ArticlePDF Available

Power Quality Improvement and LVRT Capability Enhancement of Wind Farms by Means of an Inductive Filtering Method

Authors:

Abstract

Unlike the traditional method for power quality improvement and low-voltage ride through (LVRT) capability enhancement of wind farms, this paper proposes a new wind power integrated system by means of an inductive filtering method, especially if it contains a grid-connected transformer, a static synchronous compensator (STATCOM) and fully-tuned (FT) branches. First, the main circuit topology of the new wind power integrated system is presented. Then, the mathematical model is established to reveal the mechanism of harmonic suppression and the reactive compensation of the proposed wind power integrated system, and then the realization conditions of the inductive filtering method is obtained. Further, the control strategy of STATCOM is introduced. Based on the measured data for a real wind farm, the simulation studies are carried out to illustrate the performance of the proposed new wind power integrated system. The results indicate that the new system can not only enhance the LVRT capability of wind farms, but also prevent harmonic components flowing into the primary (grid) winding of the grid-connected transformer. Moreover, since the new method can compensate for reactive power in a wind farm, the power factor at the grid side can be improved effectively.
energies
Article
Power Quality Improvement and LVRT Capability
Enhancement of Wind Farms by Means of an
Inductive Filtering Method
Yanjian Peng 1, Yong Li 1, *, Zhisheng Xu 2, Ming Wen 2, Longfu Luo 1, Yijia Cao 1and
Zbigniew Leonowicz 3
1College of Electrical and Information Engineering, Hunan University, Changsha 410082, China;
yjpeng@hnu.edu.com (Y.P.); llf@hnu.edu.cn (L.L.); yjcao@hnu.edu.cn (Y.C.)
2Hunan Electrical Power Corporation Economical & Technical Research, Changsha 410004, China;
xuzs2@hn.sgcc.com.cn (Z.X.); firelight_81107@126.com (M.W.)
3Department of Electrical Engineering, Wroclaw University of Technology, Wroclaw 50370, Poland;
zbigniew.leonowicz@pwr.edu.pl
*Correspondence: yongli@hnu.edu.cn; Tel.: +86-731-8882-2213
Academic Editor: Rodolfo Araneo
Received: 27 February 2016; Accepted: 13 April 2016; Published: 20 April 2016
Abstract:
Unlike the traditional method for power quality improvement and low-voltage ride
through (LVRT) capability enhancement of wind farms, this paper proposes a new wind power
integrated system by means of an inductive filtering method, especially if it contains a grid-connected
transformer, a static synchronous compensator (STATCOM) and fully-tuned (FT) branches. First, the
main circuit topology of the new wind power integrated system is presented. Then, the mathematical
model is established to reveal the mechanism of harmonic suppression and the reactive compensation
of the proposed wind power integrated system, and then the realization conditions of the inductive
filtering method is obtained. Further, the control strategy of STATCOM is introduced. Based on
the measured data for a real wind farm, the simulation studies are carried out to illustrate the
performance of the proposed new wind power integrated system. The results indicate that the
new system can not only enhance the LVRT capability of wind farms, but also prevent harmonic
components flowing into the primary (grid) winding of the grid-connected transformer. Moreover,
since the new method can compensate for reactive power in a wind farm, the power factor at the grid
side can be improved effectively.
Keywords:
wind farm; inductive filtering method; transformer; static synchronous compensator
(STATCOM); low-voltage ride through (LVRT); harmonic current; power quality
1. Introduction
In recent years, wind power generation has become a very attractive source of renewable energy
thanks to its unique merits: it is economical, clean and inexhaustible. Thus, more and more wind
farms are being connected to power systems [
1
,
2
]. However, such large-scale integration of wind
power into the power system brings technical challenges for the wind farm operators; for example,
the wind turbines should keep continued connection with the power system during a fault and
other conditions [
3
,
4
]. Moreover, it is important for wind farms to improve power quality [
5
10
].
For modern wind farms, variable speed wind turbines, such as double-fed induction generator
(DFIG) and permanent magnet synchronous generator (PMSG), are the commonly installed turbine
types. It is worth noting that the modern wind turbines are based on the voltage source converters
(VSCs), which consist of power electronics device and employ a carrier-based pulse width modulation
(PWM) technique. The harmonic components are inevitably generated by VSCs. Furthermore,
Energies 2016,9, 302; doi:10.3390/en9040302 www.mdpi.com/journal/energies
Energies 2016,9, 302 2 of 18
the imperfections in control system of wind turbines and the nonlinearities in generators and
transformers also produce harmonic components, polluting the public network. Particularly, the
harmonic components freely flow into the grid-connected transformer, which inevitably leads to a
series of problems, such as harmonic loss, vibration and noise. Another concern of grid-integrated
wind power system is the output voltage fluctuation resulting from the wind speed fluctuation. Voltage
fluctuation may cause serious problems for electric devices requiring a high-quality voltage supply.
Therefore, the main purpose of the normal operation requirement for wind farms is to maintain voltage
stability and provide high power quality.
Moreover, many grid codes in several countries require wind turbines to remain connected to
the power system under fault conditions, in order to restore the system to the normal conditions as
quickly as possible. Such requirements are known as fault ride through (FRT) or low-voltage ride
through (LVRT) capability of wind turbines. For example, the grid code ENTSO-E is recommended as
a common frame for all European countries [
11
]. Figure 1shows the ENTSO-E LVRT requirement for
grid-connection, where the wind farms are expected to stay connected even when the grid voltage
drops down to 0. In summary, the harmonic components, the voltage fluctuation and the LVRT
capability are the crucial issues and should be carefully addressed to improve the power quality and
increase the operating efficiency of wind farms [1215].
Energies2016,9,3022of18
imperfectionsincontrolsystemofwindturbinesandthenonlinearitiesingeneratorsand
transformersalsoproduceharmoniccomponents,pollutingthepublicnetwork.Particularly,the
harmoniccomponentsfreelyflowintothegridconnectedtransformer,whichinevitablyleadstoa
seriesofproblems,suchasharmonicloss,vibrationandnoise.Anotherconcernofgridintegrated
windpowersystemistheoutputvoltagefluctuationresultingfromthewindspeedfluctuation.
Voltagefluctuationmaycauseseriousproblemsforelectricdevicesrequiringahighqualityvoltage
supply.Therefore,themainpurposeofthenormaloperationrequirementforwindfarmsisto
maintainvoltagestabilityandprovidehighpowerquality.
Moreover,manygridcodesinseveralcountriesrequirewindturbinestoremainconnectedto
thepowersystemunderfaultconditions,inordertorestorethesystemtothenormalconditionsas
quicklyaspossible.Suchrequirementsareknownasfaultridethrough(FRT)orlowvoltageride
through(LVRT)capabilityofwindturbines.Forexample,thegridcodeENTSOEisrecommended
asacommonframeforallEuropeancountries[11].Figure1showstheENTSOELVRTrequirement
forgridconnection,wherethewindfarmsareexpectedtostayconnectedevenwhenthegridvoltage
dropsdownto0.Insummary,theharmoniccomponents,thevoltagefluctuationandtheLVRT
capabilityarethecrucialissuesandshouldbecarefullyaddressedtoimprovethepowerqualityand
increasetheoperatingefficiencyofwindfarms[12–15].
Time (sec)
0
0.2
0.4
0.6
0.8
1.0
Voltage (p.u)
0.14-0.25 sec 1.5-3 sec
Figure1.ENTSOElowvoltageridethrough(LVRT)requirementforgridconnection.
Generally,inordertoimprovethepowerquality,windfarmsmainlyadoptthepassivepower
filtering(PPF)methodtosuppresstheharmoniccurrentsandcompensateforreactivepower.The
passivepowerfiltersareconfiguredatthewindfarmsideofthegridconnectedtransformer[16].
However,itsfilteringperformanceiseasilyaffectedbyitsownparameterschange.Inaddition,the
passivefilterusuallyadoptsadetuneddesigninordertoavoidthepotentialseries/parallelresonance
withthesystemimpedance,meaningthatthefilteringperformanceisreducedtoacertaindegree.
SincethePPFmethodcannotprovideagoodpowerfactoroverthelargewindpowerrange,the
reactivecompensationdevicesareusuallyappliedatthewindfarmsideofthegridconnected
transformer,suchasthestaticVARcompensator(SVC)andthestaticsynchronouscompensator
(STATCOM)[17].TheLVRTcapabilityofwindfarmscanbeimprovedbyinjectingorabsorbingthe
reactivepowerfromSVC.However,SVCgeneratesharmoniccurrents,whichisnotgoodforthe
publicnetwork[18].ComparedtoSVC,STATCOMhasbetterperformanceatthereactive
compensationandimprovingLVRTcapabilityofwindfarms.ItshouldbenotedthattheSTATCOM
usuallyadoptsacouplingtransformertointerfacewithgrid,whichincreasesthecostofinvestment.
Inordertosatisfythemultiplepurposesofsuppressingharmoniccurrents,compensating
reactivepowerandimprovingtheLVRTcapability,thispaperproposesanewwindpower
integratedsystembymeansofthecombinationoftheinductivefilteringmethodandaSTATCOM.
Theinductivefilteringmethodwasfirstproposedin[19]forthehighvoltageDC(HVDC)system,
and[20,21]showedtheoutstandingperformanceonharmonicsuppressionandreactivepower
compensation,respectively.Theproposedwindpowerintegratedsystemfullyutilizesthefiltering
Figure 1. ENTSO-E low-voltage ride through (LVRT) requirement for grid connection.
Generally, in order to improve the power quality, wind farms mainly adopt the passive power
filtering (PPF) method to suppress the harmonic currents and compensate for reactive power. The
passive power filters are configured at the wind farm side of the grid-connected transformer [
16
].
However, its filtering performance is easily affected by its own parameters change. In addition, the
passive filter usually adopts a detuned design in order to avoid the potential series/parallel resonance
with the system impedance, meaning that the filtering performance is reduced to a certain degree. Since
the PPF method cannot provide a good power factor over the large wind power range, the reactive
compensation devices are usually applied at the wind farm side of the grid-connected transformer,
such as the static VAR compensator (SVC) and the static synchronous compensator (STATCOM) [
17
].
The LVRT capability of wind farms can be improved by injecting or absorbing the reactive power
from SVC. However, SVC generates harmonic currents, which is not good for the public network [
18
].
Compared to SVC, STATCOM has better performance at the reactive compensation and improving
LVRT capability of wind farms. It should be noted that the STATCOM usually adopts a coupling
transformer to interface with grid, which increases the cost of investment.
