1SDC007103G0202
December 2006
4Technical Application Papers
ABB circuit-breakers
inside LV switchboards
1
Index
ABB circuit-breakers inside LV switchboards

Introduction ..............................................2
1 Problems of overheating
inside switchboards
1.1 General aspects ......................................3
1.2 The current carrying capacity ................. 3
1.3 Verification of temperature-rise
by test (in compliance with
IEC 60439-1) ...........................................4
1.4 Verification of temperature-rise by
extrapolation ...........................................7
2 Advices to improve the
current carrying capacity of
the circuit-breakers inside
switchboards
2.1 Power loss inside switchboards .............9
2.1.1 Internal structure .................................................. 9
2.1.2 Tipology of the circuit-breaker installed ............... 9
2.1.3 Cross-section of conductors within
switchboards ......................................................11
2.1.4 Paths of the current ...........................................15
2.2 Dissipation of the heat generated
inside switchboards ..............................16
2.2.1 Switchboard ventilation ......................................16
2.2.2 Side surfaces and positioning of switchboards .....16
2.2.3 Forms of internal separation of switchboards ....17
2.2.4 Switchboard protection degree .......................... 17
2.3 Dissipation of the heat generated in the
terminals ..............................................17
2.3.1 Problems linked to convection ..........................17
2.3.2 Problems linked to conduction ..........................20
2.3.3 Current carrying capacity of circuit-breakers
and busbars ...................................................... 22
3 Problems concerning short-
circuit
3.1 Main definitions of the parameters
characterizing a switchboard under
short-circuit conditions .........................39
3.1.1 General prescriptions and information about
short-circuit withstand strength .........................39
3.2 Prescriptions concerning the electrical
circuits of a switchboard .......................40
3.2.1 Main busbar systems .........................................40
3.2.2 Distribution busbars and conductors derived by
the main busbars ................................................41
3.3 Reduction of the possibility of short-circuit
events and of the relevant effects ......... 42
3.3.1 Minimum anchor distances for conductors ........ 42
3.3.2 Verification of the short-circuit withstand strength
and of the current limiting characteristics of the
circuit-breakers ...................................................45
3.3.3 Problems concerning the installation distances 46
Annex A:
Example of electrical switchboards with ABB
circuit-breakers ..................................................... 48
Annex B:
Forms of internal separation ................................. 50
Annex C:
Degrees of protection (IP code) ............................. 51
Glossary ................................................................ 52
2ABB circuit-breakers inside LV switchboards

Introduction
An electrical switchboard is the combination of more
protection and switching devices assembled in one or
more adjacent compartments.
A switchboard is formed by the compartment, which
the Standards name “enclosure” (with support and
mechanical protection functions for the different
components enclosed), and the electrical equipment,
constituted by the apparatus, the internal connections
and the incoming and outgoing terminals for the
connection to the installation.
This Technical Paper is intended to deal in detail with the
equipment in the switchboard, providing the reader with
the basic information necessary to choose the circuit-
breakers to be installed inside low voltage switchboards
in the easiest and most correct way, paying particular
attention to ABB SACE range of products.
After a quick survey of the main product Standards
concerning switchboards and circuit-breakers, IEC
60439-1 and IEC 60947-2 respectively, the main
problems which a manufacturer has to face when
designing a switchboard are analyzed.
This Technical Paper is divided into three main parts
dealing with the problems of overheating in switchboards,
general prescriptions to improve the current carrying
capacity of the circuit-breakers inside enclosures and the
problems caused by short-circuit in switchboards
1 Introduction
1 The product Std. IEC 60439-1 applies to low voltage and controlgear assemblies, the
rated voltage of which does not exceed 1000 Va.c. at frequencies not exceeding 1000 Hz,
or 1500 Vd.c.; the product Std. IEC 60947-2 applies to circuit-breakers, the main contacts
of which are intended to be connected to circuits, the rated voltage of which does not
exceed 1000 Va.c. or 1500 Vd.c.
3
ABB circuit-breakers inside LV switchboards
1 Problems of overheating inside switchboards
1 Problems of overheating inside switchboards
1.1 General aspects
One of the main problems which makes difficult the
identification of the correct typology of circuit-breakers to
be installed inside a switchgear or controlgear assembly
is calculating the maximum continuous current which the
circuit-breaker can carry without damages or premature
ageing according to the service temperature.
The total freedom of the manufacturer in designing
switchboards using components different for number,
position and dimensions makes the installation conditions
of the same circuit-breaker so different that it results
impossible to determine exactly its “maximum current
carrying capacity” which, affected by peculiar operating
conditions, results different from that defined by the
manufacturer and referred to standard conditions.
1.2 The current carrying capacity
Now we shall take into consideration how the concept
of current carrying capacity is dealt with in the different
Standards, in particular, in the product Standard
concerning circuit-breakers and in that one regarding
low-voltage switchgear and controlgear assemblies.
The circuit-breakers, according to the prescriptions of the
European Low Voltage Directive 2006/95/CE (ex 73/23
CE std.), are manufactured and tested in compliance with
the product Std. IEC 60947-2 “Low-voltage switchgear
and controlgear – Part 2: Circuit-breakers”.
As regards the verification of the current carrying capacity
in uninterrupted duty (Iu), the Std. IEC 60947-2 states the
conditions of the test performance. Here are the main
requirements to be met :
- the current carrying capacity shall be verified in free-air
the Std. IEC 60947-1 “Low-voltage switchgear and
controlgear - Part 1: General rules” specifies in detail
what is meant by “free air”:
“Free air is understood to be air under normal indoor
conditions (indoor conditions are understood to be
not the conditions inside switchgear or controlgear
assemblies or enclosures, but the conditions inside
buildings or similar environments), reasonably free from
draughts and external radiation”
therefore, no external radiations (e.g. those due to the
sun’s rays-Figure 1) or draughts which are not caused
simply by the natural convective motion originated by
heating (Figure 1a) are admitted.
Figure 1 Figure 1a
- the carrying capacity is verified by connecting
the circuit-breakers with conductors having size
(maximum) and length (minimum) as specified in
the relevant Standard
this means that the standard conditions are referred also
to the connection modalities of the circuit-breaker
- the carrying capacity is verified by ensuring that
during the test, the maximum temperature-rise
limits admitted on the different parts of the circuit-
breaker are not exceeded
such temperature-rise, not meant as absolute temperature,
but as a temperature difference expressed in Kelvin, are
referred to an ambient air temperature of 40°C.
The circuit-breakers are generally installed inside
enclosures which have different functions; among these
the following :
- making inaccessible to people the connections of the
different apparatus (if not for voluntary actions);
- giving a place to house the circuit-breakers where
steady positioning is guaranteed;
- ensuring an adequate protection against ingress of
solid foreign objects and ingress of water.
These enclosures are called controlgear and switchgear
assemblies (hereafter referred to as assemblies) and
comply with the specific product Std. IEC 60439-1 “Low-
voltage switchgear and controlgear assemblies – Part 1:
Type-tested (TTA) and partially type-tested assemblies
(PTTA)”
However, the installation conditions inside an assembly
differ from the conditions specified by the Std. IEC
60947-2, which are the verification conditions of a circuit-
breaker current carrying capacity in free air.
The conditions inside the switchboard (wiring, separations,
arrangement of the different apparatus) force the circuit-
breaker to operate under conditions characterized by the
following aspects:
4ABB circuit-breakers inside LV switchboards

1 Problems of overheating inside switchboards
- not in free air, but with particular prescriptions re-
garding air circulation
in particular, it is possible to have assemblies with
complex forms of internal separations (Figure 2), or
assemblies with forced ventilation or air-conditioned
assemblies
Figure 2
- the circuit-breakers are connected through
conductors of size and length stated by the
manufacturer
- with an air ambient temperature around the circuit-
breaker depending on the assembly design and on
the devices it houses.
In particular, the different degree of protection and
the modality of arrangement of the assembly in the
environment cause a modification of the amount of heat
exchanged towards the outside of the assembly and,
consequently, also of the air temperature inside it.
After these considerations, it is evident that the conditions
leading the manufacturer to define a rated uninterrupted
current for a single circuit-breaker are different from the
conditions under which the circuit-breaker shall be used
inside an assembly; as a consequence, it is obvious
that the current carrying capacity of circuit-breakers
determined in compliance with the relevant product
Standard cannot be considered equal to their carrying
capacity when they are installed inside an assembly,
without the appropriate evaluations.
This concept is also recalled in the Std. IEC 60947-1, which
in the performance prescriptions regarding temperature-
rise, states that in normal service the current carrying
capacities may differ from the test values, depending,
for example, on the different installation conditions and
on the size of the connected conductors.
Besides, also the Std. IEC 60947-2, relevant to the low
voltage circuit-breakers, as regards the general test
conditions, reminds that the prescribed tests do not
preclude the need for additional tests on circuit-breakers
incorporated in assemblies, for example in accordance
with IEC 60439-1.
1.3 Verification of temperature-rise by test
(in compliance with IEC 60439-1)
The product Std. IEC 60439-1 concerning low voltage
controlgear and assemblies does not refer to the indivi-
dual components present, but to the “equipment” meant
as a combination of one or more protection and switching
apparatus equipped with any possible switching, mea-
suring, protection and setting, mounted and wired with
internal electrical and mechanical connections.
As a consequence, making reference to the current
carrying capacity, this Standard deals with the rated
current of the single electrical circuit and not with the
rated current of the individual components, such as
circuit-breakers or conductors. In accordance with the
definition, the rated current of a circuit is defined by the
switchboard manufacturer as a function of the ratings of
the electrical components of the circuit, of their disposi-
tion and application.
This current shall be carried without the temperature-rise
of the various parts of the assembly exceeding the limits
specified when the test is performed in accordance with
prescriptions of the Standard itself.
The performance modalities of the temperature-rise test
include two main prescriptions:
- the circuits of the switchboard shall be tested at a cur-
rent which is equal to the rated current multiplied by the
rated diversity factor fn, understood as the ratio between
the maximum value of the sum of the currents flowing
through all the main circuits considered, at any moment,
and the sum of the rated currents of the same circuits
Itest = InC x fn
- if no d etailed information about the external conductors
to be used under normal operating conditions are known,
cross-sections depending on the rated current of the
circuits are imposed by the Standard.
For further information about correlated subjects, re-
ference shall be made to the indications given in the
Standard itself.
From the prescriptions above it results that:
- if a rated diversity factor fn<1 is present (not all the
loads are supplied with 100% of their rated current) the
switchboard circuits are tested at a current value lower
than the rated one at full load; however, the test shall be
carried out on those circuits which allow the heaviest
temperature-rise conditions to be reproduced;
- if the switchboard is cabled with conductors having a
cross-section reduced with respect to that prescribed
5
ABB circuit-breakers inside LV switchboards
1 Problems of overheating inside switchboards
by the Standard and used in the test, temperature-rise
higher than the maximum acceptable values measured
in the test might occur during normal operations.
The following numerical example has the purpose of
making clear what explained above. Reference is made
to the switchboard of Figure 3, whose loads are cabled
with the same conductors through which it is put into
service; the manufacturer assigns the rated current for
the load circuits and assigns a rated diversity factor “fn”
to the enclosure to be tested. Under these conditions, the
switchboard, or a part of the switchboard, is tested by
“applying” simultaneously to all the circuits a test current
equal to the assigned rated current multiplied by “fn”.
I2 = 160A fn=0.8 I2test= 128A
I3 = 400A fn=0.8 I3test = 320A
I4 = 250A fn=0.8 I4test = 200A
I5 = 630A fn=0.8 I5test = 504A
I6 = 160A fn=0.8 I6test = 128A
I7 = 400A fn=0.8 I7test = 320A
Figure 3
Therefore, in a switchboard, the rated current of a circuit
is not that assigned, but it is determined by considering
the assigned diversity factor. In accordance with these
test conditions, the absolute temperature values TT
(expressed in °C) at which the different parts of the
assembly operate are determined and, with reference to
an average ambient temperature TA lower than or equal to
35 °C, the temperature-rise limits ΔT = (TT – TA) imposed
by the Std. IEC 60439-1 must not be exceeded.
For the different components of assemblies, Table 1
below shows the temperature-rise limits and the relevant
remarks of the Std. IEC 60439-1 (updating of Annex A1
dated March 2005) which are valid when the temperature-
rise test is carried out in compliance with the prescriptions
of the Standard itself.
Table 1
Parts of assemblies
Temperature-rise
(values or prescriptions)
Built in components
For example conventional switchgear
and controlgear; electronic sub-
assemblies (e.g. rectifier bridge and
printed circuit); parts of equipment
(e.g. regulator, stabilized power
supply unit, operational amplifier).
In accordance with the relevant
requirements for the individual com-
ponents, or in accordance with the
manufacturer’s instructions, taking
into consideration the temperature
in the assembly.
Terminals for
external insulated conductors
70K
An assembly used or tested under
installation conditions may have
connections, the type, nature and
disposition of which will not be the
same as those adopted for the test
and a different temperature rise of
terminals may result and may be
required or accepted.
