers to simulate indoor and outdoor conditions
identified by a certification standards and those identified in the North,
Side-by-side testing using twin research houses to compare whole-building performance between a
reference house equipped with a single core ERV and a test house equipped with a dual core energy
recovery unit, and
Extended performance and resiliency testing in a real northern environment, with representative
climate and occupied loads.
However, this paper presents some results from the side-by-side testing using the CCHT twin houses.
2.1. Description of the dual core ERV
A dual core ERV unit comes equipped with a regenerative cyclic dual core heat exchanger, based on
the cyclic storage and release of heat in the corrugated plates alternately exposed to exhaust and intake
air. It includes a supply and exhaust fan and two plate heat exchangers, which act as heat
accumulators. In between the cores is a patented damper section which changes over every 60 seconds
to periodically direct warm air through one of the two cores while outside air gains heat from the
heated plates in the other core. In front of each fan is a filter section to filter the air. The schematic of
the dual core unit is presented in Figure 1, where OA is the outdoor air, EA is the exhaust air to
outdoor, RA is the return air from indoor and SA is the supply air to indoor. The description of the two
sequences of the unit is as follow. During Sequence 1, exhaust air charges Core B with heat from
exhausted warm air from indoors and Core A discharges heat to the supply air: During Sequence 2 the
exhaust air charges Core A with heat from exhausted warm air from indoors and Core B discharges
heat to the supply air. The damper is controlled by two internal thermostats (thermostat 1 in the supply
air is set to 15°C and thermostat 2 in the exhaust air is set to 20°C) to ensure that comfortable air
delivery temperatures are achieved under all conditions. When the exhaust air temperature is below
20°C, the unit runs in energy recovery mode (cycling every 60 seconds). When the exhaust air
temperature is above 20°C and the supply air temperature is higher than 15°C, the unit runs in free
cooling mode (cycling every 3 hours). Finally, when the exhaust air temperature is above 20°C and the
supply air temperature is below 15°C, the unit runs in energy recovery mode until the supply air
temperature exceeds 15°C, at which point it will revert to free cooling mode.
Figure 1. Principle of function – sequence 1 (left) and sequence 2 (right)
2.2. Side-by-side testing
The Canadian Centre for Housing Technology’s (CCHT) twin research houses shown in Figure 2 (left)
were used for the comparative side-by-side testing between a dual core ERV (installed in the test
house) and a conventional single core ERV (installed in the reference house). These houses are typical
OA RA EA
SA
EA RA OA
SA
A
B
AB
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
3
2-storey wood-frame houses with their characteristics presented in Figure 2 (right). The twin-house
research facility features a “simulated occupancy system”. The simulated occupancy system, utilizes
home automation technology to simulate human activity by operating major appliances (stove,
dishwashers, washer and dryer), lights, water valves, fans, and other sources simulating typical heat
gains. The schedule is typical of activities that would take place in a home with a family comprised of
two adults and two children. Electrical and water consumption are typical for a family of four. The
heat given off by humans is simulated by two 60 W (2 adults) and two 40 W (2 children) incandescent
bulbs at various locations in the house. The CCHT research houses are equipped with a data
acquisition system (DAS) consisting of over 250 sensors and 23 metering devices (gas, water and
electrical). A computer reads the sensors every 5 minutes and provides hourly averages. Meter data
and a few other measurements are recorded on a 5 minute-basis. The DAS captures a clear history of
the house performance in terms of temperature, humidity and energy consumption.
Figure 2. CCHT twin houses (left) and their characteristics (right)
The side-by-side testing involved first benchmarking the houses for set operating conditions and
simulated occupancy, using existing high efficiency single core ERVs originally installed in each
house. The test house was modified by installing the dual core ERV unit in the basement and making
no other modifications to the house, then programing the dual core unit to match the single core ERV
supply and exhaust airflows in the reference house. Finally, whole-house performance was monitored
for four weeks during the 2019 heating season.
2.3. Performance evaluation
The performance of the innovative dual core ERV unit was primarily determined by its apparent
sensible effectiveness (ASE) and apparent total effectiveness (ATE) as described in ASHRAE testing
standard [6] and Canadian testing standard [7], airflow characteristics, supply air temperature, frosting
occurrence and whole-house energy consumption. The measured temperatures and relative humidities
across the tested unit were used to calculate the ASEs and ATEs. The ASE and ATE were calculated
using Equation 1.
=()
( ) (1)
where, ɛ is the sensible, latent, or total heat effectiveness. X is either the dry-bulb temperature, T,
humidity ratio, w, or total enthalpy, h, respectively, at the supply inlet and outlet and at the exhaust
inlet of the unit. ms is the mass flow rate of the supply and mmin is the minimum value of either mass
flow rate of the supply or mass flow arte of the exhaust.