In order to satisfy the multiple purposes of suppressing harmonic currents, compensating reactive
power and improving the LVRT capability, this paper proposes a new wind power integrated system
by means of the combination of the inductive filtering method and a STATCOM. The inductive filtering
method was first proposed in [
19
] for the high-voltage DC (HVDC) system, and [
20
,
21
] showed the
outstanding performance on harmonic suppression and reactive power compensation, respectively.
Energies 2016,9, 302 3 of 18
The proposed wind power integrated system fully utilizes the filtering and reactive compensation
ability of the new grid-connected transformer with fully-tuned (FT) branches and STATCOM, aiming
at the power quality improvement and LVRT capability enhancement of wind farms. This paper
significantly develops initial ideas presented in [22].
The structure of this paper is organized as follows. Section 2presents the main circuit topology
of the new wind power integrated system and describes its technical features. Section 3establishes
the equivalent circuit model of the new wind power integrated system, and then the corresponding
mathematical model is established to reveal the operation of the inductive filtering method. Section 4
shows the properties of the new wind power integrated system related to reactive power compensation.
In Section 5, the transient simulation of the new wind power integrated system is carried out to validate
the theoretical analysis. Finally, the conclusions are given in Section 6.
2. Main Circuit Topology of the New Wind Power Integrated System
2.1. Topology
Figure 2shows the main circuit topology of the proposed wind farm integrated system. The wind
farm is composed of 25 PMSGs with a rating of 2 MW each, with the total installed capacity of
50 MW. Each wind turbine is connected in parallel to the 35 kV bus via a 2.2 MVA, 0.69/35 kV
transformer and then connected to the public network by means of a new grid-connected transformer.
The new transformer has the grid-, the load- and the filtering-winding. The wiring scheme of the
new grid-connected transformer is shown in Figure 3. As with the description in [
19
], in order to
implementing inductive filtering method, the compensation devices, which consist of the inductive
filtering device and a cascade multiple STATCOM with
˘
10 Mvar rating, should be connected to the
filtering-winding of the new grid-connected transformer. In this way, the coupling transformer can
be saved. Moreover, the STATCOM consists of the six H-bridges, these modules being connected
in cascade in each phase. It is worth noting that this proposed wind power integrated system can
suppress the harmonic components whatever they come from the public network or the wind farm,
because the inductive filtering devices have the natural ability of suppressing harmonic components
coming from both directions. Further, the STATCOM and FT branches can also compensate for the
reactive power for the wind farm, especially the STATCOM, which can compensate for the dynamic
voltage changes of the wind farm by means of injecting or absorbing reactive power.
Energies2016,9,3023of18
andreactivecompensationabilityofthenewgridconnectedtransformerwithfullytuned(FT)
branchesandSTATCOM,aimingatthepowerqualityimprovementandLVRTcapabilityenhancement
ofwindfarms.Thispapersignificantlydevelopsinitialideaspresentedin[22].
Thestructureofthispaperisorganizedasfollows.Section2presentsthemaincircuittopology
ofthenewwindpowerintegratedsystemanddescribesitstechnicalfeatures.Section3establishes
theequivalentcircuitmodelofthenewwindpowerintegratedsystem,andthenthecorresponding
mathematicalmodelisestablishedtorevealtheoperationoftheinductivefilteringmethod.Section
4showsthepropertiesofthenewwindpowerintegratedsystemrelatedtoreactivepower
compensation.InSection5,thetransientsimulationofthenewwindpowerintegratedsystemis
carriedouttovalidatethetheoreticalanalysis.Finally,theconclusionsaregiveninSection6.
2.MainCircuitTopologyoftheNewWindPowerIntegratedSystem
2.1.Topology
Figure2showsthemaincircuittopologyoftheproposedwindfarmintegratedsystem.The
windfarmiscomposedof25PMSGswitharatingof2MWeach,withthetotalinstalledcapacityof
50MW.Eachwindturbineisconnectedinparalleltothe35kVbusviaa2.2MVA,0.69/35kV
transformerandthenconnectedtothepublicnetworkbymeansofanewgridconnected
transformer.Thenewtransformerhasthegrid,theload‐ andthefilteringwinding.Thewiring
schemeofthenewgridconnectedtransformerisshowninFigure3.Aswiththedescriptionin[19],
inordertoimplementinginductivefilteringmethod,thecompensationdevices,whichconsistofthe
inductivefilteringdeviceandacascademultipleSTATCOMwith±10Mvarrating,shouldbe
connectedtothefilteringwindingofthenewgridconnectedtransformer.Inthisway,thecoupling
transformercanbesaved.Moreover,theSTATCOMconsistsofthesixHbridges,thesemodules
beingconnectedincascadeineachphase.Itisworthnotingthatthisproposedwindpowerintegrated
systemcansuppresstheharmoniccomponentswhatevertheycomefromthepublicnetworkorthe
windfarm,becausetheinductivefilteringdeviceshavethenaturalabilityofsuppressingharmonic
componentscomingfrombothdirections.Further,theSTATCOMandFTbranchescanalso
compensateforthereactivepowerforthewindfarm,especiallytheSTATCOM,whichcan
compensateforthedynamicvoltagechangesofthewindfarmbymeansofinjectingorabsorbing
reactivepower.
FT branches
L
a
L
b
L
c
v
a1
v
a2
v
a6
C
C
C
i
La
i
Lb
i
Lc
i
fa
i
fb
i
fc
i
a
i
b
i
c
V
ab
V
bc
V
ca
i
Sa
i
Sb
i
Sc
Ls V
Sa
V
Sb
V
Sc
3-ph,
110kV,50Hz
v
b1
v
b2
v
b6
C
C
C
v
c1
v
c2
v
c6
C
C
C
Bus1 Bus2
Line 1
Line 2
Three- phase
transmission line
PMSG-based Wind Farm
25 Turbines, 50MW
MSC GSC Tr
4th 5th 7th 1 1th
25 Turbines, 50MW
25 Transformers, one for
each w ind turbine .
Figure2.Maincircuittopologyofproposedwindfarmintegratedsystem.
Figure 2. Main circuit topology of proposed wind farm integrated system.
Energies 2016,9, 302 4 of 18
Energies2016,9,3024of18
*
*
*
*
*
*
*
*
*
A
B
C
a1
b1
c1
a2
b2
c2
Filtering-winding
Load-winding
Grid-winding
Figure3.Wiringschemeofthenewgridconnectedtransformer.
2.2.WindTurbineModeling
TheprimaryimportantcomponentinthemodelingofPMSGisthewindturbinemodel,which
cantransformwindenergytothepowerPmech,expressedby[23–25],
32 ),(
2
1

pmech CRP (1)
whereρistheairdensity;ωisthewindspeed;Ristherotorradius;andCp(λ,β)isthepower
coefficient,dependingonthebladeangleβandthetipspeedratioλ.
Thetipspeedratiocanbedescribedby
R
R
(2)
whereωRistherotorspeed.
Foreachbladeangleβ,thereisanoptimaltipspeedratioλoptandacorrespondingoptimalCp
valuethatisanoptimalCpoptwiththemaximalpowercapturefromthewind.Then,thepower
coefficientisobtainedas
0068.0)54.0
116
(5176.0),(
21
i
eC
i
p(3)
1
035.0
08.0
11
3
i
(4)
AccordingtoEquations(3)and(4),theCpλcurvesfordifferentbladeanglesareobtainedas
showninFigure4.
0
0.1
0.2
0.3
0.4
0.5 β=25 β=20 β=15 β=10 β=5 β=0
0246810 12 14 16
Ti
p
s
p
eed ratio
Power coefficient
Figure4.Powercoefficienttipspeedratio(Cpλ)curvesfordifferentbladeangles.
Figure 3. Wiring scheme of the new grid-connected transformer.
2.2. Wind Turbine Modeling
The primary important component in the modeling of PMSG is the wind turbine model, which
can transform wind energy to the power Pmech, expressed by [2325],
Pmech 1
2ρπR2Cppλ,βqω3(1)
where
ρ
is the air density;
ω
is the wind speed; Ris the rotor radius; and C
p
(
λ
,
β
) is the power
coefficient, depending on the blade angle βand the tip speed ratio λ.
The tip speed ratio can be described by
λωRR
ω(2)
where ωRis the rotor speed.
For each blade angle
β
, there is an optimal tip speed ratio
λopt
and a corresponding optimal
C
p
value that is an optimal C
popt
with the maximal power capture from the wind. Then, the power
coefficient is obtained as
Cppλ,βq 0.5176p116
λi
´0.4β´5qe
´21
λi`0.0068λ(3)
1
λi
1
λ`0.08β´0.035
β3`1(4)
According to Equations (3) and (4), the C
p
-
λ
curves for different blade angles are obtained as
shown in Figure 4.
p
p
Figure 4. Power coefficient-tip speed ratio (Cp-λ) curves for different blade angles.
Energies 2016,9, 302 5 of 18
2.3. Harmonic Currents Produced by a Wind Farm
It can be seen from Figure 2that the PMSG contains the machine-side converter (MSC) and
the grid-side converter (GSC). The GSC operates at the grid frequency 50 Hz and is responsible for
regulating the DC bus voltage and can also be used to generate or absorb reactive power. However, the
MSC operates at a much lower frequency and is responsible for regulating the active and the reactive
power of the generator. Due to the MSC not being directly connected to the grid, the harmonic currents
generated by MSC cannot transfer to the grid but to the generator. Both the MSC and the GSC adopt
the PWM techniques for insulated gate bipolar transistor (IGBT) control [26,27].
When the PMSG operates at the normal conditions, the output harmonic characteristic of the two
converters is influenced by the following factors: the carrier frequency f
s
, the modulation ratio m
a
, and
other factors. Generally, the harmonic orders nproduced by these two converters can be determined
by [9]:
nk1ˆma˘k2(5)
where k
1
= 1, 2, 3, etc.; and k
2
= 1, 2, 3, etc. Note that k
1
and k
2
cannot be simultaneously equal to even
or odd numbers.
Generally, the modulation ratio m
a
is large, thus, we can see from Equation (5) that the output
harmonic currents of these two converters have less low-order, but high levels of high-order harmonic
currents can be generated. As mentioned in the above analysis, only the harmonic currents produced
by the GSC can transfer to the grid. In fact, in the real-world wind farm, the values of the high-order
harmonic currents is low whereas 4th, 5th, 7th and 11th have the high magnitudes, as shown in
Figure 5. These data are measured in a real 50 MW wind farm with PMSGs, which operates with
two different wind power ratios. This real wind farm is called the Baolian wind farm, located in the city
of Shaoyang in the Hunan Province in China. The geographical information of the wind farm is shown
in Figure 6. Actually, these harmonic currents are generated due to the non-ideal operation of the
PWM technique and also due to the control interaction of PMSGs with the public network [
27
]. In this
paper, the inductive filtering method is proposed to suppress these low orders harmonic currents, and
the design parameters for the wind farm with the inductive filtering method is discussed in Section 4.