When the terminals of the built-in
components are also the terminals
for the external insulated conductors
the lowest temperature-rise limits
shall be applied.
Busbars and conductors,
plug-in contacts of removable
or withdrawable parts which
connect to busbars
Limited by:
- mechanical strength of conducting
material;
- possible effects on adjacent
equipment;
- permissible temperature limit of
the insulating materials in contact
with the conductor;
- the effect of the temperature of
the conductor on the apparatus
connected to it;
- for plug-in contacts, nature and
surface treatment of the contact
material.
By assuming that all the other
mentioned criteria have been
fulfilled, a maximum temperature of
105K shall not be exceeded for bare
busbars and copper conductors
so that the mechanical strength of
conducting material is guaranteed.
Manual operating means:
accessible with closed assembly
of metal 15K
of insulating material 25K
accessible with open assembly
of metal 40K
of insulating material 50K
Accessible external enclosures and covers:
which need to be touched during normal operation
of metal 30K
of insulating material 40K
which need to be touched during normal operation
of metal 40K
of insulating material 50K
Discrete arrangements of plug
and socket type connection
Determined by the limits of those
components of the equipment of
which they form part.
Circuit-breakers can be defined as built-in components
and therefore they must comply with the prescriptions
of the product Standards. However, it is evident that
I1
IG I2
I3
I4
I5
I6
I7
C
B
D
E
A
6ABB circuit-breakers inside LV switchboards

1 Problems of overheating inside switchboards
Table 2
circuit-breakers and in particular some parts of them
(e.g. accessible parts and operating means) can be
also considered in all respects as part of controlgear
or switchgear assemblies. In particular this applies to
the terminals where external insulated conductors are
connected, which, in accordance with the comments
reported in Table 1, must comply with the most
demanding or restricting prescription of the two product
Standards.
To make clear this concept, Table 2 and figure 4 hereunder
show the indications concerning temperature-rise limits
given in the Std. IEC 60947-2 for circuit-breakers
considered as an individual component in free-air.
Parts of assemblies-
description
Temperature-rise
limits
Temperature limits
(starting from
TA =40°C)
Terminals 80K 120 °C
Manual operating means:
parts of metal 25K 65 °C
parts of insulating material 35K 75 °C
Parts intended to be touched but not gripped:
parts of metal 40K 80 °C
parts of insulating material 50K 90°C
Parts which need not to be touched during normal operation:
parts of metal 50K 90°C
parts of insulating material 60K 100°C
Figure 4
From Table 2 it results how for a circuit-breaker in free-
air the accepted temperature-rise on the terminals is
T=80K; therefore, taking as reference an ambient
temperature TA = 40°C, it can be deduced that the
maximum permissible temperature is TT = (T + TA) =
120°C.
The prescriptions regarding temperature-rise defined
by the switchboard Standard instead refer to an
average ambient temperature TA = 35°C; the maximum
temperature-rise limit of the switchboard terminals for
insulated external connections is 70K and consequently
the maximum operating temperature is 105°C.
If the circuit-breaker is installed inside a switchboard,
a reference ambient temperature of 35°C shall be
considered, and Table 1, with the comments reported for
the built-in components (circuit-breakers are components
of the switchboard), allows the manufacturer to state for
the circuit-breaker terminals a maximum temperature of
120°C; thus, by difference, it can be obtained that the
maximum temperature-rise limit is equal to 85K.
When the connection to the terminals is realized through
PVC insulated conductors, it is the temperature of the
cable component to determine the maximum acceptable
temperature on the terminals, in this case 70°C . On
the contrary, if the connection to the circuit-breaker is
constituted by bare copper busbars, whose maximum
operating temperature is 105°C, it is the prescription
for the terminals of the circuit-breaker component
which determines the maximum operating temperature,
consequently equal to 85°C.
As a summary of the above, Table 3 and Figure 5 show the
maximum acceptable temperature-rise and temperature
limits for the different parts of the assemblies as stated
by the switchboard Standard, and the temperature-
rise limits for a circuit-breaker installed inside a LV
switchboard recalculated for a reference ambient
temperature TA = 35°C.
Parts of assemblies-
description
Temperature-rise
limits
Temperature limits
(starting from
TA =35°C)
Terminal for external
insulated connections (IEC
60439-1)
70K 105 °C
Terminals for external con-
nections (IEC 60947-2) 85K 120 °C
Manual operating means:
Accessible with enclosed assembly
of metal 15K 50 °C
of insulating material 25K 60 °C
Accessible only with open assembly
of metal 30K 65 °C
of insulating material 40K 75 °C
Parts intended to be touched but not gripped: (CEI EN 60439-1)
of metal 30K 65 °C
of insulating material 40K 75°C
Accessible parts which need not to be touched during normal
operation (IEC 60439-1):
of metal 40K 75°C
of insulating material 50K 85°C
Non-accessible parts which need not to be touched during normal
operation (IEC 60947-2):
of metal 55K 90°C
of insulating material 65K 100°C
Table 3
Figure 5 Connection with
PVC-insulated cable
Connection
with busbar
7
ABB circuit-breakers inside LV switchboards
1 Problems of overheating inside switchboards
1.4 Verification of temperature-rise by
extrapolation
The Standard regarding low voltage controlgear and
switchgear assemblies provides that temperature-
rise verification for the PTTA type can be carried out
also by extrapolation making specific reference to
the prescriptions given in IEC/TR 60890 “A method
of temperature-rise assessment by extrapolation for
partially type-tested assemblies (PTTA) of low-voltage
switchgear and controlgear”.
The method proposed allows temperature-rise to be
determined inside PTTA enclosures without forced
ventilation.
The calculation validity is limited by a series of initial
assumptions:
- there is an approximately even distribution of power
losses inside the enclosure;
- the installed equipment is so arranged that air
circulation is but little impeded;
- the equipment installed is designed for direct current
or alternating current up to and including 60 Hz, with
the total of supply currents not exceeding 3150 A;
- conductors carrying high currents and structural
parts are so arranged that eddy current losses are
negligible;
- for enclosures with ventilation openings, the cross-
section of the air outlet openings is at least 1.1 times
the cross-section of the air inlet openings;
- there are no more than three horizontal partitions in
the assembly or in a section of it;
- where the enclosures with external ventilating
openings have compartments, the surface of the
ventilating openings in each horizontal partition shall
be at least 50% of the horizontal cross-section of the
compartment.
The following data are needed to calculate the
temperature-rise of the air inside an enclosure:
- geometric dimensions (height/width/depth);
- effective power loss of equipment, busbars, cables
and connections;
- type of installation of the enclosure (exposed, covered,
etc....);
- presence and dimensions of ventilation openings;
- number of internal horizontal partitions.
As regards the analysis of the suggested calculation
methods, the reader is required to consult the Standard
itself.
To carry out an analysis of temperature-rise in accordance
with this calculation method, ABB SACE offers its free
software program OTC. Starting from the required input
data, this program calculates the temperature of the air
at different heights of the enclosure through a dedicated
interface which appears as in the figure below.
Once the temperature of the air at the different heights
of the enclosure is known, it is possible to verify if the
components which are in a certain position are suitable to
operate at that temperature or if they need to be replaced
by other components.
To this purpose, with reference to circuit-breakers, ABB
SACE gives a derating of the current carrying capacity
as a function of the temperature of the air around the
circuit-breaker: thus it becomes possible to calculate if
the carrying capacity admitted for the circuit-breaker at
the temperature calculated at its installation point results
to be higher than the current of the supplied load.
As regards the above, the mere knowledge of the
temperature of the air around the circuit-breakers
would not allow the calculation of the current carrying
capacity.
However, it shall be taken into account that the calculation
method suggested by IEC/TR 60890 is a conservative
one which generally results into values higher than those
which can be verified in reality. As a consequence it is
possible to state that, if the minimum dimensions of the
connections suggested by ABB (see Tables 16 and 17
at page 21) are complied with, the power losses of all
the components are calculated correctly and the results
thus obtained are integrated with the manufacturer’s
experience, then the suggested calculation method can
be used without running into errors.
OTC interface
8ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2 Advices to improve the current carrying capacity
of the circuit-breakers inside switchboards
In order to give the necessary indications on the methods
intended to improve the current carrying capacity of
the circuit-breakers inside switchboards, first of all it is
necessary to analyze an assembly from a thermodynamic
point of view.
A switchboard can be considered as an enclosure
housing a series of elements generating heat and able
to dissipate heat towards the outside.
The elements generating heat inside the enclosure
exchange heat between them (conduction), with the air
inside the switchboard (convection) and with the walls of
the switchboard itself (radiation) as shown in Figure 6.
Figure 6
In its turn, the enclosure exchanges heat towards the
external environment. Also this heat exchange occurs
by conduction (through the cables connected to the
assembly), convection and radiation, as shown in
Figure 7. In enclosures with a degree of protection not
very high or with ventilation openings, part of the heat
is exchanged through a real air circulation between the
assembly and the external environment.
Figure 7
All these phenomena of circulation and exchange of
internal and external air, together with the structure of
the enclosure, affect temperature at each point of the
enclosure itself and of each component installed inside it.
This chapter analyses the main elements which contribute
to generate and influence the temperature inside a
switchboard and tries to give some useful information
for their optimization with the purpose of decreasing the
temperature and consequently of reducing the derating
of the current carrying capacity of circuit-breakers.
These elements are:
- the power loss inside the enclosure;
- the dissipation of the heat produced inside the enclosure;
- the dissipation of the heat produced by the terminals.
Conduction
Convection
Radiation
Heat
Heat
Heat
Circuit-breaker
Connection busbar
Connection busbar
Connection busbar
Circuit-breaker
Circuit-breaker
Switchboard wall
Air outside
the
enclosure
Air inside
the
enclosure
9
ABB circuit-breakers inside LV switchboards
Support in amagnetic
material
Bars
Insulator
One pole bars
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2.1 Power loss inside switchboards
As known, a modification of the temperature may be
caused by a power loss due to the current flow. Now, the
different components which constitute the main power
sources and which consequently represent also heat
sources inside a switchboard shall be considered in detail,
together with the measures to be taken in order to reduce
the power loss and limit its effects. These elements are:
the internal structure, the typology of the circuit-breaker
installed, the cross-sectional area of the internal con-
ductors of the switchboard, and the current paths.
2.1.1 Internal structure
The material used to realize structure and partitions inside
switchboards is often ferromagnetic and conductive. If
the system structure is such as to create a closed confi-
guration embracing the conductors, Joule-effect losses
due to eddy currents and hysteresis losses are induced,
with consequent local heating of remarkable importance.
The same phenomenon occurs in the bus ducts between
the enclosure and the conductor bars.
As an example to illustrate the influence of this pheno-
menon, Table 4 shows the percentage value representing
the part of losses developing inside the enclosure related
to the power loss inside the conductor bars.
Table 4
No. of
phases
No.
of
busbars
in parallel
per
phase
Cross-
section
[mm] In
[A]
Material of
the encasement
(of the bus duct)
Losses inside the
enclosure
(% referred to the
t o t a l l o s s i n s i d e
the conductor bars)
3 1 100x10 1000 ferromagnetic 35% - 45%
3 3 100x10 3000 ferromagnetic 55% - 65%
3 3 100x10 3000 amagnetic
(aluminum) 15% - 20%
From these data, it results that the increase of the rated
current and consequently the number of busbars in
parallel per phase and the material used for the separation
of the conductor bars may considerably affect heating.
For a correct assessment of the power losses it is
necessary to take into consideration also the configuration
of the separation form: in fact, if a ferromagnetic ring
embraces all the three conductors of a three-phase
system, as Figure 8 shows (or all the four conductors
in a system with the neutral conductor), the sum of the
Also the mechanical fixing of conductors could cause this
inconvenient; therefore it is important that the formation
of close rings is prevented by the insertion of insulators
or anchor clamps made of amagnetic and/or insulating
material (see Figure 9).
currents shall result into null induction; on the contrary,
if each conductor is enclosed by a single ring (Figure
8a), the total induction is not null, with the consequent
circulation of induced current, power loss and therefore
heat generation.
Figure 8 Figure 8a
Figure 9
2.1.2 Typology of the circuit-breaker installed
Circuit-breakers are components of switchboards which
cannot be disregarded when calculating total power
loss.
To make this evaluation easier, ABB SACE offers some
tables which are reported below and refer to molded-
case circuit-breakers of Tmax series (Table 5) and air
circuit-breakers type Emax (Table 6) respectively.
As the tables below show, the power loss of the same
circuit-breaker varies depending both on its version as
well as on the type of protective release installed.
Ferromagnetic meterial of
the separation form
Terminals
Current inductionNo induction
10 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Taking reference to these two variables, it is possible to
observe that :
- the power losses of withdrawable circuit-breakers are
higher than those of the fixed ones
- the power losses of the circuit-breakers equipped with
thermo-magnetic releases are higher than those of the
circuit-breakers with electronic releases.
Under heavy conditions from a thermal point of view, it
is advisable to use circuit-breakers in fixed version and
equipped with electronic type releases.