3. Results and discussion
This section compares the operation of the two houses, the Reference House incorporating a single
core ERV and the Test House incorporating a dual core ERV in terms of ventilation rate (airflows),
sensible and total efficiencies of the ERV units, supply air temperature from the ERV units, and total
energy consumption for heating and ventilating both houses.
3.1. Ventilation
The typical daily single ERV and dual core ERV supply and exhaust airflows are presented in Figure 3
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
4
for a cold day with an outdoor temperature below -10°C (January 17th 2019). The plot of the single
core ERV airflows excluded the defrost cycle as shown on the left plot of Figure 3. Both single and
dual core ERVs presented balanced supply and exhaust flows. The dual core ERV showed no sign of
frost problems and continued to provide outdoor air throughout a cold testing day (outdoor
temperature ranging between -20.1°C and -11.8°C) without stopping to defrost, unlike the single core
ERV that had to spend hours defrosting as shown in the plot on the left side of Figure 3.
Figure 3. Measured airflows from side-by-side testing, Reference House (left) and Test House (right)
The single core ERV uses a defrosting method presented in Table 1. The amount of time the single
core ERV spent in defrost mode (“defrost time”) per day during the winter test period is presented in
Figure 4 along with the minimum and mean outdoor temperatures. The duration of the de-icing cycle
is strongly dependent on outdoor temperature. The single core ERV spent between 0 and 7.5 hours per
day defrosting, during which time it did not provide fresh air to the reference house. Due to its design,
the dual core ERV did not require defrosting, and provided fresh air continuously throughout the
winter test period. The frequent defrost cycles of the single core ERV led to a reduced volume of
outdoor air being delivered to the reference house, leading to under ventilation of the reference house
(compared to the test house), and it not meeting the ventilation requirement. This is a common
situation for single core HRV/ERV units installed in extremely cold climates.
Table 1. Defrosting method
Outside Temperature
[°C]
Defrost Cycle
Defrost [min] / Operating [min]
Warmer than -10
No Defrost
-10 to -27
7 / 25
-27 and less
10 / 22
Figure 4. Daily single core ERV defrost time during winter 2019 testing
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
5
3.2. Effectiveness
The calculated ASE and ATE of a single core ERV and dual core ERV using data obtained from the
side-by-side testing in the CCHT twin houses are presented in Figure 5 and Figure 6. The calculated
ASE of the dual core ERV (installed in the test house) had a mean value of 85.1% and ranged from
63.2% to 99.4%. The single core ERV (installed in the reference house) had a mean value of ASE of
73.2% during the same testing period of four weeks and ranged from 62.3% to 94.2%, a mean
difference over reference house of 12 percentage points. The ATE, which takes into account the latent
heat of the single core ERV, varied between 58.4% and 91.4%, with a mean value of 69.9%. The dual
core ERV unit had an ATE between 64.16% and 98.9%, with a mean value of 79.1%, a mean
difference over the reference house of 9 percentage points. These results show clearly that the dual
core ERV unit over perform the conventional single core ERV in terms of sensible and totale
efficiencies.
Figure 5. Calculated apparent sensible efficiencies
Figure 6. Calculated apparent total efficiencies
3.3. Supply air temperature
The temperature of the supply air from the single and dual core units to indoors (to return air plenum
upstream of the furnace) measured during the side-by-side testing (January 17 to February 12, 2019)
are presented in Figure 7 with the measured outdoor temperature. The supply outlet air temperature
from the single core ERV in reference house varied between 7.5°C and 18.8°C and the test period
mean value was 13.5°C. The supply outlet air temperature from the dual core ERV in test house varied
between 9.9°C and 19.8°C and the mean value over the same testing period was 16.1°C. The mean
temperature of the supplied air to the house was higher by 2.6°C from the dual core ERV than the
single ERV. This was due to the much higher ASE of the dual core unit (higher than 80%) from
regenerative cyclic dual cores. The supply air to the test house required less tempering by the furnace
IAQVEC
IOP Conf. Series: Materials Science and Engineering 609 (2019) 052017
IOP Publishing
doi:10.1088/1757-899X/609/5/052017
6
to meet the thermostat set point of 22°C, which means that a dual core unit provided more pre-heating
than a single core ERV and would lead to additional energy savings.
Figure 7. Measured supply air temperature from side-by-side testing
3.4. Energy
Changes in whole-house energy performance due to the innovation were addressed through
comparison of the test house performance (with dual core ERV) to that of the reference house (with
single core ERV). The recorded whole-house energy consumption of both reference house and test
house included; heating energy consumption (furnace natural gas consumption), furnace fan electrical
consumption, single core ERV fan electrical consumption and dual core ERV fan electrical
consumption. The expected test house energy consumption in benchmark configuration (i.e. operating
the benchmark ERV equipment, both houses with single core ERV) was first calculated, and from this
the overall energy savings when the dual core ERV system was operating in the test house was
calculated. Savings were calculated by subtracting the measured test house (with dual core ERV0
experiment consumption from the calculated test house (with single core ERV) benchmark
consumption. The average energy saving when operating the dual core ERV compared to the
benchmark ERV over the period of the study was 4.7%.