Energies2016,9,3025of18
2.3.HarmonicCurrentsProducedbyaWindFarm
ItcanbeseenfromFigure2thatthePMSGcontainsthemachinesideconverter(MSC)andthe
gridsideconverter(GSC).TheGSCoperatesatthegridfrequency50Hzandisresponsiblefor
regulatingtheDCbusvoltageandcanalsobeusedtogenerateorabsorbreactivepower.However,
theMSCoperatesatamuchlowerfrequencyandisresponsibleforregulatingtheactiveandthe
reactivepowerofthegenerator.DuetotheMSCnotbeingdirectlyconnectedtothegrid,the
harmoniccurrentsgeneratedbyMSCcannottransfertothegridbuttothegenerator.BoththeMSC
andtheGSCadoptthePWMtechniquesforinsulatedgatebipolartransistor(IGBT)control[26,27].
WhenthePMSGoperatesatthenormalconditions,theoutputharmoniccharacteristicofthe
twoconvertersisinfluencedbythefollowingfactors:thecarrierfrequencyfs,themodulationratio
ma,andotherfactors.Generally,theharmonicordersnproducedbythesetwoconverterscanbe
determinedby[9]:
21 kmkn a (5)
wherek1=1,2,3,etc.;andk2=1,2,3,etc.Notethatk1andk2cannotbesimultaneouslyequaltoeven
oroddnumbers.
Generally,themodulationratiomaislarge,thus,wecanseefromEquation(5)thattheoutput
harmoniccurrentsofthesetwoconvertershavelessloworder,buthighlevelsofhighorder
harmoniccurrentscanbegenerated.Asmentionedintheaboveanalysis,onlytheharmoniccurrents
producedbytheGSCcantransfertothegrid.Infact,intherealworldwindfarm,thevaluesofthe
highorderharmoniccurrentsislowwhereas4th,5th,7thand11thhavethehighmagnitudes,as
showninFigure5.Thesedataaremeasuredinareal50MWwindfarmwithPMSGs,whichoperates
withtwodifferentwindpowerratios.ThisrealwindfarmiscalledtheBaolianwindfarm,locatedin
thecityofShaoyangintheHunanProvinceinChina.Thegeographicalinformationofthewindfarm
isshowninFigure6.Actually,theseharmoniccurrentsaregeneratedduetothenonidealoperation
ofthePWMtechniqueandalsoduetothecontrolinteractionofPMSGswiththepublicnetwork[27].
Inthispaper,theinductivefilteringmethodisproposedtosuppresstheselowordersharmonic
currents,andthedesignparametersforthewindfarmwiththeinductivefilteringmethodisdiscussed
inSection4.
245 11 17
Harmonic order
Harmonic currents (A)
0
1
2
3
4
5
37
13
68 1923
25
P/P
N
= 14%
P/P
N
= 35%
Figure5.FastFouriertransformationresultsontheoutputcurrentsofwindfarmoperatingwith
differentwindpowerratios.
Figure 5.
Fast Fourier transformation results on the output currents of wind farm operating with
different wind power ratios.
Energies 2016,9, 302 6 of 18
Energies2016,9,3026of18
Figure6.GeographicalinformationoftheBaolianwindfarm.
3.TheoreticalAnalysis
3.1.HarmonicModelandEquivalentCircuitModel
Figure7showsthesinglephaseequivalentcircuitmodelofthenewgridconnectedtransformer
withFTbranchesandSTATCOM,wheretheVSCbasedwindturbinegeneratorsareregardedasthe
voltagesource.AccordingtotheflowpathofthenorderharmoniccurrentshowninFigure7,the
followingequationscanbeobtained:
nn
STnfnn
nSn
II
III
II
2
3
1
(6)
whereI1n,I2nandI3naretheharmoniccurrentsinthegrid,theload‐(windfarmside)andthefiltering
windingofthenewgridconnectedtransformer,respectively;additionally,ISn,In,IfnandISTnarethe
norderharmoniccurrentsatthegridside,theloadside,theFTbranchessideandtheSTATCOM
side,respectively.NotethattheSTATCOMcannotcompensatefortheharmoniccurrents,i.e.,ISTn=0.
Z
fn
N
3
N
2
N
1
Z
w
Wind farm
I
n
+
I
1n
I
2n
I
3n
V
w
STATCOM
I
fn
I
STn
V
sn
+
Z
sn
I
sn
Figure7.Thesinglephaseequivalentcircuitmodelofthenewgridconnectedtransformerwith
fullytuned(FT)branches.
Similarly,wecanobtainthevoltageequationsatthenorderharmonicfrequency,i.e.,
Figure 6. Geographical information of the Baolian wind farm.
3. Theoretical Analysis
3.1. Harmonic Model and Equivalent Circuit Model
Figure 7shows the single-phase equivalent circuit model of the new grid-connected transformer
with FT branches and STATCOM, where the VSC-based wind turbine generators are regarded as the
voltage source. According to the flow path of the n-order harmonic current shown in Figure 7, the
following equations can be obtained:
$
&
%
ISn I1n
I3n ´If n ´ISTn
I2nIn
(6)
where I
1n
,I
2n
and I
3n
are the harmonic currents in the grid-, the load- (wind farm side) and the
filtering-winding of the new grid-connected transformer, respectively; additionally, I
Sn
,I
n
,I
fn
and
I
STn
are the n-order harmonic currents at the grid side, the load side, the FT branches side and the
STATCOM side, respectively. Note that the STATCOM cannot compensate for the harmonic currents,
i.e.,ISTn = 0.
Energies2016,9,3026of18
Figure6.GeographicalinformationoftheBaolianwindfarm.
3.TheoreticalAnalysis
3.1.HarmonicModelandEquivalentCircuitModel
Figure7showsthesinglephaseequivalentcircuitmodelofthenewgridconnectedtransformer
withFTbranchesandSTATCOM,wheretheVSCbasedwindturbinegeneratorsareregardedasthe
voltagesource.AccordingtotheflowpathofthenorderharmoniccurrentshowninFigure7,the
followingequationscanbeobtained:
nn
STnfnn
nSn
II
III
II
2
3
1
(6)
whereI1n,I2nandI3naretheharmoniccurrentsinthegrid,theload‐(windfarmside)andthefiltering
windingofthenewgridconnectedtransformer,respectively;additionally,ISn,In,IfnandISTnarethe
norderharmoniccurrentsatthegridside,theloadside,theFTbranchessideandtheSTATCOM
side,respectively.NotethattheSTATCOMcannotcompensatefortheharmoniccurrents,i.e.,ISTn=0.
Z
fn
N
3
N
2
N
1
Z
w
Wind farm
I
n
+
I
1n
I
2n
I
3n
V
w
STATCOM
I
fn
I
STn
V
sn
+
Z
sn
I
sn
Figure7.Thesinglephaseequivalentcircuitmodelofthenewgridconnectedtransformerwith
fullytuned(FT)branches.
Similarly,wecanobtainthevoltageequationsatthenorderharmonicfrequency,i.e.,
Figure 7.
The single-phase equivalent-circuit model of the new grid-connected transformer with
fully-tuned (FT) branches.
Energies 2016,9, 302 7 of 18
Similarly, we can obtain the voltage equations at the n-order harmonic frequency, i.e.,
$
&
%
V1nVSn ´ZSn ISn
V3nVf n
Vf n Zf n If n
(7)
where V
1n
and V
3n
are the harmonic voltage in the grid- and the filtering-winding of the new
grid-connected transformer, respectively; V
fn
is the harmonic voltage of the FT branches; V
Sn
is
the harmonic voltage at the grid side.
Moreover, the magnetic-potential balance equation of the new transformer can be expressed
as follows:
N1I1n`N2I2n`N3I3n0 (8)
where N
1
,N
2
,N
3
are the numbers of turns of the grid-, the load- and the filtering-winding, respectively.
Then, according to the theory of the multi-winding transformer and combining the equivalent
circuit model shown in Figure 7, the voltage transfer equations can be obtained as follows [28]:
#V2n´N2
N1V1n ´ N1
N2Z21nI1n´N3
N2Z2nI3n
V2n´N2
N3V3n ´ N3
N2Z23nI3n´N1
N2Z2nI1n
(9)
The harmonic equivalent impedance of the grid-, load-, and filtering-winding of the new
grid-connected transformer can be expressed as
$
&
%
Z1n1
2`Z21n`Z13n´Z1
23n˘
Z2n1
2`Z21n`Z23n´Z1
13n˘
Z3n1
2`Z31n`Z32n´Z1
12n˘
(10)
where Z
12n
,Z
13n
and Z
23n
are the short-circuit impedance between the grid- and load-winding,
between grid- and filtering-winding, between load- and filtering-winding of the new grid-connected
transformer, respectively. They can be obtained by the transformer short-circuit test.
According to the model, the current in the grid-winding of the new grid-connected transformer
can be expressed as follows:
ISn ´
N1N2´Z3n`Zf n¯
N2
1´Z3n`Zf n¯`N2
3pZ1n´ZSnq
In´N2
3VSn
N2
1´Z3n`Zf n¯`N2
3pZ1n´ZSnq
(11)
Assuming that there is no or little harmonic voltage in the public network, that is to say, V
Sn «
0,
the above Equation (11) can be rewritten as
ISn ´
N1N2´Z3n`Zf n¯
N2
1´Z3n`Zf n¯`N2
3pZ1n´ZSnq
In(12)
From Equation (12), it can be seen that as long as the Z
3n
and Z
fn
are approximately equal
to 0, the source harmonic current I
Sn
is approximately equal to 0, which means there will be no
induction harmonic current in the grid-winding of the grid-connected transformer. Therefore, in order
to implementing inductive filtering method, there are two conditions must be realized: one is the
impedance of FT branches should be 0 at the resonant frequency, and the other is the impedance
of filtering-winding of new grid-connected transformer also should be 0. The designed method for
implementing inductive filtering method is given in Section 4.1.
Energies 2016,9, 302 8 of 18
3.2. Reactive Power Compensation Characteristics
In the wind power integrated system, the FT branches and STATCOM can compensate for
the reactive power that the wind farm needs. The current distribution in the new grid-connected
transformer is shown in Figure 8. Correspondingly, the phasor diagram of the load-winding’s voltages
and currents of the new grid-connected transformer can be obtained, as shown in Figure 9.