The difference between the power loss of a circuit-breaker
in three-pole version compared with a four-pole version is
not considered, since in a normal circuit the current flowing
in the neutral conductor is assumed to be null.
Total (3/4 poles)
power loss In T11P T1 T2 T3 T4 T5 T6 T7 S,H,L T7 V
[W] [A] F F F P F P F P/W F P/W F W F W F W
Releases 1 4.5 5.1
1.6 6.3 7.5
2 7.5 8.7
2.5 7.8 9
3.2 8.7 10.2
4 7.8 9
5 8.7 10.5
6.3 10.5 12.3
8 8.1 9.6
10 9.3 10.8
12.5 3.3 3.9
16 1.5 4.5 4.2 4.8
TMF 20 1.8 5.4 5.1 6 10.8 10.8
TMD 25 2 6 6.9 8.4
TMA 32 2.1 6.3 8.1 9.6 11.1 11.1
MF 40 2.6 7.8 11.7 13.8
MA 50 3.7 11.1 12.9 15 11.7 12.3
63 4.3 12.9 15.3 18 12.9 15.3
80 4.8 14.4 18.3 21.6 14.4 17.4 13.8 15
100 7 21 25.5 30 16.8 20.4 15.6 17.4
125 10.7 32.1 36 44.1 19.8 23.7 18.6 21.6
160 15 45 51 60 23.7 28.5 22.2 27
200 39.6 47.4 29.7 37.2
250 53.4 64.2 41.1 52.8
320 40.8 62.7
400 58.5 93
500 86.4 110.1
630 92 117
800 93 119
10 1.5 1.8
25 3 3.6
63 10.5 12
100 24 27.2 5.1 6.9
160 51 60 13.2 18
250 32.1 43.8
320 52.8 72 31.8 53.7
PR221 400 49.5 84 15 27 24 36
PR222 630 123 160.8 90 115 36 66 60 90
PR223 800 96 125 57,9 105,9 96 144
1000 150 90 165 150 225
1250 141 258 234,9 351,9
1600 231 423
Table 5
F: fixed W: withdrawable P: plug-in
Total (3/4 poles)
power loss X1B-N X1L E1B-N E2B-N-S E2L E3N-S-H-V E3L E4S-H-V E6H-V
[W] FWFWFWFWFWFWFWFWFW
In=630 41 63 50 87
In=800 65 100 80 140 65 95 29 53 22 36
In=1000 102 157 125 219 96 147 45 83 38 58
In=1250 159 257 196 342 150 230 70 130 105 165 60 90
In=1600 260 400 253 378 115 215 170 265 85 150
In=2000 180 330 130 225 215 330
In=2500 205 350 335 515
In=3200 330 570 235 425 170 290
In=4000 360 660 265 445
In=5000 415 700
In=6300 650 1100
Table 6
F: fixed W: withdrawable
11
ABB circuit-breakers inside LV switchboards
1) dd dd
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2.1.3 Cross-section of the conductors within
switchboards
In primary distribution switchboards, the power loss of the
connection systems (busbars/cables) is usually from 20%
to 40% of the total power loss of the switchboard.
The Std. IEC/TR 60890 includes a series of tables
which give the power loss of cables and busbars inside
switchboards per unit length, making reference to the
current carrying capacity.
By applying these tables (here defined as Tables 7 8 – 9)
it is possible to point out how a reduction in the power
loss corresponds to an increased cross-section.
In addition, it is important to remark how the cables
entering the enclosure give a contribution not negligible
to power loss, whereas they are often not considered
since they are not “strictly” part of the switchboard.
Here is an example to show how the contribution of
the connection cables is fundamental for a correct
assessment of the total power loss of the components
inside the switchboard.
Table 7: Operating current and power losses of insulated conductors
Section
(Cu)
Maximum permissible conductor temperature 70 °C
Air temperature inside the enclosure around the conductors
35 °C 55 °C 55 °C 35 °C 55 °C
operating current
power losses 2)
operating current
power losses 2)
operating current
power losses 2)
operating current
power losses 2)
operating current
power losses 2)
operating current
power losses 2)
mm2A W/m A W/m A W/m A W/m A W/m A W/m
1.5
2.5
4
12
17
22
2.1
2.5
2.6
8
11
14
0.9
1.1
1.1
12
20
25
2.1
3.5
3.4
8
12
18
0.9
1.3
1.8
12
20
25
2.1
3.5
3.4
8
12
20
0.9
1.3
2.2
6
10
16
28
38
52
2.8
3.0
3.7
18
25
34
1.2
1.3
1.6
32
48
64
3.7
4.8
5.6
23
31
42
1.9
2.0
2.4
32
50
65
3.7
5.2
5.8
25
32
50
2.3
2.1
3.4
25
35
50
85
104
130
6.3
7.5
7.9
55
67
85
2.6
3.1
3.4
85
115
150
6.3
7.9
10.5
65
85
115
3.7
5.0
6.2
70
95
120
161
192
226
8.4
8.7
9.6
105
125
147
3.6
3.7
4.1
175
225
250
9.9
11.9
11.7
149
175
210
7.2
7.2
8.3
150
185
240
275
295
347
11.7
10.9
12.0
167
191
225
4.3
4.6
5.0
275
350
400
11.7
15.4
15.9
239
273
322
8.8
9.4
10.3
300 400 13.2 260 5.6 460 17.5 371 11.4
Conductors for auxiliary circuits
mm2A W/m A W/m Diam.
0.12
0.14
2.6
2.9
1.2
1.3
1.7
1.9
0.5
0.6
0.4
-
0.20
0.22
3.2
3.6
1.1
1.3
2.1
2.3
0.5
0.5
-
0.5
0.30
0.34
4.4
4.7
1.4
1.4
2.9
3.1
0.6
0.6
0.6
0.6
0.50
0.56
6.4 1.8
1.6 4.2 0.8
0.7
0.8
-
0.75
1.00
8.2
9.3
1.9
1.8
5.4
6.1
0.8
0.8
1.0
-
1) Any arrangement desired with the values specified referring to six cores in a multi-core bundle with a simultaneous load 100%
2) single length
35 °C
12 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Width
x
Thickness
Cross-
section
(Cu)
Maximum permissible conductor temperature 85 °C
Air temperature inside the enclosure
around the conductors 35 °C
Air temperature inside the enclosure
around the conductors 55 °C
50 Hz 60 Hz ac dc and ac to 16 2/3 Hz 50 Hz 60 Hz ac dc and ac to 16 2/3 Hz
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
mm x mm mm2A* W/m A** W/m A* W/m A** W/m A* W/m A** W/m A* W/m A** W/m
12 x 2 23.5 144 19.5 242 27.5 144 19.5 242 27.5 105 10.4 177 14.7 105 10.4 177 14.7
15 x 2
15 x 3
29.5
44.5
170
215
21.7
23.1
282
375
29.9
35.2
170
215
21.7
23.1
282
375
29.9
35.2
124
157
11.6
12.3
206
274
16.0
18.8
124
157
11.6
12.3
206
274
16.0
18.8
20 x 2
20 x 3
20 x 5
20 x 10
39.5
59.5
99.1
199
215
271
364
568
26.1
27.6
29.9
36.9
351
463
665
1097
34.8
40.2
49.8
69.2
215
271
364
569
26.1
27.6
29.9
36.7
354
463
668
1107
35.4
40.2
50.3
69.6
157
198
266
414
13.9
14.7
16.0
19.6
256
338
485
800
18.5
21.4
26.5
36.8
157
198
266
415
12.3
14.7
16.0
19.5
258
338
487
807
18.8
21.4
26.7
37.0
25 x 5 124 435 34.1 779 55.4 435 34.1 78 55.6 317 18.1 568 29.5 317 18.1 572 29.5
30 x 5
30 x 10
149
299
504
762
38.4
44.4
894
1410
60.6
77.9
505
770
38.2
44.8
899
1436
60.7
77.8
368
556
20.5
27.7
652
1028
32.3
41.4
369
562
20.4
23.9
656
1048
32.3
41.5
40 x 5
40 x 10
199
399
641
951
47.0
52.7
1112
1716
72.5
88.9
644
968
47.0
52.6
1128
1796
72.3
90.5
468
694
25.0
28.1
811
1251
38.5
47.3
469
706
24.9
28.0
586
1310
38.5
48.1
50 x 5
50 x 10
249
499
775
1133
55.7
60.9
1322
2008
82.9
102.9
782
1164
55.4
61.4
1357
2141
83.4
103.8
566
826
29.7
32.3
964
1465
44.1
54.8
570
849
29.4
32.7
989
1562
44.3
55.3
60 x 5
60 x 10
299
599
915
1310
64.1
68.5
1530
2288
94.2
116.2
926
1357
64.7
69.5
1583
2487
94.6
117.8
667
955
34.1
36.4
1116
1668
50.1
62.0
675
989
34.4
36.9
1154
1814
50.3
62.7
80 x 5
80 x 10
399
799
1170
1649
80.7
85.0
1929
2806
116.4
138.7
1200
1742
80.8
85.1
2035
3165
116.1
140.4
858
1203
42.9
45.3
1407
2047
61.9
73.8
875
1271
42.9
45.3
1484
1756
61.8
74.8
100 x 5
100 x 10
499
999
1436
1982
100.1
101.7
2301
3298
137.0
164.2
1476
2128
98.7
102.6
2407
3844
121.2
169.9
1048
1445
53.3
54.0
1678
2406
72.9
84.4
1077
1552
52.5
54.6
1756
2803
69.8
90.4
120 x 10 1200 2314 115.5 3804 187.3 2514 115.9 4509 189.9 1688 61.5 2774 99.6 1833 61.6 3288 101.0
*) one conductor per phase **) two conductors per phase 1) single length
Table 8: Operating current and power losses of bare conductors, in vertical arrangement, without direct connections to the apparatus
Table 9: Operating current and power losses of bare conductors used as connections between the apparatus and the main busbars
Width
x
Thickness
Cross-
section
(Cu)
Maximum permissible conductor temperature 65 °C
Air temperature inside the enclosure
around the conductors 35 °C
Air temperature inside the enclosure
around the conductors 55 °C
50 Hz to 60 Hz ac and dc 50 Hz to 60 Hz ac and dc
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
operating current
power losses 1)
mm x mm mm2A* W/m A** W/m A* W/m A** W/m
12 x 2 23.5 82 5.9 130 7.4 69 4.2 105 4.9
15 x 2
15 x 3
29.5
44.5
96
124
6.4
7.1
150
202
7.8
9.5
88
102
5.4
4.8
124
162
5.4
6.1
20 x 2
20 x 3
20 x 5
20 x 10
39.5
59.5
99.1
199
115
152
218
348
6.9
8.0
9.9
12.8
184
249
348
648
8.9
10.8
12.7
22.3
93
125
174
284
4.5
5.4
6.3
8.6
172
198
284
532
7.7
6.8
8.4
15.0
25 x 5 124 253 10.7 413 14.2 204 7.0 338 9.5
30 x 5
30 x 10
149
299
288
482
11.6
17.2
492
960
16.9
32.7
233
402
7.6
11.5
402
780
11.3
21.6
40 x 5
40 x 10
199
399
348
648
12.8
22.7
648
1245
22.3
41.9
284
532
8.6
15.3
532
1032
15.0
28.8
50 x 5
50 x 10
249
499
413
805
14.7
28.5
805
1560
27.9
53.5
338
660
9.8
19.2
655
1280
18,5
36.0
60 x 5
60 x 10
299
599
492
960
17.2
34.1
960
1848
32.7
63.2
402
780
11.5
22.5
780
1524
21.6
43.0
80 x 5
80 x 10
399
799
648
1256
22.7
45.8
1256
2432
42.6
85.8
532
1032
15.3
30.9
1032
1920
28.8
53.5
100 x 5
100 x 10
499
999
805
1560
29.2
58.4
1560
2680
54.8
86.2
660
1280
19.6
39.3
1280
2180
36.9
57.0
120 x 10 1200 1848 68.3 2928 85.7 1524 46.5 2400 57.6
*) one conductor per phase **) two conductors per phase 1) single length
13
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Example
This example has the purpose of evaluating – as rst approximation – the total power loss inside the switchboard of
which Figure 10 shows the arrangement of the components, the dimensions, the structure and the relevant single-
wire diagram.
Figure 10
The components which form the switchboard are circuit-breakers, busbars and cables.
The power loss is calculated for each component and then the total power loss is determined.
Switchboard front
Single-wire diagram
H
L
P
IG
I1 I2 I3 I4 I5
H
[mm] W
[mm] D
[mm]
2000 1440 840
Dimensions
Number of horizontal partitions = 0
Wall-mounted separated enclosure
IG
B
D
F
A
E
C
I1
I2
I3
I4
I5
Table 10
Circuit-breaker
In CB
[A]
Ib
[A]
Power loss
[W]
IG E2 1600 EL 1600 1340 80.7
I1 T5 400 EL 400 330 33.7
I2 T5 400 EL 400 330 33.7
I3 T5 400 EL 400 330 33.7
I4 T3 250 TMD 250 175 26.2
I5 T3 250 TMD 250 175 26.2
Total power loss of the circuit-breakers [W] 234
Circuit-breakers
As regards circuit-breakers, the power loss can be determined on the basis of the dissipated power “Pn ” at the
rated current “InCB” (see previous Tables 5 and 6) referred to the current which really fl ows through the circuit-
breaker “Ib” (full load current of the circuit).