4. Conclusion
In comparison with conventional single core ERV, the dual core ERV designed with two parallel
regenerative heat exchangers and a controlled cycling damper had higher ASE and ATE from side-by-
side testing than the single core ERV. It was more frost-tolerant, showing no signs of frost problems,
and was capable of withstanding an outdoor temperature down to -23°C without degrading its thermal
performance, and provided a continuous supply of outdoor air without stopping to defrost, unlike the
conventional single core ERV which spent many hours defrosting during cold days of the side-by-side
testing. The dual core technology was capable of providing air at the supply outlet at a temperature
2.6°C higher than the air temperature supplied by a single core ERV. Its incorporation into the test
house showed a saving in heating and ventilation energy consumption of approximately 4.7% (24.6
MJ/day). The project demonstrated that a dual core ERV is a viable solution for northern housing.
References
[1] National Building Code of Canada (NBCC) 2015
[2] ANSI/ASHRAE 62.2 2013 ASHRAE Atlanta, GA
[3] CAN/CSA F-326 2013 National Standard of Canada CAN/CSA-F326-M91
[4] Rafati Nasr M, Fauchoux M, Besant R W and Simonson C J 2014 Renew. Sustain. Energy Rev.
30 538-554
[5] CMHC Survey 2017 Canadian Mortgage and Housing Corporation Research Report
[6] ANSI/ASHRAE Standard 84 2013 ASHARE Atlanta GA
[7] CAN/CSA-C-439-09 2010 Canadian Standard Association
... 17,18 It is well-known that the system is capable of transferring both sensible and latent heat from the incoming fresh air to the outgoing air. This system also aids in reducing the ventilation load of the airconditioning unit in the hot and humid environment, 19 which is associated with the system load when fresh outdoor air is moved towards the return-side of the unit. The energy recovery system also helps to lessen the airconditioning thermal load, which is the demand for heat energy needed for space cooling by dehumidifying the incoming air. ...
... 41 ε tot denoted a similar tendency to ε lat , due to the mass transfer is leading over the heat transfer. 19 The latent efficiency of the system depended on the capability of the hydrophilic polymeric membrane-based material to transport water vapour. This is related to the moisture diffusive resistance capacity in allowing the water molecules diffuse through it, which is influenced by the membrane material, temperature and humidity difference. ...
Article
An analysis of the performance of a fixed‐plate air‐to‐air energy recovery system on its efficiency and recovered energy for potential building applications in the hot and humid environment was performed. Investigations were executed under controlled laboratory conditions in an energy testing chamber. Tests were carried out with varying operating parameters in terms of airflow rates that ranged from 1.0 to 3.0 m/s, intake air temperature of 28°C, 31°C, 35°C, 40°C and intake relative humidity of 70%, 75% and 80%. The performance was analysed by adopting the calculation methods of the ASHRAE Standard. This study showed that increased airflow rate decreased efficiency. The increase of airflow rate raised the recovered energy of the system. The study indicated that increasing values of intake air temperature (Tin) resulted in the increase of efficiency and recovered energy. A decrease in the efficiency of the system was observed, notably when the intake relative humidity (RHin) increased.
Chapter
The usage of energy recovery systems continues to increase the acceptance and use of mechanical ventilation systems in construction. They are designed to provide energy savings by recycling or recovering about 70% of energy from the building’s exhaust air to pre-treat or pre-condition the outside air/ventilation air. The load and the mechanical ventilation equipment may be minimised by pre-treatment or pre-conditioning of the outside air. It has increased interest in and economic applications of energy recovery technology. Energy recovery systems can be used for both new and retrofit applications. The general rule for pre-treatment or pre-condition of outside air/ventilation air in energy recovery systems is that the reduction of 2.3 metric tons of the mechanical ventilation unit for each 1000 ft³/min of outdoor/ventilation air operated by an energy recovery system. This chapter addresses applications of energy recovery systems under different types of buildings and climatic conditions.
  • Rafati Nasr
  • M Fauchoux
  • M Besant
  • R Simonson
Rafati Nasr M, Fauchoux M, Besant R W and Simonson C J 2014 Renew. Sustain. Energy Rev. 30 538-554
Canadian Mortgage and Housing Corporation Research Report
CMHC Survey 2017 Canadian Mortgage and Housing Corporation Research Report