Energies2016,9,3028of18
filteringwindingofnewgridconnectedtransformeralsoshouldbe0.Thedesignedmethodfor
implementinginductivefilteringmethodisgiveninSection4.1.
3.2.ReactivePowerCompensationCharacteristics
Inthewindpowerintegratedsystem,theFTbranchesandSTATCOMcancompensateforthe
reactivepowerthatthewindfarmneeds.Thecurrentdistributioninthenewgridconnected
transformerisshowninFigure8.Correspondingly,thephasordiagramoftheloadwinding’s
voltagesandcurrentsofthenewgridconnectedtransformercanbeobtained,asshowninFigure9.
A
CB
0
V
An
V
Cn
V
Bn
a
b
c
Windfarm
I
a
I
b
I
c
Z
an
Z
bn
Z
cn
a
2
b
2
g0
I
fa
I
fb
I
fc
+
+
+
I
ca
I
cb
I
cc
STA TCOM
Figure8.Thecurrentdistributionofthenewgridconnectedtransformer.
TakingtheAphasewindinginFigure9asanexample,assumethattheloadwindingcurrentIa
lagsthephaseoftheloadwindingvoltageVabyδ.SincetheimpedanceoftheFTbranchesis
capacitiveforthefundamental,whenweconsidertheFTbranchesandSTATCOM,thephasecurrent
oftheFTbrancheswillleadtheloadwindingvoltageVaby90°.Inaddition,thecurrentsIcathatthe
STATCOMinjectedlagsthephaseoftheloadwindingvoltageUAby90°,aswell.Thus,wecanobtain
thattheangleoftheloadsideI’a(withtheinductivefilteringmethodandSTATCOM)lagstheload
windingvoltageUabyananglesmallerthanδ.Hence,itisshownthattheFTbranchesand
STATCOMhavethereactivepowercompensationabilityintheloadwinding,whichmeanstheFT
branchesandSTATCOMcanimprovethepowerfactorofthewindfarms.
V
c
V
a
V
b
I
c
I
a
I
b
I
fa
+I
ca
I'
a
Figure9.Phasordiagramofthevoltageandcurrentoftheloadwinding.
Figure 8. The current distribution of the new grid-connected transformer.
Energies2016,9,3028of18
filteringwindingofnewgridconnectedtransformeralsoshouldbe0.Thedesignedmethodfor
implementinginductivefilteringmethodisgiveninSection4.1.
3.2.ReactivePowerCompensationCharacteristics
Inthewindpowerintegratedsystem,theFTbranchesandSTATCOMcancompensateforthe
reactivepowerthatthewindfarmneeds.Thecurrentdistributioninthenewgridconnected
transformerisshowninFigure8.Correspondingly,thephasordiagramoftheloadwinding’s
voltagesandcurrentsofthenewgridconnectedtransformercanbeobtained,asshowninFigure9.
A
CB
0
V
An
V
Cn
V
Bn
a
b
c
Windfarm
I
a
I
b
I
c
Z
an
Z
bn
Z
cn
a
2
b
2
g0
I
fa
I
fb
I
fc
+
+
+
I
ca
I
cb
I
cc
STA TCOM
Figure8.Thecurrentdistributionofthenewgridconnectedtransformer.
TakingtheAphasewindinginFigure9asanexample,assumethattheloadwindingcurrentIa
lagsthephaseoftheloadwindingvoltageVabyδ.SincetheimpedanceoftheFTbranchesis
capacitiveforthefundamental,whenweconsidertheFTbranchesandSTATCOM,thephasecurrent
oftheFTbrancheswillleadtheloadwindingvoltageVaby90°.Inaddition,thecurrentsIcathatthe
STATCOMinjectedlagsthephaseoftheloadwindingvoltageUAby90°,aswell.Thus,wecanobtain
thattheangleoftheloadsideI’a(withtheinductivefilteringmethodandSTATCOM)lagstheload
windingvoltageUabyananglesmallerthanδ.Hence,itisshownthattheFTbranchesand
STATCOMhavethereactivepowercompensationabilityintheloadwinding,whichmeanstheFT
branchesandSTATCOMcanimprovethepowerfactorofthewindfarms.
V
c
V
a
V
b
I
c
I
a
I
b
I
fa
+I
ca
I'
a
Figure9.Phasordiagramofthevoltageandcurrentoftheloadwinding.
Figure 9. Phasor diagram of the voltage and current of the load winding.
Taking the A-phase winding in Figure 9as an example, assume that the load-winding current
I
a
lags the phase of the load-winding voltage V
a
by
δ
. Since the impedance of the FT branches is
capacitive for the fundamental, when we consider the FT branches and STATCOM, the phase current
of the FT branches will lead the load-winding voltage V
a
by 90
˝
. In addition, the currents I
ca
that
the STATCOM injected lags the phase of the load-winding voltage U
A
by 90
˝
, as well. Thus, we can
obtain that the angle of the load-side I’
a
(with the inductive filtering method and STATCOM) lags
the load-winding voltage U
a
by an angle smaller than
δ
. Hence, it is shown that the FT branches and
STATCOM have the reactive power compensation ability in the load-winding, which means the FT
branches and STATCOM can improve the power factor of the wind farms.
Energies 2016,9, 302 9 of 18
4. Design of Impedance Parameters and STATCOM Control System
4.1. Design of FT Branches and the New Grid-Connected Transformer
According to the analysis in Section 3.1, we can see that the equivalent impedance of FT branches
should be equal or approximately equal to 0; in other words, the FT branches should reach resonance
state at the considered harmonic orders, i.e., 4th, 5th, 7th and 11th. The new wind power integrated
system adopts a single LC filter, consists of a reactor and a capacitor, as the FT branch. In practice, the
capacity of the reactive power compensation for each FT branch should be determined at first, and
then the capacitance and reactance of FT branches can be designed, i.e.,
$
&
%
jnωnLn´1
jnωnCn0
CnQCpnqpn2´1q
pV2ω1qn2
Ln1
n2ω2
1n2
(13)
where,
ω
1 is the fundamental angle frequency; QC(n) is the capacity of the reactive power
compensation of the nth-order FT branch; and Vis the voltage of the filtering winding connected to
the FT branches.
Another condition for implementing the inductive filtering method is that the equivalent
impedance of the filtering winding should be approximately equal to 0, i.e.,Z
3n«
0, which can
be obtained by the transformer short-circuit impedances shown in Equation (10). Note that these
impedances shown in Equation (10) can be obtained by the short-circuit test of the manufactured
transformer. The design parameters of the new grid-connected transformer and the FT branches are
shown in Tables 1and 2respectively.
Table 1. Design parameters of the new grid-connected transformer.
Parameters Value
Rated capacity 60 MVA
Winding voltage V1110 kV
Winding voltage V235 kV
Winding voltage V310 kV
Short-circuit impedance Zn12 0.105 p.u.
Short-circuit impedance Zn13 0.065 p.u.
Short-circuit impedance Zn23 0.040 p.u.
No load loss 55 kW
Copper loss 275 kW
Table 2. Design parameters of the FT branches.
n-Order Capacity (MVar) Capacitance (µF) Reactance (mH)
4th branch 0.5 14.9000 42.4410
5th branch 1.0 30.5575 13.2629
7th branch 0.5 15.5907 13.2629
11th branch 0.5 15.7840 5.3052
4.2. Control Strategy of Cascade Multilevel STATCOM
As shown in Figure 2, it can be seen that the cascade multilevel STATCOM has three links, and
each link of them is independent. Therefore, the cascade multilevel STATCOM can be controlled
individually, based on [
29
], the individual phase instantaneous current control strategy is improved,
and then the control strategy of the cascade multilevel STATCOM is shown in Figure 10.
Energies 2016,9, 302 10 of 18
Energies2016,9,30210of18
individually,basedon[29],theindividualphaseinstantaneouscurrentcontrolstrategyisimproved,
andthenthecontrolstrategyofthecascademultilevelSTATCOMisshowninFigure10.
PLL
sin
cos cos cos
sin
sin
PI
PI
PI
Cascade
STATCOM
PWM
Control
QPR
Vab
Vbc
Vca
vra
vrb
vrc
Vab
Vbc
Vca
Reactiv e current
references
Vdcc
Vdcc
*
Vdcb
Vdcb
*
Vdca
Vdca
*
Acti ve current references
iaibic
Instantaneous current tracking
ab
bc
ca
iq
*
iq
*
iq
*
ic
*
ib
*
ia
*
QPR
QPR
Figure10.Controlstrategyofcascademultilevelstaticsynchronouscompensator(STATCOM).
Thephaselockedloop(PLL)detectsthephaseanglesofthefilteringwinding’sthreephase
voltage.Theactivecurrentreferencescanbegeneratedbyaproportionalintegral(PI)controllerin
ordertomaintainitsDCvoltageconstant.Thereactivecurrentreferences(iq*)comefromtheupper
controller,whosevalueisdeterminedbycompensatingmode,whichwillbeintroducedinnext
chapter.Addingtheactivecurrentreferencesandthereactivecurrentreference,theinstantaneous
currentreferencesareformed.Then,aquasiproportionalresonant(QPR)controllerispresentedto
trackthealternatingcurrentreferencesforeachlink,whichisablenotonlytokeephighgain,but
alsoreducethesteadystateerroratthefundamentalfrequency.ThetransferfunctionoftheQPR
controllerisexpressedas
2
0
22
2
)(
ss
sk
ksG
c
cr
pQPR (14)
wherekpandkraretheproportionalcoefficientandresonantgain,respectively;ωcistheequivalent
bandwidthoftheresonantcontroller,andω0isthefundamentalanglefrequency.TheQPRcontroller
isdesignedtohavethefollowingparameters:kp=0.5,kr=20,ωc=5rad/sandω0=2π ×50rad/s.
Figure11showsthebodeplotsoftheQPRcontroller.ItcanbeseenthattheQPRcontrollercankeep
thehighgainattheresonant/fundamentalfrequencyandverysmallatotherfrequencies,thusthe
zerosteadystateerrorcanbeachievedattheresonant/fundamentalfrequency.
ThesignalsobtainedfromQPRcontrolleractasthereferencevoltage,andtheywillbedelivered
tothePWMcontrolblockaftersubtractingthevoltagevalue(e.g.,Vab,Vbc,andVca).Finally,thecontrol
signalsofSTATCOMaregeneratedbythePWMcontrolblock,andtheycontrolthecascade
multilevelSTATCOMtoinjectorabsorbreactivepowerforthewindfarm.
Figure 10. Control strategy of cascade multilevel static synchronous compensator (STATCOM).