The formula linking these three quantities is the following :
PCB = PnCB x (Ib / InCB)2
Then, according to the type of apparatus installed inside the switchboard, the contribution to the load current in
terms of power loss of the individual circuit-breaker and the total power loss are reported in the following table:
14 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Busbars
As regards main busbars, distribution busbars and the busbars connecting circuit-breakers and cables, the ef-
fective power loss can be determined from the dissipated powers, at the nominal current and per unit length, as
shown in the previous Tables 8 and 9.
The formula to relate the data in the table to the characteristics (load current and length) of the busbars installed
in the switchboard is the following:
PSB = PnSB (Ib/InSB)2 x 3 x LSB
Therefore, with reference to the typology, the length “L” and the load current of the busbars installed inside the
switchboard, the contribution in terms of power loss of the single length and the total power loss are reported in
Table 11 below:
Connection busbar
Cross-sectional area
nx[mm]x[mm]
Length
[m]
Ib
[A]
Power loss
[W]
IG 2x60x10 0.450 1340 54
I1 30x10 0.150 330 3.8
I2 30x10 0.150 330 3.8
I3 30x10 0.150 330 3.8
I4 20x10 0.150 175 1.6
I5 20x10 0.150 175 1.6
Total power loss of the connection busbars [W] 68
Table 11
Cables
As regards cables, taking reference to Table 8 above, the same method used for the busbars can be applied and
the relevant results are reported in Table 12.
Then, the total power dissipated inside the switchboard is given by the sum of the three contributions already de-
termined above, therefore:
PTQ = 234+68+332=784W
It is important to note how the total power loss would be equal to 452W and therefore the estimated temperature
would be much lower than the effective one if the cable contribution (332W) were not taken into account.
Tabella 12
Cable
Cross-sectional area
[n]xmm2
Length
[m]
Ib
[A]
Power loss
[W]
IG 4x240 1.0 1340 133.8
I1 240 2.0 330 64.9
I2 240 1.7 330 55.2
I3 240 1.4 330 45.4
I4 120 1.1 175 19
I5 120 0.8 175 13.8
Total power loss of the connection busbars [W] 332
15
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2.1.4 Paths of the current
The positioning of apparatus and conductors may
result into a different power loss inside the switchboard.
It is a good rule to position the circuit-breakers as
shown in Figure 11, so that the paths of the highest
currents are as short as possible.
Thus, contrary to what
occurs in a type of installation as that of Figure 11a, the
dissipated power inside the switchboard is reduced and
unquestionable advantages from the thermal point of
view are achieved.
Figure 11
Suggested positioning:
The highest current (500 A) flows through the shortest path
Figure 11a
NOT suggested positioning:
The highest current (500 A) flows through the longest path
In case of switchboards with many columns, whenever
possible, it is advisable that the main circuit-breaker is
installed in the middle column or, however, in barycentric
position with respect to the load distribution, as shown in
Figure 12. Thus, by dividing the current into the two bran-
ches of the switchboard busbar system, a remarkable
reduction in the power loss is obtained – with the same
cross-section – in comparison with a configuration having
the incoming feeder at both ends of the switchboard as
in Figure 12a, which is a solution implying the circulation
of highest currents.
Figure 12
Advisable solution from a thermal point of view
Figure 12a
Heavier solution from a thermal point of view
50 A
50 A
100 A
300 A
500 A
INCOMING FEEDER OUTGOING FEEDER
50 A
50 A
100 A
300 A
500 A
INCOMING FEEDER OUTGOING FEEDER
2000 A 1200 A
3200 A
Busbar
Cables
3200 A
3200 A
Busbar
Cables
16 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2.2 Dissipation of the heat generated
inside switchboards
After an analysis of the main heat sources and of the
measures to limit heat generation, the modalities through
which switchboards can dissipate the heat towards the
outside are described now.
Many of these considerations derive from the Std.
IEC/TR 60890, which gives formulas and tables where
constructional characteristics and installation modalities
are in relation with the temperature-rise at the same
power loss. In particular, this chapter shall take into
consideration the switchboard ventilation, the surfaces
of the switchboard and their positioning, the form of
internal separation of the switchboard and the degree
of protection of the switchboard.
2.2.1 Switchboard ventilation
To increase the switchboard cooling, it is important
that a good circulation of air inside the switchboard is
realized (see Figure 13) and maintained. To this purpose,
for example, the possible ventilation openings are to be
properly dimensioned and positioned.
As regards dimensioning, IEC/TR 60890 for temperature-
rise assessment inside low voltage switchgear and
controlgear assemblies prescribes for the enclosures with
ventilation openings that the cross section for air outlets
is 1.1 times the cross section of the inlets.
This requirement is due to the greater volume of hot air
(going out of the switchboard) in comparison with the
cold air (going into the switchboard).
When disregarding this prescription, the air inlet surface
of the switchboard is not fully exploited.
As regards the positioning of the ventilation openings,
these are to be located so that the “draught chimney”
effect is achieved: an opening shall be positioned at the
bottom of the switchboard, on the front part, the other
one shall be positioned at the top, on the rear part, or
on the “roof” of the switchboard. It is important to re-
mind that any openings at mid height could reduce the
“draught chimney” effect, thus causing a reduction of
the air “draught”.
The equipment inside the switchboard shall be positioned
so that the circulation of the air is not excessively impeded
by a reduction of the section for the air flow.
In case of withdrawable circuit-breakers, particular
attention shall be paid to prevent the obstruction of the
ventilation openings in the fixed part of the circuit-breaker
(Figure 14).
Figure 13
Figure 14
2.2.2 Side surfaces and positioning of
switchboards
It is necessary to take into account that a switchboard
exchanges heat with the surrounding environment through
its surfaces (top, bottom and side walls) and therefore,
at the same power dissipation level by the internal
components, the larger the exchange surface towards
the outside and the better the exchange conditions
depending on the installation modality are, the greater
amount of heat is released. For example, the switchboard
should be positioned so that the air circulation around
its external surface is facilitated or, however, is little
impeded, thus improving heat exchange.
IEC/TR 60890, which, as already said, suggests a method
for the temperature-rise assessment inside switchboards,
does not consider the real external geometric surface
of the switchboard, but introduces the concept of
effective cooling surface “Ae”, intended as the sum of
the individual surface areas (top, front, side, ....) “A0
multiplied by the surface factor “b”. This factor takes into
account the heat dissipation of the individual surfaces
according to the type of installation of the enclosure, that
is the different capacity of dissipating heat according to
17
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
the surface positions and to their being either exposed or
covered. The values of the parameter “b” related to the
different surface types are shown in Table 13.
Ae = (A0 x b)
Table 13
Type of installation
Surface factor
“b”
Exposed top surface 1.4
Covered top surface, e.g. of built-in enclosures 0.7
Exposed side faces, e.g. front, rear and side walls 0.9
Covered side faces, e.g. rear side of wall-mounted
enclosures 0.5
Side faces of central enclosures 0.5
Floor surface
Not taken into
account
2.2.3 Forms of internal separation of
switchboards
With separation form it is meant the type of division provided
for the different circuits inside the switchboard.
Separation is obtained by means of metallic or insulating
barriers or partitions.
For further information about the different forms of
separation reference shall be made to the content of the
Annex B or to the prescriptions of Std. IEC 60439-1.
As evident, remarkable separation forms tend to limit
air circulation inside the switchboard, thus affecting
the temperature inside the switchboard itself. To take
into consideration this phenomenon, Tables 14 and 15
show the multiplying factor “d” which IEC/TR 60890
suggests to use under particular conditions to increase
the temperature-rise of the air inside the switchboard as
a function of the number of horizontal partitions in the
column under examination.
Number of horizontal partitions n Factor d
0 1
1 1.05
2 1.15
3 1.3
Table 14: For enclosures without ventilation openings and effective
cooling surface >1.25m2
Table 15: For enclosures with ventilation openings and effective
cooling surface >1.25m2
Number of horizontal partitions n Factor d
0 1
1 1.05
2 1.10
3 1.15
From the tables above, it results how horizontal partitions
can cause air temperature rises up to 30% (3 partitions
without ventilation openings).
2.2.4 Switchboard protection degree
The degree of protection IP shows the protection of the
enclosure against access to hazardous parts, against
ingress of solid foreign objects and ingress of water.
The code IP is the identification system of the degrees
of protection based on the prescriptions of the Std. IEC
60529.
The degree of protection of a switchboard affects its
capacity of dissipating heat: the higher the degree
of protection is, the less heat is dissipated by the
switchboard. Therefore, the choice of high degrees
of protection is not recommended when they are
unnecessary. Besides, it should be kept in mind that a
defined degree of protection may be reached through
different modalities.
For example, the protection against the vertical fall of
drops of water (IPX1) can be realized by such modalities
so as not to affect heat dissipation and so as to keep the
“chimney effect” inside the switchboard.
2.3 Dissipation of the heat generated in the
terminals
After a study of the main power sources inside the
switchboard and of the modalities through which
switchboards can dissipate the generated heat, an
analysis of how the circuit-breaker current carrying
capacity can be improved by reducing local heating
phenomena near the terminals shall be carried out.
In practice, when heat dissipation has not been
optimized, the presence of localized heating phenomena
limiting the maximum service current of the circuit is quite
frequent, even with low average air temperatures inside
the switchboard.
The phenomena affecting heat dissipation by the circuit-
breaker terminals are mainly convection (through the air
moving inside the switchboard) and conduction (through
the bars connected to the terminals); these phenomena
are to be related with the typology of terminals used
and to the version (fixed, withdrawable or plug-in) of the
circuit-breaker installed.
2.3.1 Problems linked to convection
As a general principle linked to the phenomenon of
convection, based on the convective motion of the air
which, while heating, tends to rise to the top, the busbar
arrangement should be such as to present the minimum
cross-sectional area to the air flow and to be licked
by the air flow on its maximum surface, therefore in a
“comb-like” arrangement. The circuit-breaker typology
which is most suitable for this configuration is the version
providing vertical rear terminals.
18 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Here are some practical considerations regarding use
and installation modalities of vertical rear terminals for
Emax series circuit-breakers. The use of these terminals
allows a better heat dissipation since, compared with the
horizontal ones, they oppose a smaller cross-section
to the natural motion of the air and a greater surface to
thermal exchange. Yet, one of the main problems to be
faced when using vertical terminals is their complicated
connection to the main busbar system when this runs
horizontally along the switchboard with the busbar
section arranged vertically. This problem is not present
with the same busbar system when the circuit-breaker
terminals are horizontal, since both busbars and terminals
are oriented according to two simple connection planes.
This concept is definitely more evident when making
reference to Figure 15.
Figure 15
Circuit-breaker with vertical terminals and vertical main busbars
Circuit-breaker with horizontal terminals and vertical main busbars
For example, in the case of E4 and E6 circuit-breakers,
to facilitate the connection between the vertical terminals
and the vertical connection busbars, it is possible to use
bars suitably bent as shown in Figure 16.
Figure 16
Emax E6
Connection bars to
the main busbars
Bars properly bent
Connection bars to
the main busbars
Vertical
terminals
Bars properly bent
Top view
Vertical terminals for E4 and E6 CBs
(detail referred to one pole)
Connection
busbars
Main busbars running horizontally along the
switchboard and vertically arranged
Circuit-breaker with
horizontal terminals
Detail of the horizontal
connection busbar with
air flow direction
Main busbars running horizontally along the
switchboard and vertically arranged
Circuit-breaker with
vertical terminals
Detail of the vertical con-
nection busbar with air flow
direction
Connection
busbars
19
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
As further example, Figure 17 shows two other pictures
representing an hypothesis of solution for the connection
of the vertical terminals to the vertical connection busbar
system for Emax E3 circuit-breakers.
Figure 17
On the contrary, when in the presence of upper vertical
terminals and lower terminals of different type or, howe-
ver, when in the presence of different upper and lower
terminals, the solutions to be adopted must not impede
the circulation of air in the upper terminals. For example,
as Figure 18 shows, the lower terminals shall not divert
too much the air flow and prevent it from reaching the
upper terminals causing the loss of the benefits of cooling
by convection.
Figure 18
Lower connection with rear horizontal terminals.
Air circulation, near the upper terminals (vertical) is impeded.
Lower connection with front terminals.
Air circulation, near the upper terminals (vertical), is only partially reduced.
Generally speaking, for the improvement of the heating
condition of busbars and terminals, the positioning of the
busbars acquires a remarkable importance; here is an
example of the solutions which can be adopted.