The phase-locked loop (PLL) detects the phase angles of the filtering-winding’s three-phase
voltage. The active current references can be generated by a proportional integral (PI) controller in
order to maintain its DC voltage constant. The reactive current references (i
q
*) come from the upper
controller, whose value is determined by compensating mode, which will be introduced in next chapter.
Adding the active current references and the reactive current reference, the instantaneous current
references are formed. Then, a quasi-proportional-resonant (QPR) controller is presented to track the
alternating current references for each link, which is able not only to keep high gain, but also reduce
the steady-state error at the fundamental frequency. The transfer function of the QPR controller is
expressed as
GQPRpsq kp`2krωcs
s2`2ωcs`ω2
0
(14)
where k
p
and k
r
are the proportional coefficient and resonant gain, respectively;
ωc
is the equivalent
bandwidth of the resonant controller, and
ω0
is the fundamental angle frequency. The QPR controller
is designed to have the following parameters: k
p
= 0.5, k
r
= 20,
ωc
= 5 rad/s and
ω0
= 2
πˆ
50 rad/s.
Figure 11 shows the bode plots of the QPR controller. It can be seen that the QPR controller can keep
the high gain at the resonant/fundamental frequency and very small at other frequencies, thus the
zero steady-state error can be achieved at the resonant/fundamental frequency.
The signals obtained from QPR controller act as the reference voltage, and they will be delivered
to the PWM control block after subtracting the voltage value (e.g., V
ab
,V
bc
, and V
ca
). Finally, the
control signals of STATCOM are generated by the PWM control block, and they control the cascade
multilevel STATCOM to inject or absorb reactive power for the wind farm.
Energies 2016,9, 302 11 of 18
Energies2016,9,30211of18
-10
0
10
20
30
Magnitude (dB)
10
1
10
2
10
3
10
4
-90
-45
0
45
90
Phase (deg)
Frequency (rad/sec)
Bode Diagram
Figure11.Bodediagramofthequasiproportionalresonant(QPR)controller.
Thewindfarmoperatorsexpectthepowerfactortobehigh,i.e.,near1,whenthewindfarm
operatesatthenormalcondition;inparticular,theyexpectwindturbinestoremainconnectedtothe
powersystemunderfaultconditions.Therefore,thecascademultilevelSTATCOMhastwo
compensationmodestomeettherequirementsofthewindfarm,andtheyarecalledreactivecontrol
modeandvoltagecontrolmode.ThecontrolblockoftwocompensationmodesisshowninFigure12.
Inthisfigure,Vg,Qg,arethevoltageandinstantaneousreactivepowerofthegridsideofnew
gridconnectedtransformer,respectively.Thereactivecurrentreferencesiq*canbeobtainedbythe
meanoftheswitchfunction.Notethatinthereactivecontrolmode,thePIcontrollerobtainsthereactive
powerreferences,notthereactivecurrentreferences.Thereactivecurrentreferencescanbeobtainedby
g
ref
qV
Q
i3
2
*(15)
Therefore,atthenormaloperatingcondition,thegridvoltageisstableandthecascade
multilevelSTATCOMwillprovidereactivepowertothewindfarmtoimprovethepowerfactorof
thewindfarm.Whenafaultordisturbanceoccursinpublicnetwork,thevoltagestabilityisaffected,
andtheSTATCOMinjectsanamountofreactivepowerforenhancementofvoltagestability.Hence,
thiscontrolstrategyreactsimmediatelytoasuddenvoltagevariationandiswellsuitablefor
improvingtheLVRTcapabilityofwindfarm.
PI
V
g
V
ref
PI
Q
g
0
Q
ref
Eq.13
i
q
*
1
0
Comparator
V
g
0.9
V
g
>0.9: 1 Normal operation
V
g
<0.9: 0 Fault condition
Reactive co ntrol mode
Voltage control mode
Figure12.Controlblockoftwocompensationmode.
5.CaseStudy
Inordertovalidatethetheoreticalanalysisandrevealtheoperatingcharacteristicsoftheproposed
windpowerintegratedsystem,thefollowingtestsarecarriedout:(1)thefilteringperformance;(2)the
reactivecompensationperformance;and(3)thefaultrecoveryperformance.Allthetestsareperformed
Figure 11. Bode diagram of the quasi-proportional-resonant (QPR) controller.
The wind farm operators expect the power factor to be high, i.e., near 1, when the wind farm
operates at the normal condition; in particular, they expect wind turbines to remain connected to
the power system under fault conditions. Therefore, the cascade multilevel STATCOM has two
compensation modes to meet the requirements of the wind farm, and they are called reactive control
mode and voltage control mode. The control block of two compensation modes is shown in Figure 12.
In this figure, V
g
,Q
g
, are the voltage and instantaneous reactive power of the grid-side of new
grid-connected transformer, respectively. The reactive current references i
q
* can be obtained by the
mean of the switch function. Note that in the reactive control mode, the PI controller obtains the
reactive power references, not the reactive current references. The reactive current references can be
obtained by
i˚
q2Qre f
3Vg(15)
Therefore, at the normal operating condition, the grid voltage is stable and the cascade multilevel
STATCOM will provide reactive power to the wind farm to improve the power factor of the wind
farm. When a fault or disturbance occurs in public network, the voltage stability is affected, and
the STATCOM injects an amount of reactive power for enhancement of voltage stability. Hence, this
control strategy reacts immediately to a sudden voltage variation and is well-suitable for improving
the LVRT capability of wind farm.
Energies2016,9,30211of18
-10
0
10
20
30
Magnitude (dB)
10
1
10
2
10
3
10
4
-90
-45
0
45
90
Phase (deg)
Frequency (rad/sec)
Bode Diagram
Figure11.Bodediagramofthequasiproportionalresonant(QPR)controller.
Thewindfarmoperatorsexpectthepowerfactortobehigh,i.e.,near1,whenthewindfarm
operatesatthenormalcondition;inparticular,theyexpectwindturbinestoremainconnectedtothe
powersystemunderfaultconditions.Therefore,thecascademultilevelSTATCOMhastwo
compensationmodestomeettherequirementsofthewindfarm,andtheyarecalledreactivecontrol
modeandvoltagecontrolmode.ThecontrolblockoftwocompensationmodesisshowninFigure12.
Inthisfigure,Vg,Qg,arethevoltageandinstantaneousreactivepowerofthegridsideofnew
gridconnectedtransformer,respectively.Thereactivecurrentreferencesiq*canbeobtainedbythe
meanoftheswitchfunction.Notethatinthereactivecontrolmode,thePIcontrollerobtainsthereactive
powerreferences,notthereactivecurrentreferences.Thereactivecurrentreferencescanbeobtainedby
g
ref
qV
Q
i3
2
*(15)
Therefore,atthenormaloperatingcondition,thegridvoltageisstableandthecascade
multilevelSTATCOMwillprovidereactivepowertothewindfarmtoimprovethepowerfactorof
thewindfarm.Whenafaultordisturbanceoccursinpublicnetwork,thevoltagestabilityisaffected,
andtheSTATCOMinjectsanamountofreactivepowerforenhancementofvoltagestability.Hence,
thiscontrolstrategyreactsimmediatelytoasuddenvoltagevariationandiswellsuitablefor
improvingtheLVRTcapabilityofwindfarm.
PI
V
g
V
ref
PI
Q
g
0
Q
ref
Eq.13
i
q
*
1
0
Comparator
V
g
0.9
V
g
>0.9: 1 Normal operation
V
g
<0.9: 0 Fault condition
Reactive control mode
Voltage control mode
Figure12.Controlblockoftwocompensationmode.
5.CaseStudy
Inordertovalidatethetheoreticalanalysisandrevealtheoperatingcharacteristicsoftheproposed
windpowerintegratedsystem,thefollowingtestsarecarriedout:(1)thefilteringperformance;(2)the
reactivecompensationperformance;and(3)thefaultrecoveryperformance.Allthetestsareperformed
Figure 12. Control block of two compensation mode.
Energies 2016,9, 302 12 of 18
5. Case Study
In order to validate the theoretical analysis and reveal the operating characteristics of the proposed
wind power integrated system, the following tests are carried out: (1) the filtering performance; (2)
the reactive compensation performance; and (3) the fault recovery performance. All the tests are
performed on the simulation model established by in the environment of the Power System Computer
Aided Design (PSCAD).
5.1. Test 1: Filtering Performance
In this paper, the measurement data for the real wind farm is obtained. Figures 13 and 14
show the current waveform of grid-winding of the grid-connected transformer, when the output
power of the wind farm is 4.5 MW and 15 MW, respectively. From these figures, we can see that the
current waveform of the grid-winding represents a clean sinusoidal waveform when implementing
the inductive filtering method. Moreover, Figure 15 gives more details about the main order harmonic
currents in the grid-winding of the grid-connected transformer. It is clear that, when applying the
inductive filtering method, the harmonic currents are reduced greatly, and the total harmonic distortion
(THD) is reduced from 23.5% to 6.2%, and from 6.36% to 2.2%, respectively. It is important that there are
low 4th-, 5th-, 7th, 11th-order harmonic currents in the grid winding of the grid-connected transformer.
Hence, the inductive filtering method can effectively suppress the harmonic currents generated from a
wind farm, and the power quality of the public network can be greatly improved.
Energies2016,9,30212of18
onthesimulationmodelestablishedbyintheenvironmentofthePowerSystemComputerAided
Design(PSCAD).
5.1.Test1:FilteringPerformance
Inthispaper,themeasurementdatafortherealwindfarmisobtained.Figures13and14show
thecurrentwaveformofgridwindingofthegridconnectedtransformer,whentheoutputpowerof
thewindfarmis4.5MWand15MW,respectively.Fromthesefigures,wecanseethatthecurrent
waveformofthegridwindingrepresentsacleansinusoidalwaveformwhenimplementingthe
inductivefilteringmethod.Moreover,Figure15givesmoredetailsaboutthemainorderharmonic
currentsinthegridwindingofthegridconnectedtransformer.Itisclearthat,whenapplyingthe
inductivefilteringmethod,theharmoniccurrentsarereducedgreatly,andthetotalharmonic
distortion(THD)isreducedfrom23.5%to6.2%,andfrom6.36%to2.2%,respectively.Itisimportant
thattherearelow4th,5th,7th,11thorderharmoniccurrentsinthegridwindingofthegridconnected
transformer.Hence,theinductivefilteringmethodcaneffectivelysuppresstheharmoniccurrents
generatedfromawindfarm,andthepowerqualityofthepublicnetworkcanbegreatlyimproved.
0.40 0.42 0.46
-60 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-30
0
30
60
Time (s)
Is (A)
Phase B Phase C
Phase A
(a)
0.40 0.42 0.46
-60 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-30
0
30
60
Time (s)
Is (A)
Phase B Phase C
Phase A
(b)
Figure13.Simulationresultaboutcurrentsinthegridwindingofthenewgridconnected
transformerwhenwindfarm’soutputpoweris4.5MW.(a)Nofiltering;(b)Withinductivefiltering.
0.40 0.42 0.46
-200 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-100
0
100
200
Time (s)
Is (A)
PhaseBPh aseC
PhaseA
(a)
0.40 0.42 0.46
-200 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-100
0
100
200
Time (s)
Is (A)
PhaseBPhaseCPhaseA
(b)
Figure 13.
Simulation result about currents in the grid-winding of the new grid-connected transformer
when wind farm’s output power is 4.5 MW. (a) No filtering; (b) With inductive filtering.
Energies 2016,9, 302 13 of 18
Energies2016,9,30212of18
onthesimulationmodelestablishedbyintheenvironmentofthePowerSystemComputerAided
Design(PSCAD).
5.1.Test1:FilteringPerformance
Inthispaper,themeasurementdatafortherealwindfarmisobtained.Figures13and14show
thecurrentwaveformofgridwindingofthegridconnectedtransformer,whentheoutputpowerof
thewindfarmis4.5MWand15MW,respectively.Fromthesefigures,wecanseethatthecurrent
waveformofthegridwindingrepresentsacleansinusoidalwaveformwhenimplementingthe
inductivefilteringmethod.Moreover,Figure15givesmoredetailsaboutthemainorderharmonic
currentsinthegridwindingofthegridconnectedtransformer.Itisclearthat,whenapplyingthe
inductivefilteringmethod,theharmoniccurrentsarereducedgreatly,andthetotalharmonic
distortion(THD)isreducedfrom23.5%to6.2%,andfrom6.36%to2.2%,respectively.Itisimportant
thattherearelow4th,5th,7th,11thorderharmoniccurrentsinthegridwindingofthegridconnected
transformer.Hence,theinductivefilteringmethodcaneffectivelysuppresstheharmoniccurrents
generatedfromawindfarm,andthepowerqualityofthepublicnetworkcanbegreatlyimproved.
0.40 0.42 0.46
-60 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-30
0
30
60
Time (s)
Is (A)
Phase B Phase C
Phase A
(a)
0.40 0.42 0.46
-60 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-30
0
30
60
Time (s)
Is (A)
Phase B Phase C
Phase A
(b)
Figure13.Simulationresultaboutcurrentsinthegridwindingofthenewgridconnected
transformerwhenwindfarm’soutputpoweris4.5MW.(a)Nofiltering;(b)Withinductivefiltering.
0.40 0.42 0.46
-200 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-100
0
100
200
Time (s)
Is (A)
PhaseBPh aseC
PhaseA
(a)
0.40 0.42 0.46
-200 0.44 0.48 0.50 0.52 0.54 0.56 0.58 0.60
-100
0
100
200
Time (s)
Is (A)
PhaseBPhaseCPhaseA
(b)
Figure 14.
Simulation result about currents in the grid winding of the new grid-connected transformer
when wind farm’s output power is 15 MW. (a) No filtering; (b) With inductive filtering.
Energies2016,9,30213of18
Figure14.Simulationresultaboutcurrentsinthegridwindingofthenewgridconnectedtransformer
whenwindfarm’soutputpoweris15MW.(a)Nofiltering;(b)Withinductivefiltering.
2457 17
Harmonic order
Mag. of current (A)
0
1
2
3
4
5
36
811 13 19 23 25
No filte ring ;THD=23. 5%
With inductive filtering; THD=6.2%
(a)
2457 17
Harmonic order
Mag. of current (A)
0
1
2
3
4
5
36
811 13 19 23 25
No filte ring; THD=6. 36%
With inductive fi ltering; THD=2.2%
(b)
Figure15.FFTresultsonthecurrentwaveforminthegridwinding.(a)Outputpowerofwindfarm
is4.5MW;(b)Outputpowerofwindfarmis15MW.
5.2.Test2:ReactivePowerCompensationPerformance
Measureddataforwindpowerinarealwindfarmisalsoobtained,asshowninFigure16.It
canbeseenfromFigure16thattheactivepowervariesinawiderange,whereasthereactivepower
fluctuatesaround−6Mvar.Inthistest,thewindpowerdataat0hisselectedtostudythereactive
compensationperformanceofthenewwindpowerintegratedsystem.Table3showstheactiveand
thereactivepoweratthepublicnetworkside.WhenusingtheFTbranchesandSTATCOM,theycan
compensateforthereactivepowerofthewindfarm.Hoverer,theywillconsumetheactivepower
fromwindfarm,buttoaverysmalldegree.Morespecifically,thepowerlossesoftheSTATCOMand
theFTbranchesare41.2kWand7.45kW,respectively.Table3showsthepowerlossofthenewgrid
connectedtransformerwithorwithouttheFTbranchesandtheSTATCOM.Figure17showsthe
voltageandcurrentatthegridsideofthenewgridconnectedtransformer.ItcanbeseenfromFigure
17andTable3thatthecombinedimplementationoftheinductivefilteringmethodandthe
STATCOMcaneffectivelycompensateforthereactivepowerofthewindfarm,hence,thepower
factoratthepublicnetworksideisimprovedeffectively.Besides,thecombinedimplementationof
theinductivefilteringmethodandtheSTATCOMcanalsoreducethepowerlossofthegrid
connectedtransformer,whichmeanstheefficiencyofthewindfarmcanbeimprovedeffectively.
Moreover,Figure18showstheoutputvoltageandcurrentoftheSTATCOM.Itisclearfromthis
figurethattheSTATCOMprovidesthereactivepowercompensationforthewindfarm.
Figure 15.
FFT results on the current waveform in the grid winding. (
a
) Output power of wind farm is
4.5 MW; (b) Output power of wind farm is 15 MW.
5.2. Test 2: Reactive Power Compensation Performance
Measured data for wind power in a real wind farm is also obtained, as shown in Figure 16. It can
be seen from Figure 16 that the active power varies in a wide range, whereas the reactive power
Energies 2016,9, 302 14 of 18
fluctuates around
´
6 Mvar. In this test, the wind power data at 0 h is selected to study the reactive
compensation performance of the new wind power integrated system. Table 3shows the active and
the reactive power at the public network side. When using the FT branches and STATCOM, they can
compensate for the reactive power of the wind farm. Hoverer, they will consume the active power
from wind farm, but to a very small degree. More specifically, the power losses of the STATCOM
and the FT branches are 41.2 kW and 7.45 kW, respectively. Table 3shows the power loss of the new
grid-connected transformer with or without the FT branches and the STATCOM. Figure 17 shows
the voltage and current at the grid side of the new grid-connected transformer. It can be seen from
Figure 17 and Table 3that the combined implementation of the inductive filtering method and the
STATCOM can effectively compensate for the reactive power of the wind farm, hence, the power
factor at the public network side is improved effectively. Besides, the combined implementation of the
inductive filtering method and the STATCOM can also reduce the power loss of the grid-connected
transformer, which means the efficiency of the wind farm can be improved effectively. Moreover,
Figure 18 shows the output voltage and current of the STATCOM. It is clear from this figure that the
STATCOM provides the reactive power compensation for the wind farm.
Energies2016,9,30214of18
012345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0
10
20
30
40
Time (Hour)
Active Power
(MW)
(a)
012345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24
-8
-6
-4
-2
0
Time (Hour)
Reactive Power
(Mvar)
(b)
Figure16.Windpowerdatainonedaywithathreesecondinterval.(a)Activepower;(b)Reactivepower.
0.15 0.16 0.18
-100 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-50
0
50
100
Time (s)
Voltage of grid
side (kV)
Voltage
-0.4
-0.2
0
0.2
0.4
Current
Current of grid
side (kA)
(a)
0.15 0.16 0.18
-100 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-50
0
50
100
Time (s)
Voltage of grid
side (kV)
Voltage
-0.4
-0.2
0
0.2
0.4
Current
Current of grid
side (kA)
(b)
Figure17.Voltageandcurrentinthegridsideofthenewgridconnectedtransformer.(a)Without
compensation;(b)Withcompensation.
Figure 16.
Wind power data in one day with a three-second interval. (a) Active power; (b) Reactive power.
Table 3.
Active power and reactive power at the public network side and power loss of new
grid-connected transformer.
Parameter No Compensation With Compensation
Active power (MW) 16.0282 16.0531
Reactive power (Mvar) ´5.3744 0.8786
Power factor 0.9481 0.9985
Power loss of transformer (Mvar) 0.1045 0.0845
Energies 2016,9, 302 15 of 18
Energies2016,9,30214of18
012345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0
10
20
30
40
Time (Hour)
Active Power
(MW)
(a)
012345678910 11 12 13 14 15 16 17 18 19 20 21 22 23 24
-8
-6
-4
-2
0
Time (Hour)
Reactive Power
(Mvar)
(b)
Figure16.Windpowerdatainonedaywithathreesecondinterval.(a)Activepower;(b)Reactivepower.
0.15 0.16 0.18
-100 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-50
0
50
100
Time (s)
Voltage of grid
side (kV)
Voltage
-0.4
-0.2
0
0.2
0.4
Current
Current of grid
side (kA)
(a)
0.15 0.16 0.18
-100 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-50
0
50
100
Time (s)
Voltage of grid
side (kV)
Voltage
-0.4
-0.2
0
0.2
0.4
Current
Current of grid
side (kA)
(b)
Figure17.Voltageandcurrentinthegridsideofthenewgridconnectedtransformer.(a)Without
compensation;(b)Withcompensation.
Figure 17.
Voltage and current in the grid side of the new grid-connected transformer. (
a
) Without
compensation; (b) With compensation.
Energies2016,9,30215of18
0.15 0.16 0.18
-10 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-5
0
5
10
Time (s)
Voltage of the
STATCOM (kV)
V
statcom
-500
-200
0
200
500
I
statcom
Current of the
STATCOM (A)
Figure18.AphasevoltageandcurrentoftheSTATCOM.
Table3.Activepowerandreactivepoweratthepublicnetworksideandpowerlossofnew
gridconnectedtransformer.