It should be kept into consideration that, the more the
clearance between the busbars, the more heat they dis-
sipate and that the upper middle terminal is usually that
with the most problems from the thermal point of view.
Therefore it is advisable to separate and keep apart
as much as possible the connection busbars (from the
main busbars to the circuit-breaker terminals) so that the
heating condition does not get worse.
Busbars
Connection busbars
Terminal
Busbars
Connection busbars
Terminal
Busbars
Terminal
Connection busbars
20 ABB circuit-breakers inside LV switchboards

Top view
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
For example, as Figure 19 shows, in the case of three-
pole circuit-breakers, the external connections can be
taken out of alignment with the terminals, so that distance
is increased.
Figure 19
In case of circuit-breaker connection through busbar
systems with the three phases vertically arranged, it is
advisable that spacing of the 3 phases starts as near as
possible to the circuit-breaker, with a solution as that
shown in Figure 20.
Figure 20
As already mentioned, the upper terminals and in parti-
cular the upper middle terminal are usually those which,
due to their positions, reach the highest temperatures.
Then, particular measures can be taken to improve
the heat exchange of these terminals, for example by
lengthening the horizontal part of the upper connection
busbars in comparison with the lower ones, as shown
in Figure 21.
Figure 21
Further increases in the carrying capacity of the circuits
may be obtained by mounting some dissipators (see
Figure 22) on the connection conductors – between the
circuit-breaker and the busbar system – for a better heat
dissipation, or by treating busbars and dissipators with
special paints, which allow an increase in the radiated
heat, without creating, on the other hand, a surface
thermal insulation.
Figure 22
2.3.2 Problems linked to conduction
Instead, with reference to the thermal exchange through
the phenomenon of conduction, the terminals of a circuit-
breaker release heat also towards the busbars or the
cables connected to them. In particular, besides carrying
the current, the connection busbars convey heat far from
the terminals. Therefore, their dimensioning and position
shall have to take into account this double function.
There is a rise in the heat exchanged by conduction
both when the cross-section through which heat is
exchanged enlarges (contact section between the
cables or the connection busbars and the circuit-breaker
terminals), as well as when the temperature difference
between the bodies in touch involved by this exchange
increases. From this remark it results that, on their turn,
the connection busbars shall effectively dissipate heat
to keep their temperature low. To obtain a connection
allowing a sufficient heat exchange between the terminals
and the distribution system of the switchboard, ABB
SACE indicates the minimum cross-sectional area of the
cables and busbars to be used.
Main busbars
Connection busbars
Connection
busbars
Main busbars
21
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Table 16
Circuit-breaker type In Cables Bars
Tmax [A] [ n // ] x [ mm2 ] [ n // ] x [ mm x mm ]
T2 <=8 1
T2-T4 10 1,5
T1-T2 16 2,5
T1-T2-T4 20 2,5
T1-T2-T4 25 4
T1-T2-T4 32 6
T1-T2-T4 40 10
T1-T2-T4 50 10
T1-T2-T3-T4 63 16
T1-T2-T3-T4 80 25
T1-T2-T3-T4 100 35
T1-T2-T3-T4 125 50
T1-T2-T3-T4 160 70
T3-T4 200 95 20x5
T3-T4 250 120 25x5
T4-T5 320 185 40x5
T5 400 240 50x5
T5 500 2x150 2x30x5
T5-T6 630 2x185 2x40x5
T6 800 2x240 2x50x5
T6-T7 1000 3x240 2x60x5
T7 1250 4x240 2x80x5
T7 1600 5x240 2x100x5
Here are the indications given for the molded-case
circuit-breakers series Tmax and the air circuit-breakers
series Emax, reported in Table 16 and in Table 17
respectively.
The cross-sectional areas of the cables and busbars
reported in Tables 16 and 17 are those used to determine
the rated current carrying capacity of the circuit-breakers
in free air according to the Std. IEC 60947-2.
Circuit-breaker Vertical terminals Front horizontal terminals
Emax [ n // ] x [ mm x mm ] [ n // ]x[ mm x mm ]
E1B/N 08 1x(60x10) 1x(60x10)
E1B/N 12 1x(80x10) 2x(60x8)
E2B/N 12 1x(60x10) 1x(60x10)
E2B/N 16 2x(60x10) 2x(60x10)
E2B/N 20 3x(60x10) 3x(60x10)
E2L 12 1x(60x10) 1x(60x10)
E2L 16 2x(60x10) 2x(60x10)
E3S/H 12 1x(60x10) 1x(60x10)
E3S/H 16 1x(100x10) 1x(100x10)
E3S/H 20 2x(100x10) 2x(100x10)
E3N/S/H 25 2x(100x10) 2x(100x10)
E3N/S/H 32 3x(100x10) 3x(100x10)
E3L20 2x(100x10) 2x(100x10)
E3L 25 2x(100x10) 2x(100x10)
E4H 32 3x(100x10) 3x(100x10)
E4S/H 40 4x(100x10) 6x(60x10)
E6V 32 3x(100x10) 3x(100x10)
E6V 40 4x(100x10) 4x(100x10)
E6H/V 50 6x(100x10) 6x(100x10)
E6H/V 63 7x(100x10) ----------------------
Table 17
22 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
2.3.3 Current carrying capacity of circuit-breakers
and busbars
To conclude this chapter, Figure 23 shows the curves
reporting the carrying capacity of the Tmax molded-case
circuit-breakers equipable with electronic relays, referred
to the different temperatures and the different types of
terminals and available versions, whereas Table 18 repor-
ts the current carrying capacity of the Tmax molded-case
circuit-breakers equipable with thermomagnetic releases.
As regards the air circuit-breakers of Emax series, Table
19 reports the carrying capacity of the single apparatus
at the different temperatures.
Note: in the plug-in version the
maximum setting is derated
by 10%
Note: in the plug-in version the
maximum setting is derated
by 10%
F = Front flat terminals
FC Cu = Front terminals for
copper cables
EF = Front extended terminals
FC CuAl = Front terminals for CuAl cables ES = Front extended spread terminals
R = Rear terminals
F = Front flat terminals
FC Cu = Front terminals for
copper cables
EF = Front extended terminals
FC CuAl = Front terminals for CuAl cables ES = Front extended spread terminals
R = Rear terminals
T2 160
Fixed
T2 160
Plug-in
Figure 23
23
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
215
220
225
230
235
240
245
250
255
Iu [A]
T [°C]
40 45 50 55 60 65 70
210
205
VR
HR-F-FC
T4 250
215
220
225
230
235
240
245
250
255
Iu [A]
T [°C]
40 45 50 55 60 65 70
HR-F-FC
VR
T4 250
Fixed
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
Plug-in / Withdrawable
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
24 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
250
260
270
280
290
300
310
320
330
Iu [A]
T [°C]
40 45 50 55 60 65 70
240
VR
HR-F-FC
T4 320
Fixed
250
260
270
280
290
300
310
320
330
Iu [A]
T [°C]
40 45 50 55 60 65 70
240
30 35
FC-HR-F
VR
T4 320
Plug-in / Withdrawable
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
25
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
365
370
375
380
385
390
395
400
405
Iu [A]
T [°C]
40 45 50 55 60 65 70
360
355
350
HR-FC-F
VR
T5 400
365
370
375
380
385
390
395
400
405
Iu [A]
T [°C]
40 45 50 55 60 65 70
360
355
350
35
345
340
335
330
HR-FC-F
VR
T5 400
Fixed
Plug-in / Withdrawable
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
26 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
560
570
580
590
600
610
620
630
640
Iu [A]
T [°C]
40 45 50 55 60 65 70
550
540
530
35
520
510
500
490
30
480
470
VR
HR-FC-F
T5 630
Iu [A]
T [°C]
40 45 50 55 60 65 7035
600
550
500
450
400
VR
EF-HR
T5 630
EF = Front extended terminals VR = Rear flat vertical terminalsHR = Rear flat horizontal terminals
Fixed
Plug-in / Withdrawable
FC = Front terminals for cables
VR = Rear flat vertical terminals
F = Front flat terminals HR = Rear flat horizontal terminals
27
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
4
T6 630
Fixed
VR
EF-HR
T6 630
Withdrawable
R(VR)
F-FC
R(HR)
EF = Front extended terminals HR = Rear flat horizontal terminals VR = Rear flat vertical terminals
FC = Front terminals for cablesF = Front flat terminals R(VR)=Rear(vertical)terminals R(HR) = Rear(horiz.)terminals
28 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
4
VR
EF-HR
T6 800
Withdrawable
R(VR)
T6 800
Fixed
F-FC
R(HR)
EF = Front extended terminals HR = Rear flat horizontal terminals VR = Rear flat vertical terminals
FC = Front terminals for cablesF = Front flat terminals R(VR)=Rear(vertical)terminals R(HR) = Rear(horiz.)terminals
29
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
900
1000
35 40 45 50 55 60 65 70
1100
R(VR)
FC
R (HR)
ES
T6 1000
Fixed
FC = Front terminals for cables R (VR) = Rear flat vertical terminals
R (HR) = Rear flat horizontal terminals
ES = Front extended spread terminals
30 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
950
900
1000
35 40 45 50 55 60 65 70
1050
VR
EF-HR
T7 V 1000
Fixed
950
900
1000
35 40 45 50 55 60 65 70
1050
T7 V 1000
Withdrawable
VR
EF-HR
Note: For ratings below 1000 A Tmax T7 does not undergo any thermal derating.
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminalsEF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
31
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
1200
1150
800
850
900
950
1000
1050
1100
1250
35 40 45 50 55 60 65 70
1300
VR
EF-HR
T7 S,H,L, 1250
1200
1150
800
850
900
950
1000
1050
1100
1250
35 40 45 50 55 60 65 70
1300
T7 V 1250
VR
EF-HR
Fixed
Fixed
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
32 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
1200
1150
800
850
900
950
1000
1050
1100
1250
35 40 45 50 55 60 65 70
1300
VR
EF-HR
T7 S,H,L, 1250
Withdrawable
1200
1150
800
850
900
950
1000
1050
1100
1250
35 40 45 50 55 60 65 70
1300
T7 V 1250
VR
EF-HR
Withdrawable
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
33
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
1200
1000
1100
1400
1500
1600
1700
35 40 45 50 55 60 65 70
1300
VR
EF-HR
T7 S,H,L, 1600
Fixed
1200
1000
1100
1400
1500
1600
1700
35 40 45 50 55 60 65 70
1300
T7 S,H,L, 1600
Withdrawable
VR
EF-HR
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
EF = Extended front terminals VR = Rear flat vertical terminals HR = Rear flat horizontal terminals
34 ABB circuit-breakers inside LV switchboards

Table 18
Tmax T1 and T1 1P (*)
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
16 13 18 12 18 12 17 11 16 11 15 10 14 9 13
20 16 23 15 22 15 21 14 20 13 19 12 18 11 16
25 20 29 19 28 18 26 18 25 16 23 15 22 14 20
32 26 37 25 35 24 34 22 32 21 30 20 28 18 26
40 32 46 31 44 29 42 28 40 26 38 25 35 23 33
50 40 58 39 55 37 53 35 50 33 47 31 44 28 41
63 51 72 49 69 46 66 44 63 41 59 39 55 36 51
80 64 92 62 88 59 84 56 80 53 75 49 70 46 65
100 81 115 77 110 74 105 70 100 66 94 61 88 57 81
125 101 144 96 138 92 131 88 125 82 117 77 109 71 102
160 129 184 123 176 118 168 112 160 105 150 98 140 91 130
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Tmax T2
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
1,6 1,3 1,8 1,2 1,8 1,2 1,7 1,1 1,6 1 1,5 1 1,4 0,9 1,3
2 1,6 2,3 1,5 2,2 1,5 2,1 1,4 2 1,3 1,9 1,2 1,7 1,1 1,6
2,5 2 2,9 1,9 2,8 1,8 2,6 1,8 2,5 1,6 2,3 1,5 2,2 1,4 2
3,2 2,6 3,7 2,5 3,5 2,4 3,4 2,2 3,2 2,1 3 1,9 2,8 1,8 2,6
4 3,2 4,6 3,1 4,4 2,9 4,2 2,8 4 2,6 3,7 2,4 3,5 2,3 3,2
5 4 5,7 3,9 5,5 3,7 5,3 3,5 5 3,3 4,7 3 4,3 2,8 4
6,3 5,1 7,2 4,9 6,9 4,6 6,6 4,4 6,3 4,1 5,9 3,8 5,5 3,6 5,1
8 6,4 9,2 6,2 8,8 5,9 8,4 5,6 8 5,2 7,5 4,9 7 4,5 6,5
10 8 11,5 7,7 11 7,4 10,5 7 10 6,5 9,3 6,1 8,7 5,6 8,1
12,5 10,1 14,4 9,6 13,8 9,2 13,2 8,8 12,5 8,2 11,7 7,6 10,9 7,1 10,1
16 13 18 12 18 12 17 11 16 10 15 10 14 9 13
20 16 23 15 22 15 21 14 20 13 19 12 17 11 16
25 20 29 19 28 18 26 18 25 16 23 15 22 14 20
32 26 37 25 35 24 34 22 32 21 30 19 28 18 26
40 32 46 31 44 29 42 28 40 26 37 24 35 23 32
50 40 57 39 55 37 53 35 50 33 47 30 43 28 40
63 51 72 49 69 46 66 44 63 41 59 38 55 36 51
80 64 92 62 88 59 84 56 80 52 75 49 70 45 65
100 80 115 77 110 74 105 70 100 65 93 61 87 56 81
125 101 144 96 138 92 132 88 125 82 117 76 109 71 101
160 129 184 123 178 118 168 112 160 105 150 97 139 90 129
(*) For T1 1P circuit-breakers (fitted with TMF themomagnetic trip unit) consider only the column corresponding to the maximum adjustament of the TMD
trip units.