ParameterNoCompensation WithCompensation
Activepower(MW)16.028216.0531
Reactivepower(Mvar)−5.37440.8786
Powerfactor0.94810.9985
Powerlossoftransformer(Mvar)0.10450.0845
5.3.Test3:FaultRecoveryPerformance
Toinvestigatetheperformanceofthedynamicvoltageimprovementofthenewwindpower
integratedsystem,athreephaseshortcircuitfaultisappliedtoline1ofthepublicnetwork(shown
inFigure2)at0.6s,andclearedat0.65s.ItisworthnotingthattheprotectivesystemofthePMSG,
suchasacrowbarcircuit,isoutofservice.Figure19showsthemagnitudesofthevoltageatthepublic
network.FromFigure19,itcanbeseenthat,withouttheimplementationofSTATCOM,thevoltage
atthenetworksidebecomeslowerthan110kV(1p.u.),whichisdisadvantageousforthestable
operationofwindfarm.WhenusingSTATCOM,thevoltageisabletoreturn110kVafterclearing
thefault,andthewindfarmcansuccessfullyridethroughthegridfault.Thereactivepowerthat
STATCOMoutputsisshowninFigure20.ItcanbefoundfromFigure20thatwhenthegriddisturbed
orfault,theSTATCOMwillrespondimmediatelyandinjectanamountofreactivepowertosupport
thevoltageofthewindfarm.Figure21showstheoutputcurrentandcommandcurrentofSTATCOM,
especiallythecommandcurrentmentionedinFigure10.ItcanbealsofoundfromFigure21thatthe
STATCOMhasagoodtrackingperformanceontheoutputcurrent.Inthisway,theLVRTcapability
ofwindfarmcanbegreatlyimproved.
0.4 0.5 0.7
00.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
40
60
80
Time (s)
20
120
Voltage of grid side (kV)
100
110kV
107 kV
With inductive filters and STATCOMNo compensation
Figure19.Magnitudesofthevoltageatthepublicnetwork.
Figure 18. A-phase voltage and current of the STATCOM.
5.3. Test 3: Fault Recovery Performance
To investigate the performance of the dynamic voltage improvement of the new wind power
integrated system, a three-phase short circuit fault is applied to line 1 of the public network (shown
in Figure 2) at 0.6 s, and cleared at 0.65 s. It is worth noting that the protective system of the PMSG,
such as a crowbar circuit, is out of service. Figure 19 shows the magnitudes of the voltage at the public
network. From Figure 19, it can be seen that, without the implementation of STATCOM, the voltage at
the network side becomes lower than 110 kV (1 p.u.), which is disadvantageous for the stable operation
of wind farm. When using STATCOM, the voltage is able to return 110 kV after clearing the fault,
and the wind farm can successfully ride through the grid fault. The reactive power that STATCOM
outputs is shown in Figure 20. It can be found from Figure 20 that when the grid disturbed or fault, the
STATCOM will respond immediately and inject an amount of reactive power to support the voltage of
the wind farm. Figure 21 shows the output current and command current of STATCOM, especially the
command current mentioned in Figure 10. It can be also found from Figure 21 that the STATCOM has
a good tracking performance on the output current. In this way, the LVRT capability of wind farm can
be greatly improved.
Energies 2016,9, 302 16 of 18
Energies2016,9,30215of18
0.15 0.16 0.18
-10 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25
-5
0
5
10
Time (s)
Voltage of the
STATCOM (kV)
V
statcom
-500
-200
0
200
500
I
statcom
Current of the
STATCOM (A)
Figure18.AphasevoltageandcurrentoftheSTATCOM.
Table3.Activepowerandreactivepoweratthepublicnetworksideandpowerlossofnew
gridconnectedtransformer.
ParameterNoCompensation WithCompensation
Activepower(MW)16.028216.0531
Reactivepower(Mvar)−5.37440.8786
Powerfactor0.94810.9985
Powerlossoftransformer(Mvar)0.10450.0845
5.3.Test3:FaultRecoveryPerformance
Toinvestigatetheperformanceofthedynamicvoltageimprovementofthenewwindpower
integratedsystem,athreephaseshortcircuitfaultisappliedtoline1ofthepublicnetwork(shown
inFigure2)at0.6s,andclearedat0.65s.ItisworthnotingthattheprotectivesystemofthePMSG,
suchasacrowbarcircuit,isoutofservice.Figure19showsthemagnitudesofthevoltageatthepublic
network.FromFigure19,itcanbeseenthat,withouttheimplementationofSTATCOM,thevoltage
atthenetworksidebecomeslowerthan110kV(1p.u.),whichisdisadvantageousforthestable
operationofwindfarm.WhenusingSTATCOM,thevoltageisabletoreturn110kVafterclearing
thefault,andthewindfarmcansuccessfullyridethroughthegridfault.Thereactivepowerthat
STATCOMoutputsisshowninFigure20.ItcanbefoundfromFigure20thatwhenthegriddisturbed
orfault,theSTATCOMwillrespondimmediatelyandinjectanamountofreactivepowertosupport
thevoltageofthewindfarm.Figure21showstheoutputcurrentandcommandcurrentofSTATCOM,
especiallythecommandcurrentmentionedinFigure10.ItcanbealsofoundfromFigure21thatthe
STATCOMhasagoodtrackingperformanceontheoutputcurrent.Inthisway,theLVRTcapability
ofwindfarmcanbegreatlyimproved.
0.4 0.5 0.7
00.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
40
60
80
Time (s)
20
120
Voltage of grid side (kV)
100
110kV
107 kV
With inductive filters and STATCOMNo compensation
Figure19.Magnitudesofthevoltageatthepublicnetwork.
Figure 19. Magnitudes of the voltage at the public network.
Energies2016,9,30216of18
0.4 0.5 0.7
-10 0.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
-5
0
5
10
Time (s)
Reactive power
(Mvar)
Figure20.ReactivepowerinjectedfromSTATCOM.
0.4 0.5 0.7
-1.2 0.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
-0.3
0
0.6
1.2
Time (s)
Current (p.u)
-0.6
-0.9
0.3
0.9
i
a
i
a
*
Figure21.OutputcurrentandcommandcurrentoftheSTATCOM.
6.Conclusions
Thispaperproposesanewwindpowerintegratedsystembasedonaninductivefiltering
method.Thenewsystemcontainsanewgridconnectedtransformerwiththespecialwiringand
impedancedesigns,thefullytunedbranchesandacascademultilevelSTATCOM.Theequivalent
circuitandthemathematicalmodelareestablishedforthenewwindpowerintegratedsystem.
Further,theoperatingmechanismontheinductivefilteringandthereactivepowercompensationfor
thewindfarmareinvestigated,andtherealizationconditionsareobtainedforimplementingthe
inductivefilteringmethod.Then,theimprovedinstantaneouscurrentcontrolstrategyisproposedin
thispaper.Moreover,thesystemsimulationmodelisestablishedaccordingtoarealworldwind
farmandthemeasureddata.Thesimulationresultsindicatethatthenewwindpowerintegrated
systemcancomprehensivelyimprovethepowerqualityofthewindfarm,suchasharmonic
suppressionandreactivepowercompensation.Furthermore,theresultsindicatethatthenewsystem
hasagoodfaultrecoveryperformanceandrepresentsanenhancedlowvoltageridethrough
capabilityforthestableandsecureoperationofwindfarm.
Acknowledgments:ThisworkwassupportedbythenationalNaturalScienceFoundationofChina(NSFC)
underGrant51377001,61233008,61304092and51520105011,bytheSpecialProjectofInternationalScientificand
TechnologicalCooperationofChinaunderGrant2015DFR70850,andbytheScienceandTechnologyProjectof
HunanPowerCompanyofChinaunderGrant5216A014002and5216A213509X.
AuthorContributions:Alltheauthorsmadecontributionstotheconceptanddesignofthearticle;YanjianPengis
themainauthorofthiswork.YongLiprovidedgoodadviceandtechnicalguidanceforthemanuscript;YongLi,
ZhishengXu,MingWen,LongfuLuo,YijiaCaoandZbigniewLeonowiczreviewedandpolishedthemanuscript.
ConflictsofInterest:Theauthorsdeclarenoconflictofinterest.
Figure 20. Reactive power injected from STATCOM.
Energies2016,9,30216of18
0.4 0.5 0.7
-10 0.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
-5
0
5
10
Time (s)
Reactive power
(Mvar)
Figure20.ReactivepowerinjectedfromSTATCOM.
0.4 0.5 0.7
-1.2 0.6 0.8 0.9 1.0 1.1 1.2 1.3 1.4
-0.3
0
0.6
1.2
Time (s)
Current (p.u)
-0.6
-0.9
0.3
0.9
i
a
i
a
*
Figure21.OutputcurrentandcommandcurrentoftheSTATCOM.
6.Conclusions
Thispaperproposesanewwindpowerintegratedsystembasedonaninductivefiltering
method.Thenewsystemcontainsanewgridconnectedtransformerwiththespecialwiringand
impedancedesigns,thefullytunedbranchesandacascademultilevelSTATCOM.Theequivalent
circuitandthemathematicalmodelareestablishedforthenewwindpowerintegratedsystem.
Further,theoperatingmechanismontheinductivefilteringandthereactivepowercompensationfor
thewindfarmareinvestigated,andtherealizationconditionsareobtainedforimplementingthe
inductivefilteringmethod.Then,theimprovedinstantaneouscurrentcontrolstrategyisproposedin
thispaper.Moreover,thesystemsimulationmodelisestablishedaccordingtoarealworldwind
farmandthemeasureddata.Thesimulationresultsindicatethatthenewwindpowerintegrated
systemcancomprehensivelyimprovethepowerqualityofthewindfarm,suchasharmonic
suppressionandreactivepowercompensation.Furthermore,theresultsindicatethatthenewsystem
hasagoodfaultrecoveryperformanceandrepresentsanenhancedlowvoltageridethrough
capabilityforthestableandsecureoperationofwindfarm.
Acknowledgments:ThisworkwassupportedbythenationalNaturalScienceFoundationofChina(NSFC)
underGrant51377001,61233008,61304092and51520105011,bytheSpecialProjectofInternationalScientificand
TechnologicalCooperationofChinaunderGrant2015DFR70850,andbytheScienceandTechnologyProjectof
HunanPowerCompanyofChinaunderGrant5216A014002and5216A213509X.
AuthorContributions:Alltheauthorsmadecontributionstotheconceptanddesignofthearticle;YanjianPengis
themainauthorofthiswork.YongLiprovidedgoodadviceandtechnicalguidanceforthemanuscript;YongLi,
ZhishengXu,MingWen,LongfuLuo,YijiaCaoandZbigniewLeonowiczreviewedandpolishedthemanuscript.
ConflictsofInterest:Theauthorsdeclarenoconflictofinterest.
Figure 21. Output current and command current of the STATCOM.
6. Conclusions
This paper proposes a new wind power integrated system based on an inductive filtering method.