Tmax T3
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
63 51 72 49 69 46 66 44 63 41 59 38 55 35 51
80 64 92 62 88 59 84 56 80 52 75 48 69 45 64
100 80 115 77 110 74 105 70 100 65 93 61 87 56 80
125 101 144 96 138 92 132 88 125 82 116 76 108 70 100
160 129 184 123 176 118 168 112 160 104 149 97 139 90 129
200 161 230 154 220 147 211 140 200 130 186 121 173 112 161
250 201 287 193 278 184 263 175 250 163 233 152 216 141 201
(*) For plug-in circuit-breakers, a derating of 10% is to be considered.
(*) For plug-in circuit-breakers, a derating of 10% is to be considered.
35
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Tmax T4
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
20 19 27 18 24 16 23 14 20 12 17 10 15 8 13
32 26 43 24 39 22 36 19 32 16 27 14 24 11 21
50 37 62 35 58 33 54 30 50 27 46 25 42 22 39
80 59 98 55 92 52 86 48 80 44 74 40 66 32 58
100 83 118 80 113 74 106 70 100 66 95 59 85 49 75
125 103 145 100 140 94 134 88 125 80 115 73 105 63 95
160 130 185 124 176 118 168 112 160 106 150 100 104 90 130
200 162 230 155 220 147 210 140 200 133 190 122 175 107 160
250 200 285 193 275 183 262 175 250 168 240 160 230 150 220
Tmax T5
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
320 260 368 245 350 234 335 224 320 212 305 200 285 182 263
400 325 465 310 442 295 420 280 400 265 380 250 355 230 325
500 435 620 405 580 380 540 350 500 315 450 280 400 240 345
Tmax T6
In [A]
10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
630 520 740 493 705 462 660 441 630 405 580 380 540 350 500
800 685 965 640 905 605 855 560 800 520 740 470 670 420 610
36 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
Table 19
X1 withdrawable – rear horizontal terminals
Temperature
[°C]
X1 630 X1 1800 X1 1000 X1 1250 X1 1600
% [A] % [A] % [A] % [A] % [A]
10 100 630 100 800 100 1000 100 1250 100 1600
20 100 630 100 800 100 1000 100 1250 100 1600
30 100 630 100 800 100 1000 100 1250 100 1600
40 100 630 100 800 100 1000 100 1250 100 1600
45 100 630 100 800 100 1000 100 1250 100 1600
50 100 630 100 800 100 1000 100 1250 97 1550
55 100 630 100 800 100 1000 100 1250 94 1500
60 100 630 100 800 100 1000 100 1250 93 1480
X1 withdrawable – rear vertical terminals
Temperature
[°C]
X1 630 X1 1800 X1 1000 X1 1250 X1 1600
% [A] % [A] % [A] % [A] % [A]
10 100 630 100 800 100 1000 100 1250 100 1600
20 100 630 100 800 100 1000 100 1250 100 1600
30 100 630 100 800 100 1000 100 1250 100 1600
40 100 630 100 800 100 1000 100 1250 100 1600
45 100 630 100 800 100 1000 100 1250 100 1600
50 100 630 100 800 100 1000 100 1250 100 1600
55 100 630 100 800 100 1000 100 1250 98 1570
60 100 630 100 800 100 1000 100 1250 95 1520
SACE Emax E1
Temperature
[°C]
E1 800 E1 1000 E1 1250 E1 1600
% [A] % [A] % [A] % [A]
10 100 800 100 1000 100 1250 100 1600
20 100 800 100 1000 100 1250 100 1600
30 100 800 100 1000 100 1250 100 1600
40 100 800 100 1000 100 1250 100 1600
45 100 800 100 1000 100 1250 98 1570
50 100 800 100 1000 100 1250 96 1530
55 100 800 100 1000 100 1250 94 1500
60 100 800 100 1000 100 1250 92 1470
65 100 800 100 1000 99 1240 89 1430
70 100 800 100 1000 98 1230 87 1400
37
ABB circuit-breakers inside LV switchboards
2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
SACE Emax E2
Temperature
[°C]
E2 800 E2 1000 E2 1250 E2 1600 E2 2000
% [A] % [A] % [A] % [A] % [A]
10 100 800 100 1000 100 1250 100 1600 100 2000
20 100 800 100 1000 100 1250 100 1600 100 2000
30 100 800 100 1000 100 1250 100 1600 100 2000
40 100 800 100 1000 100 1250 100 1600 100 2000
45 100 800 100 1000 100 1250 100 1600 100 2000
50 100 800 100 1000 100 1250 100 1600 97 1945
55 100 800 100 1000 100 1250 100 1600 94 1885
60 100 800 100 1000 100 1250 98 1570 91 1825
65 100 800 100 1000 100 1250 96 1538 88 1765
70 100 800 100 1000 100 1250 94 1510 85 1705
SACE Emax E3
Temperature
[°C]
E3 800 E3 1000 E3 1250 E3 1600 E3 2000 E3 2500 E3 3200
% [A] % [A] % [A] % [A] % [A] % [A] % [A]
10 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 100 3200
20 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 100 3200
30 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 100 3200
40 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 100 3200
45 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 100 3200
50 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 97 3090
55 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 93 2975
60 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 89 2860
65 100 800 100 1000 100 1250 100 1600 100 2000 97 2425 86 2745
70 100 800 100 1000 100 1250 100 1600 100 2000 94 2350 82 2630
SACE Emax E4
Temperature
[°C]
E4 3200 E4 4000
% [A] % [A]
10 100 3200 100 4000
20 100 3200 100 4000
30 100 3200 100 4000
40 100 3200 100 4000
45 100 3200 100 4000
50 100 3200 98 3900
55 100 3200 95 3790
60 100 3200 92 3680
65 98 3120 89 3570
70 95 3040 87 3460
SACE Emax E6
Temperature
[°C]
E6 3200 E6 4000 E6 5000 E6 6300
% [A] % [A] % [A] % [A]
10 100 3200 100 4000 100 5000 100 6300
20 100 3200 100 4000 100 5000 100 6300
30 100 3200 100 4000 100 5000 100 6300
40 100 3200 100 4000 100 5000 100 6300
45 100 3200 100 4000 100 5000 100 6300
50 100 3200 100 4000 100 5000 100 6300
55 100 3200 100 4000 100 5000 98 6190
60 100 3200 100 4000 98 4910 96 6070
65 100 3200 100 4000 96 4815 94 5850
70 100 3200 100 4000 94 4720 92 5600
38 ABB circuit-breakers inside LV switchboards

2 Advices to improve the current carrying capacity of the circuit-breakers inside switchboards
As regards small-size molded-case circuit-breakers there
is no remarkable difference among the various terminal
typologies, whereas for big-size molded-case circuit-
breakers (starting from T4), the rear vertical terminals are
to be preferred to the other terminal typologies when the
circuit-breaker is installed in vertical position. In general,
however, the fixed version is suggested instead of the
withdrawable and the plug-in ones. If the circuit-breaker
were installed in horizontal position, to determine its
current carrying capacity reference should be taken to
the lowest curve in the graphics.
As regards the air circuit-breakers of Emax series, the
behaviour of the rear horizontal terminals is analogous
to that of the front ones.
The greater heat dissipation capacity is definitely that of
the rear vertical terminals.
In the same way, as an example, Table 20 shows the
different current carrying capacity given by the Std. DIN
43671 for copper conductors of rectangular cross-sec-
tion in indoor installations, where the radiation coefficient
is assumed to be equal to 0.4 for not painted bars and
0.9 for painted bars.
As it can be observed from the table, under the same
conditions in the busbar system, passing from bare
busbars to painted busbars there is an increase in the
current carrying capacity which can reach also 15%.
Table 20
Width
x
Thickness
Carrying capacity in A
a.c. up to 60Hz
for bare copper conductors
Carrying capacity in A
up to 60Hz
for painted copper conductors
[mm] x [mm] I II III II II* I II III II II*
50 x 5 583 994 1240 1920 679 1140 1330 2010
50 x 10 852 1510 2040 2600 1020 1720 2320 2950
60 x 5 688 1150 1440 2210 826 1330 1510 2310
60 x 10 985 1720 2300 2900 1180 1960 2610 3290
80 x 5 885 1450 1750 2720 1070 1680 1830 2830
80 x 10 1240 2110 2790 3450 1500 2410 3170 3930
100 x 5 1080 1730 2050 3190 1300 2010 2150 3300
100 x 10 1490 2480 3260 3980 1810 2850 3720 4530
Validity condition of the table: ambient temperature 35°C, conductor temperature 65°C, conductor width vertical, clearance between conductors in paral-
lel equal to conductor thickness.
(*) minimum clearance between the central conductors: 50mm.
39
ABB circuit-breakers inside LV switchboards
3 Problems concerning short-circuit
3 Problems concerning short-circuit
In this chapter the problems regarding short-circuit are
analyzed, making specific reference to the interaction
between the protection circuit-breaker installed in the
switchboard and the switchboard itself. After a short
introduction defining the main electrical parameters
related to short-circuit, an analysis shall be carried out to
illustrate the prescriptions regarding the electrical circuits
of switchboards and the modalities aimed at reducing the
possibility of occurrence of a short-circuit on the circuits
inside the switchboards and to reduce its effects.
3.1 Main definitions of the parameters
characterizing a switchboard under
short-circuit conditions
As far as the short-circuit withstand strength of a switchboard
is concerned, the main parameters characterizing a
switchboard are:
- rated short-time withstand current;
- rated peak withstand current;
- rated conditional short-circuit current.
The Std. IEC 60439-1 about low voltage controlgear and
switchgear define the above parameters as follows :
Rated short-time withstand current “Icw”
The rated short-time withstand current of a circuit of
a switchboard is the r.m.s. value of short-time current
assigned to that circuit by the manufacturer which
that circuit can carry without damage under the test
conditions specified by the Standard. Unless otherwise
stated by the manufacturer, the reference time is 1s. To
this short-time current a determined peak value “Ipk” is
associated and it is assumed that the maximum current
value which can occur and which can be withstand by
the switchboard does not exceed the peak value, related
to the Icw by a coefficient “n”.
Rated peak withstand current “Ipk
The rated peak withstand current of a switchboard circuit
is the value of peak current assigned to that circuit
by the manufacturer which that circuit can withstand
satisfactorily under the test conditions specified by
the Standard. The peak current value, which is used
to determine electro-dynamic stresses, is obtained by
multiplying the short-time current by the coefficient “n”.
The values normalized by the multiplying factor “n” are
reported in Table 21.
Values normalized by coefficient
“n”
RMS value of
short-circuit current
kA Cojn
I 5 0.7 1.5
5 < I 10 0.5 1.7
10 < I 20 0.3 2
20 < I 50 0.25 2.1
50 < I 0.2 2.2
Table 21
Rated conditional short-circuit current “Icc”
The rated conditional short-circuit current characterizing
the circuit of a switchboard is the value of prospective
short-circuit current, stated by the manufacturer, which
that circuit, protected by a short-circuit protective
device specified by the manufacturer, can withstand
satisfactorily for the operating time of the device under
the test conditions specified.
With reference to these definitions, it is possible to say
that the circuit of a switchboard for which a specific Icw
has been defined, can withstand the electro-dynamic
stresses due to the initial peak value which can reach
a maximum value equal to “Icw x n” and a specific
thermal energy due to the current and equal to Icw
2
x t
(with t=1s).
On the other hand, the circuit of a switchboard protected
by a suitable device shall have a rated conditional short-
circuit current if it can withstand the electro-dynamic
stresses due to the peak current limited by the protective
device and a specific thermal energy let through by the
protective device in correspondence with the prospective
short-circuit current Ik.
3.1.1 General prescriptions and information
about short-circuit withstand strength
As regards the short-circuit withstand strength of an
assembly, the Std. IEC 60439-1 prescribes that the user
of the switchboard shall give the manufacturer the data
relevant to the short-circuit currents at the installation
point so that the assembly is protected against short-
circuit by protective devices for example automatic
circuit-breakers positioned inside or outside the
switchboard – and so that it is manufactured to withstand
the thermal and dynamic stresses occurring under short-
circuit conditions. The information concerning the short-
circuit withstand strength of the switchboard are given
by the manufacturer according to the presence or not of
the protective device.
40 ABB circuit-breakers inside LV switchboards

3 Problems concerning short-circuit
For assemblies with an automatic circuit-breaker
incorporated in the incoming unit, the manufacturer shall
indicate the maximum allowable value of short-circuit
current, expressed as:
- rated conditional short-circuit current Icc, when the
protective device is a circuit-breaker having remarkable
current limiting characteristics;
- allowable short-time withstand current Icw, when the
protective device is a circuit-breaker having a high Icw
value.
For assemblies where a protective circuit-breaker is not
incorporated in the incoming unit, the manufacturer may
indicate:
- a rated conditional short-circuit current (Icc), specifying
the characteristics of the external device which protects
the switchboard (rated current, breaking capacity,
limited current, specific let-through energy);
-
an allowable value of short-time withstand current (Icw).
If the duration of the current is not specified, the current
is understood to be equal to 1sec; if the initial peak
value is not specified, this is understood to be linked to
the assigned conditional short-circuit withstand current
through the factor “n”.
3.2 Prescriptions concerning the electrical
circuits of a switchboard
In addition to the previous general prescriptions
concerning the indication of the short-circuit withstand
strength of a switchboard, the Standard prescribes
how the electrical circuits inside the assembly must be
dimensioned in order to reduce the possibility that a
fault occurs.
The main prescriptions are given with reference to the
internal busbar system, which shall be designed so that
the likelihood of a short-circuit on the busbars is remote.
As regards busbar dimensioning in relation to the short-
circuit withstand strength, different prescriptions must
be complied with if reference is made to a main busbar
system rather than to circuits derived from the busbars.
3.2.1 Main busbar systems
The main busbars (bare or insulated) shall be arranged
in such a manner that an internal short-circuit is not
to be expected under normal operating conditions.
Unless otherwise specified, the busbars shall be rated
in accordance with the information concerning the short-
circuit withstand strength and designed to withstand the
short-circuit stresses limited by the protective devices
installed on the supply side of the busbars.
In practice, if the limiting characteristics of the protective
device upstream the busbar system are not remarkable
(or if they are not known in advance), the busbar system
shall be rated so that the Icw is higher than the short-
circuit current value at the installation point.
Here is an application example to illustrate this
concept:
In the switchboard of Figure 24, the circuit-breaker
protecting the main busbar system is an Emax E4H with
Icw = 100kA.
If also the busbar system has an Icw value equal to 100kA
or higher, the circuit formed by the circuit-breaker and by the
busbar system shall be considered to have Icw = 100kA.
On the other hand, if the device protecting the main
busbar system is an automatic circuit-breaker with
current limiting characteristics, the busbar system may
be dimensioned to withstand the stresses due to the
limited peak current and to the specific let-through energy
limited by the circuit-breaker.
The switchboard of Figure 25 to be installed in a plant
with a prospective short-circuit current Ik equal to 100kA
at 400V is now taken as example. A Tmax T6L1000 is
chosen as incoming circuit-breaker.
Figure 24
Icw=100kA
Ik=100kA
SACE
41
ABB circuit-breakers inside LV switchboards
3 Problems concerning short-circuit
In correspondence with the Ik values, downstream the
incoming apparatus, the following parameters are verified:
- specific let-through energy lower than 20MA2s
- limited peak current lower than 80kA
The presence of a current limiting apparatus inside the
switchboard allows a busbar system with an Icw value
< 100kA (short-circuit current in the plant) to be installed
on the load side of this apparatus, to which, however,
a peak current value and a specific let-through energy
exceeding those measured on the load side of the circuit-
breaker shall correspond.
Figure 25
For example, a busbar system characterized by an Icw
value equal to 50kA can withstand the following para-
meters:
- specific let-through energy
50kA x 50kA x 1s = 2500MA2s
- peak current
50kA x 2.1 = 105kA
As a consequence it is quite easy to verify that the busbar
system (Icw = 50kA, Ipk = 105kA, I2t = 2500MA2s) can
withstand greater stresses than those ones generated
on the load side of T6L circuit-breaker. To conclude: it
is possible to install a busbar system with an Icw value
equal to 50kA on the load side of the circuit-breaker
type T6L; in this case, the circuit formed by the busbars
and by the circuit-breaker shall have Icc = 100kA and
therefore it is suitable for the prospective short-circuit
current of the plant.
3.2.2 Distribution busbars and conductors
derived by the main busbars
Within a section of an assembly, the conductors and
the distribution busbars positioned between the main
busbars and the supply side of functional units, as well
as the components included in these units, may be
rated on the basis of the reduced short-circuit stresses
occurring on the load side of the respective short-circuit
device, provided that these conductors are arranged
so that under normal operating conditions, an internal
short-circuit between phases and/or between phases
and earth is only a remote possibility. Such conductors
are preferably of solid rigid manufacture.
The economical and dimensional advantages which
result from this prescription of the Standard are evident,
above all when there are many circuits derived by a single
main busbar system.
Figure 26
Figure 26 represents a switchboard where the vertical
distribution busbar, constituted by a bare bar of solid
manufacture and provided with spacers, is derived from
the main busbar, so that the possibility that a short-circuit
occurs can be considered as remote.
From this busbar, different horizontally-arranged
conductors (in cable) depart, supplying the main circuit-
breakers of the different outgoing feeders.
For a correct dimensioning of the vertical distribution
busbar, it is possible to consider the outgoing device
having the lowest current limiting performances. Thus,
also in the event of a fault on the load side of the circuit-
Icw=50kA
Ik=100kA
T2 160
T2 160
T3 250
T3 250
T3 250
T7
Main busbar
Distribution busbar
Dimensioned according to the limiting
characteristics of the main circuit-breaker
Dimensioned according to
the limiting characteristics of T2
circuit-breaker
Dimensioned according to
the limiting characteristics
of T3 circuit-breaker
Conductors
Dimensioned according either
to the limiting characteristics
of the biggest circuit-breaker
among the outgoing circuit-
breakers of the single units, or
to the performances of the
main circuit-breaker.
42 ABB circuit-breakers inside LV switchboards

breaker with lower limiting characteristics, the busbar
shall undergo acceptable stresses.
Dimensioning of the distribution busbar carried out
according to the above corresponds to the Standard
prescriptions; in spite of this, the usual procedure for many
switchboard manufacturers is dimensioning distribution
busbars making reference to the performances of the
circuit-breaker on the incoming of the switchboard, in
terms of let-through energy and limited peak current
value.
On the contrary, the different cables which feed the
individual circuit-breakers shall be dimensioned
according to the limiting characteristics of the relevant
device they supply.
3.3 Reduction of the possibility of short-
circuit events and of the relevant
effects
As regards the prescriptions aimed at making unlikely
the occurrence of a short-circuit in live conductors, the
Std. IEC 60439-1 suggests a series of measures which
depend on the conductor typology. As an example here
are the prescriptions intended for:
- bare conductors, or single-core conductors, with basic
insulation, e.g. cables complying with IEC 60227-3, for
which mutual contact or contact with conductive parts
shall be avoided, for example by use of spacers;
- single-core conductors with basic insulation and a
maximum permissible conductor-operating temperature
above 90° C, for example cables complying with IEC
60245-3, or heating resistant PVC insulated cables
according to IEC 60227-3, for which mutual contact
or contact with conductive parts is permitted where
there is no applied external pressure. Contact with
sharp edges must be avoided. There must be no risk
of mechanical damage. These conductors may only
be
loaded such that an operating temperature of 70° C
is
not exceeded:
- conductors with basic insulation (cables complying
with IEC 60227-3), having additional secondary
insulation, for example individual covered cables with
shrink sleeving or individually run cables in plastic
conduits, or conductors insulated with a very high
mechanical strength material (FTFE insulation), for
which there are no additional requirements if there is
no risk of mechanical damage.
3 Problems concerning short-circuit
3.3.1
Minimum anchor distances for conductors
One of the main problems which regard short-circuit
and which is to be faced directly by panel builders is the
maximum anchor distances of the conductors connected
to the circuit-breakers from the circuit-breaker terminals.
As known, inside the switchboards it is necessary that
cables and busbars are fastened to the frame.
In fact, during a short-circuit, the dynamic stresses on the
conductors could affect also the circuit-breaker terminals
causing damages. Figure 27 shows some diagrams
relevant to Tmax and Emax series circuit-breakers
allowing to determine, as a function of the maximum
peak current under short-circuit conditions and of the
circuit-breaker typology, the maximum distances from
the circuit-breaker terminals to the first anchor element
of the conductors.
The term conductor is used for busbars when the
current exceeds or is equal to 400A, whereas cables are
referred to when the current is lower than this value. This
distinction is made complying with the Tables 8 and 9 of
the Std. IEC 60439-1.
When specific requirements demand or prescribe the
use of busbars also for currents lower than 400A, the
distances which can be obtained by the diagrams shall
not undergo any variations, whereas the distances
referred to the use of busbars are not valid when using
cables.
Distance suggested for the first anchor element of busbars as a
function of the maximum prospective short-circuit current peak.
Figure 27
Tmax T1
350
300
250
200
150
100
50
0
10 100
I
pk
[kA]
L [mm]
43
ABB circuit-breakers inside LV switchboards
450
400
350
300
250
200
150
0
10
100
L [mm]
100
50
1000
I
pk
[kA]
I
pk
[kA]
500
400
350
300
250
200
150
0
10 100
L [mm]
100
50
1000
450
Tmax T3
Tmax T4
Tmax T2
Distance suggested for the first anchor element of busbars as a
function of the maximum prospective short-circuit current peak.
Circuit-breaker with horizontal and vertical terminals..
Emax
3 Problems concerning short-circuit
Tmax T5
Valid for:
- front and rear terminals
- connection by means of rigid busbars
700
400
500
300
200
0
10 100
L [mm]
100
1000
600
I
pk
[kA]
600
400
500
300
200
0
10 100
L [mm]
100
1000
I
pk
[kA]
0
40
I
pk
[kA]
60 80 100 120 140 160 180 200 220 240 260 280 300
50
100
150
200
250
300
350
400
450
500
L [mm]
E4 S-H
E6 H-V
E2 B-N
E3 N-S-H
E1 B
E2 L
E3 L
44 ABB circuit-breakers inside LV switchboards

3 Problems concerning short-circuit
Figure 28
200200
200200
300300
Tmax T1 Tmax T3
Tmax T5 Tmax T6 Tmax T7
200200
Tmax T2
5050
1÷10mm2
200200
200200
5050
16÷70mm2
6060
2.5÷10mm2
200
200
Tmax T4
As regards Tmax molded-case circuit-breakers, Figure
28 gives an example of the maximum distance (in mm)
suggested for the positioning of the nearest anchor sup-
port, in relation to the maximum peak current admitted
for the circuit-breaker.
45
ABB circuit-breakers inside LV switchboards
3 Problems concerning short-circuit
As regards Emax air circuit-breakers, Figure 29 gives an
example of the maximum distance (in mm) suggested
for the positioning of the nearest anchor support for the
busbars connecting to the circuit-breaker according to the
different types of terminals available and for the
highest
peak values, as derived from the curves of Figure 28.
Figure 29
3.3.2 Verification of the short-circuit withstand
strength and of the current limiting
characteristics of circuit-breakers
In some cases, the Std. IEC 60439-1 allows that the short-
circuit withstand strength of assemblies is not verified.
In particular, the following switchgear and controlgear
assemblies are free from verification:
-
those having rated short-time withstand currents or rated
conditional short-circuit currents lower than 10kA;
- those protected by current limiting devices with a limited
peak current not exceeding 17kA in correspondence
with the maximum prospective short-circuit current
measured at the terminals of the incoming circuit of
the assembly.
As known, the limiting characteristics of a circuit-breaker are a
function of the working voltage of the circuit-breaker itself.
Table 22 below gives - for the different protective circuit-
breakers and the most common voltages of the plant
the values which approximately represent the maximum
prospective short-circuit current in [kA] which guarantee
a limited peak current not exceeding 17kA, so that the
short-circuit withstand test for the switchboard is not to
be carried out.
Table 22
Circuit-breaker Rated voltage of the plant
Type
Rated
current In
[A] 230Vac 415Vac 500Vac 690Vac
S200 63 20 10 - -
S200M 63 25 15 - -
S200P 25 40 25 - -
S200P 32-63 25 15 - -
S800 125 50 50 15(In80A) 6(In80A)
10(In80A) 4.5(In80A)
S290 125 25 15 - -
T1 <160 50 35 15 6
T1 160 37 33 15 6
T2 32 120 85 50 10
T2 50 120 85 39 10
T2 63 120 65 30 10
T2 80 -160 120 50 29 10
T3 63 37 20 18 8
T3 80 27 18 17 8
T3 100 21 16 15 8
T3 125-160 18 15 14 8
T3 200-250 16 14 13 8
T4 20 200 200 150 80
T4 32-50 200 200 150 55
T4 80 200 100 48 32
T4 100-320 200 24 21 19
T5 T6 T7 320-1600 10 10 10 10
The short-circuit current value reported in the table above must be compared
with the breaking capacity of the circuit-breaker for the different versions
available.
Emax X1
Emax E1÷E6
200 200
200
P
Vertical
P
Horizontal
Front Flat
P
P
PP
Emax
Horizontal
P
[mm]
Vertical
P
[mm]
Front
P
[mm]
Flat
P
[mm]
E1-E2 250 250 - -
E3-E4-E6 150 150 - -
E1-E6 - - 250 250
46 ABB circuit-breakers inside LV switchboards

3.3.3 Problems concerning the installation
distances
The Std. IEC 60439-1 assigns the circuit-breaker ma-
nufacturers the task of defining the prescriptions for the
installation of these devices inside switchboards.
Hereunder, Figures 30 and 31 give, for ABB SACE cir-
cuit-breakers series Tmax and Emax respectively, the
indications relevant to the distances to be complied with
in the plants up to 690 Va.c.; such distances are already
specified in the circuit-breaker technical catalogues and
installation manuals.
Figure 30
3 Problems concerning short-circuit
A
B
C
I
HH
H
Insulation distances for installation in metallic cubicle
T1
T2
T3
T4
T5
T6
T7
A
[mm]
25
25
50
30(*)
30(*)
35(*)
50(*)
B
[mm]
20
20
25
25
25
25
20
C
[mm]
20
20
20
25(*)
25(*)
20
10
(*) For Un 440V and T6L all versions: distances A 100 mm
Note: For the insulation distances of the 1000 V circuit-breakers, please ask ABB SACE.
Distances between two circuit-breakers side by side or superimposed
For assembly side by side or superimposed, check that the connection busbars or cables
do not reduce the air insulation distance
Minimum centre distance for two circuit-breakers side by side
T1
T2
T3
T4
T5
T6
T7
3 poles
76
90
105
105
140
210
210
4 poles
102
120
140
140
184
280
280
Circuit-breaker width (mm)
3 poles
76.8
90
105
105
140(*)
210
210
4 poles
102
120
140
140
184(*)
280
280
Centre distance I [mm]
(*) For Un 500 V minimum centre I (mm) 3 poles 180, minimum centre I (mm) 4 poles 224
Minimum distance between two superimposed circuit-breakers
T1
T2
T3
T4
T5
T6
T7
60
90
140
160
160
180
180
H
[mm]
Cable terminal
Insulated cable
Connection -
not insulated
Note: The dimensions shown apply for operating voltage Un up to
690 V. The dimensions to be respected must be added to
the maximum dimensions of the various different versions
of the circuit-breakers, including the terminals. For 1000 V
versions, please ask ABB SACE.
47
ABB circuit-breakers inside LV switchboards
Figure 31
3 Problems concerning short-circuit
Compartment dimensions
Emax
E1
E2
E3
E4
E4f
E6
E6f
A
[mm]
400
400
500
700
-
1000
-
B
[mm]
490
490
630
790
880
1130
1260
Emax – withdrawable version
Emax – fixed version
380
500
A
3 poles
B
4 poles
242 min.
282 max
A
3 poles
B
4 poles
500
Nota: For Emax X1 CB, please consider the same indications of
Figure 30 referred to the insulation distance of Tmax T7 CB
48 ABB circuit-breakers inside LV switchboards

Annex A
Example of electrical switchboards with ABB circuit-breakers
This Annex contains considerations about two different typologies of switchboards with ABB circuit-breakers.
First example
Data table
Circuit Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9
Circuit-breaker E6H E3H E2L E2L S7L S7L S6L S5L S4L
Rated current In [A] 5000 2500 1250 1250 1600 1250 630 400 250
Rated diversity factor 0.9 0.8 0.9 0.9 0.85 0.85 0.85 0.85 0.85
Test current [A] 4500 2000 1125 1125 1360 1062.5 535.5 340 212.5
Rated short-time current Icw [kA] 100 100 - - - - - - -
Rated peak current Ipk [kA] 220 220 - - - - - - -
Rated conditional short-circuit current Icc [kA] - - 100 100 100 100 100 100 100
Switchboard characteristics
Switchboard dimensions Heigth: 2300 mm Width: 2900 mm Depth: 1100 mm
Degree of protection IP3X Form of separation 4B
The table above reports the data concerning the circuit-breakers installed in the switchboard and the relevant effective current carrying
capacities obtained by the tests carried out in compliance with IEC 60439-1.
From these results it is evident that, if the switchboard has been designed according to a correct layout and with suitable forms of se-
paration, by positioning the apparatuses properly and with conductors and busbars rated in compliance with cross-sectional areas and
minimum length prescribed by the Standard, the current carrying capacities of the circuit-breakers inside the switchboard shall be very
near to the rated ones.
From this table it results also how the main distribution circuit (orange trace), which is provided with a non-current-limiting circuit-breaker,
shall be rated to withstand the conditioned current for 1 second and its relevant peak; on the other hand, the distribution circuits (brown
trace), which are equipped with a current limiting circuit-breaker, shall be dimensioned according to the conditioned short-circuit current:
thus, for the section C, the circuit-breakers shall be rated to withstand the peak and specific energy let-through by E2L, whereas, for the
section A, they shall be sized according to the peak and specific energy let-through by S7L. Dimensioning carried out in compliance with
this criterion is valid only if it can guarantee that the possibility that a fault occurs on the distribution busbar is null. If not, the distribution
busbar too shall be dimensioned as the main busbar.
Annex A
S7L - 1600A
S7L - 1250A
S6L - 630A
S5L - 400A
S4L - 250A
E6 - 5000A E3 - 2500A
E2 - 1250A
E2 - 1250A
Supply
Section A Section B Section C
Configuration of the switchboard front
SACE
SACE
SACE
SACE
Q5
Q6
Q7
Q8
Q9
Q1 Q2
Q3
Q4
49
ABB circuit-breakers inside LV switchboards
Second example
Data table
Circuit Q1 Q2 Q3 Q4 Q5
Circuit-breaker E6H S7H T5H T5H T4H
Rated current In [A] 5000 1250 630 400 250
Rated diversity factor 11111
Test current [A] 5000 1250 630 400 250
Rated short-time current Icw [kA] 100 - - - -
Rated peak current Ipk [kA] 220 - - - -
Rated conditional short-circuit current Icc
[kA] 100 100 100 100
Switchboard characteristics
Switchboard dimensions Heigth: 2320 mm Width: 1800 mm Depth: 1240 mm
Degree of protection IP30 Form of separation 4
The conductors and busbars used for the realization of the circuits of this switchboard are of bigger cross-sections than those suggested
by the Standard. Under these conditions, as it results from an analysis of the data reported in the table, the effective current carrying
capacities of the circuits inside the switchboard turn out to coincide with the rated carrying capacities of the circuit-breakers.
The same remarks of the previous case are valid also for the verification of the busbar protection.
Annex A
Configuration of the switchboard front
Section A Section B
ChimneyChimney
SACE
E6H
withdrawable
5000A
S7
withdraw.
1250A
T5
withdraw.
630A
T5
withdraw.
400A
T4
fixed
250A
Q1
Q2
Q3
Q4
Q5
50 ABB circuit-breakers inside LV switchboards

Forms of internal separation
By dividing assemblies by means of barriers or partitions (metallic or non-metallic) into separate compartments or
enclosed protected spaces, protection against contact with hazardous live parts belonging to the adjacent functional
units and protection against the passage of solid foreign bodies from one unit of the assembly to an adjacent one
can be attained.
The following are typical forms of separation by barriers or partitions:
Annex B
Annex B
Form 1
No internal separation
Form 2
Separation of busbars from the functional
units
Form 2a
Terminals for external conductors not
separated from busbars
Form 2b
Terminals for external conductors separated
from busbars
Form 3
Separation of busbars from the functional units
and separation of all functional units from one
another. Separation of terminals for external
conductors from the functional units, but not
from those of other functional units
Form 3a
Terminals for external conductors not separated
from busbars
Form 3b
Terminals for external conductors separated
from busbars
Form 4
Separation of busbars from all functional units
and separation of all functional units from one
another. Separation of terminals for external
conductors associated with a functional unit
from those of any other functional unit and
the busbars
Form 4a
Terminals for external conductors in the same
compartment as the associated functional
unit
Form 4b
Terminals for external conductors not in
the same compartment as the associated
functional unit, but in individual, separate,
enclosed protected spaces or compartments
Caption
aEnclosure
b Internal separation
cFunctional units including terminals for associated external conductors
dBusbars, including distribution busbars
b
a
d
c
Symbols
51
ABB circuit-breakers inside LV switchboards
Annex C
Degrees of protection (IP code)
As example, the table below reports the minimum degrees of protection for a switchgear and controlgear assembly
to be installed in the specified environments in compliance with the above mentioned Standards.
The degree of protection prescribed for an apparatus against access to hazardous live parts and against ingress of
solid foreign objects and liquids is indicated by the Code IP... in accordance with the Std. IEC 60529.
A brief description of the IP Code elements is given hereunder. For full details reference shall be made to the Std.
IEC 60529.
When a characteristic numeral is not required to be specified, it shall be replaced by the letter “X” (“XX” if both numerals are omitted).
Code letters (International Protection) IP
First characteristic numeral (numerals 0 to 6, or letter X) Against ingress of solid foreign objects
Second characteristic numeral (numerals 0 to 8, or letter X)
Against ingress of water with harmful effects
Additional letter (optional) (letters A, B, C, D): Against access to hazardous parts
Supplementary letter (optional) (letters H, M, S, W): Supplementary information
Type of assemblies / Type of environment Standards and sub-clause Minimum degree of protection
Switchgear and controlgear assembly: enclosed switchboard IEC 60439-1 sub-clause 2.3.3 Not defined
Assemblies for outdoor installation IEC 60439-1 sub-clause 7.2.1.3 IPX3
Assemblies with protection by total insulation IEC 60439-1 sub-clause 7.4.3.2.2 IP2XC
Installations in normal environments
Live parts which are not be touched intentionally IEC 60364-4 sub-clause 412.2.1 IPXXB (IP2X)
Live parts which are readily accessible (horizontal top) IEC 60364-4 sub-clause 412.2.2 IPXXD (IP4X)
Installations in locations containing a bath tube or shower basin
Zones 1 and 2 IEC 60364-7 sub-clause 701.512.2 IPX4
Zone 3 IEC 60364-7 sub-clause 701.512.2 IPX1
Zones 1–2–3 public baths where water jets are used for
cleaning purposes IEC 60364-7 sub-clause 701.512.2 IPX5
Installations for swimming-pools
Zone 0 IEC 60364-7 sub-clause 702.512.2 IPX8
Zone 1 IEC 60364-7 sub-clause 702.512.2 IPX5
Zone 2 for indoor locations IEC 60364-7 sub-clause 702.512.2 IPX2
Zone 2 for outdoor location IEC 60364-7 sub-clause 702.512.2 IPX4
Zone 2 where water jets are used for cleaning purposes IEC 60364-7 sub-clause 702.512.2 IPX5
Installations for rooms and cabins containing sauna heaters IEC 60364-7 sub-clause 703.512.2 IP24
Assemblies for construction sites (ACS) IEC 60439-4 sub-clause 7.2.1.1 IP44
Annex C
52 ABB circuit-breakers inside LV switchboards

Glossary
Glossary
fn rated diversity factor
Incrated current of the circuit
I2test, I3test.... test current of the circuit “2”, test current of the circuit “3”, etc.
TTabsolute temperature [°C]
TAair ambient temperature [°C]
Ttemperature-rise [K]
LV low voltage
PTTA partially type-tested low-voltage switchgear and controlgear assembly
d.c. direct current
a.c. alternating current
Ib full load current
PCB power loss of the circuit-breaker at Ib
PnCB power loss of the circuit-breaker at InCB
InCB rated current of the circuit-breaker
PSB power loss of the busbar at Ib
PnSB power loss of the busbar at InSB
InSB busbar rated current
LSB busbar length
PTQ total power dissipated inside the switchboard
AEeffective cooling surface
bsurface factor
A0sum of the individual surface areas
dtemperature coefficient
IP degree of protection
Icw rated short-time current
Ipk rated peak withstand current
Icc rated conditional short-circuit current
Ik prospective short-circuit current
npeak factor
Technical Application Paper
QT1
Low voltage selectivity with ABB circuit-breakers
QT2
MV/LV trasformer substations: theory and exam-
ples of short-circuit calculation
QT3
Distribution systems and protection against indi-
rect contact and earth fault
QT4
ABB circuit-breakers inside LV switchboards
QT5
ABB circuit-breakers for direct current
applications
QT6
Arc-proof low voltage switchgear and controlge-
ar assemblies
1SDC007103G0202 May ’08
Printed in Italy
6.000 - CAL
December 2006
4Technical Application Papers
http://www.abb.com
Due to possible developments of standards as well as of
materials, the characteristics and dimensions specified in this
document may only be considered binding after confirmation
by ABB SACE.
ABB SACE
A division of ABB S.p.A.
L.V. Breakers
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433