The new system contains a new grid-connected transformer with the special wiring and impedance
designs, the fully-tuned branches and a cascade multilevel STATCOM. The equivalent circuit and
the mathematical model are established for the new wind power integrated system. Further, the
operating mechanism on the inductive filtering and the reactive power compensation for the wind
farm are investigated, and the realization conditions are obtained for implementing the inductive
filtering method. Then, the improved instantaneous current control strategy is proposed in this paper.
Moreover, the system simulation model is established according to a real-world wind farm and the
measured data. The simulation results indicate that the new wind power integrated system can
Energies 2016,9, 302 17 of 18
comprehensively improve the power quality of the wind farm, such as harmonic suppression and
reactive power compensation. Furthermore, the results indicate that the new system has a good fault
recovery performance and represents an enhanced low-voltage ride through capability for the stable
and secure operation of wind farm.
Acknowledgments:
This work was supported by the national Natural Science Foundation of China (NSFC)
under Grant 51377001, 61233008, 61304092 and 51520105011, by the Special Project of International Scientific and
Technological Cooperation of China under Grant 2015DFR70850, and by the Science and Technology Project of
Hunan Power Company of China under Grant 5216A014002 and 5216A213509X.
Author Contributions:
All the authors made contributions to the concept and design of the article; Yanjian Peng
is the main author of this work. Yong Li provided good advice and technical guidance for the manuscript; Yong Li,
Zhisheng Xu, Ming Wen, Longfu Luo, Yijia Cao and Zbigniew Leonowicz reviewed and polished the manuscript.
Conflicts of Interest: The authors declare no conflict of interest.
References
1.
Keane, A.; Cuffe, P.; Diskin, E.; Brooks, D.; Harrington, P.; Hearne, H.; Rylander, M.; Fallon, T. Evaluation of
advanced operation and control of distributed wind farms to support efficiency and reliability. IEEE Trans.
Sustain. Energy 2012,4, 735–742. [CrossRef]
2.
Yao, J.; Li, Q.; Chen, Z.; Liu, A. Coordinated control of a DFIG-Based wind-power generation system with
SGSC under distorted grid voltage conditions. Energies 2013,6, 2541–2561. [CrossRef]
3.
Konopinski, R.; Vijayan, P.; Ajjarapu, V. Extended reactive capability of DFIG wind parks for enhanced
system performance. IEEE Trans. Power Syst. 2009,3, 1346–1355. [CrossRef]
4.
Okedu, K.; Muyeen, S.M.; Takahashi, R.; Tamura, J. Wind farms fault ride through using DFIG with new
protection scheme. IEEE Trans. Sustain. Energy 2012,2, 242–254. [CrossRef]
5.
Lu, S.; Wang, L.; Ke, S.; Chang, C.; Yang, Z. Evaluation of Measured Power Quality Results of a Wind Farm
Connected to Taiwan Power System. IEEE Trans. Ind. Appl. 2016,1, 42–49. [CrossRef]
6.
Jayaweera, D.; Islam, S. Steady-state security in distribution networks with large wind farms. J. Mod. Power
Syst. Clean Energy 2014,2, 134–142. [CrossRef]
7.
Mohod, S.W.; Aware, M.V. A STATCOM-Control Scheme for Grid Connected Wind Energy System for Power
Quality Improvement. IEEE Syst. J. 2010,3, 346–352. [CrossRef]
8.
Liang, S.; Hu, Q.; Lee, W. A Survey of Harmonic Emissions of a Commercially Operated Wind Farm.
IEEE Trans. Ind. Appl. 2012,3, 1115–1123. [CrossRef]
9.
Tentzerakis, S.T.; Papathanassiou, S.A. An investigation of the harmonic emissions of wind turbines.
IEEE Trans. Energy Convers. 2007,1, 150–158. [CrossRef]
10.
Teng, J.H.; Leou, R.C.; Chang, C.Y.; Chan, S.Y. Harmonic current predictors for wind turbines. Energies
2013
,
6, 1314–1328. [CrossRef]
11.
ENTSO-E Network Code for Requirements for Grid Connection Applicable to All Generators. Available
online: http://networkcodes.entsoe.eu/wp-content/uploads/2013/08/130308_Final_Version_NC_RfG1.pdf
(accessed on 12 December 2015).
12.
Hasan, K.N.B.M.; Rauma, K.; Luna, A.; Cadela, J.I.; Rodríguez, P. Harmonic Compensation Analysis in
Offshore Wind Power Plants Using Hybrid Filters. IEEE Trans. Ind. Appl. 2014,3, 2050–2060. [CrossRef]
13.
Gan, L.; Li, G.; Zhou, M. Coordinated Planning of Large-Scale Wind Farm Integration System and
Transmission Network. CSEE J. Power Energy Syst. 2016,1, 19–29. [CrossRef]
14.
Montao, A.F.O.; Carrillo, C.; Cidrás, J.; Dorado, E.D. A STATCOM with Supercapacitors for Low-Voltage
Ride-Through in Fixed-Speed Wind Turbines. Energies 2014,7, 5922–5952.
15.
Roncero-Sànchez, P.; Acha, E. Design of a control scheme for distribution static synchronous compensators
with power-quality improvement capability. Energies 2014,7, 2476–2497. [CrossRef]
16.
Bai, J.; Gu, W.; Yuan, X.; Li, Q.; Xue, F.; Wang, X. Power quality prediction, early warning, and control for
points of common coupling with wind farms. Energies 2015,8, 9365–9382. [CrossRef]
17.
Zheng, Z.; Yang, G.; Geng, H. Coordinated control of a doubly-fed induction generator-based wind farm and
a static synchronous compensator for low voltage ride-through grid code compliance during asymmetrical
grid faults. Energies 2013,6, 4660–4681. [CrossRef]
Energies 2016,9, 302 18 of 18
18.
Daratha, N.; Das, B.; Sharma, J. Coordination between OLTC and SVC for voltage regulation in unbalanced
distribution system distributed generation. IEEE Trans. Power Syst. 2014,1, 289–299. [CrossRef]
19.
Luo, L.; Li, Y.; Xu, J.; Li, J.; Hu, B.; Liu, F. A new converter transformer and a corresponding inductive
filtering method for HVDC transmission system. IEEE Trans. Power Deliv. 2008,3, 1426–1431. [CrossRef]
20.
Li, Y.; Luo, L.; Rehtanz, C.; Yang, D.; Rüberg, S.; Liu, F. Harmonic transfer characteristics of a new HVDC
system based on an inductive filtering method. IEEE Trans. Power Electron. 2012,5, 2273–2282.
21.
Li, Y.; Luo, L.; Rehtanz, C.; Nakamura, K.; Xu, J.; Liu, F. Study on characteristic parameters of a new converter
transformer for HVDC system. IEEE Trans. Power Deliv. 2009,4, 2125–2131.
22.
Xu, Z.; Peng, Y.; Li, Y.; Wen, M.; Luo, L.; Cai, Y.; Cao, Y. Improvement of power quality and dynamic voltage
of wind farms using an inductive filtering method. In Proceedings of the 2015 IEEE 15th International
Conference on Environment and Electrical Engineering (EEEIC), Rome, Italy, 10–13 June 2015.
23.
Wang, L.; Nhon, D. Stability enhancement of a power system with a PMSG-Based and a DFIG-Based offshore
wind farm using a SVC with an Adaotive-Network-Based fuzzy inference system. IEEE Trans. Ind. Electron.
2013,7, 2799–2807. [CrossRef]
24.
Lázaro, E.G.; Bueso, M.C.; Kessler, M.; Martínez, S.M.; Zhang, J.; Hodge, B.M. Probability density function
characterization for aggregated large-scale wind power based on Weibull mixtures. Energies
2016
,9, 91.
[CrossRef]
25.
Papathanassiou, S.A.; Papadopoulous, M.P. Harmonic analysis in a power system with wind generation.
IEEE Trans. Power Deliv. 2006,4, 2006–2016. [CrossRef]
26.
Cirrincione, M.; Pucci, M.; Vitale, G. Growing neural gas-based MPPT of variable pitch wind generators
with induction machines. IEEE Trans. Ind. Appl. 2012,3, 1006–1016. [CrossRef]
27.
Sainz, L.; Mesas, J.J.; Teodorescu, R.; Rodriguez, P. Deterministic and stochastic study of wind farm harmonic
currents. IEEE Trans. Energy Convers. 2010,4, 1071–1080. [CrossRef]
28.
Heathcote, M.J. The J & P Transformer Book; Reed Educational and Professional Publishing: Oxford, UK, 1998.
29.
Shi, Y.; Liu, B.; Shi, Y.; Duan, S. Individual phase current control based on optimal zero-sequence current
separation for a star-connected cascade STATCOM under unbalanced conditions. IEEE Trans. Ind. Electron.
2016,3, 2099–2110. [CrossRef]
©
2016 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC-BY) license (http://creativecommons.org/licenses/by/4.0/).
... During grid faults, the transient stator flux sets up a surge current in the rotor circuit which can destroy the Power Electronic Converter (PEC). Voltage dips at the Point of Common Coupling (PCC) also reduces the converter capability to transfer power to the grid, which leads to increased DC-link capacitor voltage [4], [5]. ...
... Reactive power consumption further contributes to voltage degradation. If the fault persists, the wind power generating plant is eventually disconnected from the grid [5], [6]. Previously, wind farms were allowed to disconnect from grids during power system faults. ...
... By means of the ingenious design of the transformer winding, the transformer itself or some parts can work as the filtering device to improve the power quality. Such techniques are collectively known as the transformer integrated filtering method, which includes two key technologies: the inductive filtering method and the filtering reactor integrated method, [16]- [22]. The inductive filtering method is initially applied in the large-power industrial rectifier system [17]. ...
... However, when the harmonic frequency matches with the system parameter, the serial/parallel resonance is excited and the harmonic currents will be seriously amplified. Now that the principles of harmonic suppression and reactive power compensation for the inductive filtering method have been adequately analyzed in [17] and [22], this paper just focuses on the ability of resonance damping of inductive filtering method in the PV power plant. where Z 1h and Z 3h are the equivalent impedance of the grid winding and the low-voltage winding; N 1 , N 2 and N 3 are the number of turns of the three windings; Z Sh and Z fh are the system impedance and the equivalent impedance of the passive filter. ...
Article
This paper presents a new solution of power quality management for the photovoltaic (PV) power plant with the transformer integrated filtering method. The PV power plant contains two-stage filtering station, which consists of a box-type transformer with integrated filter and a 110 kV grid-connected transformer based on inductive filtering method. The filtering reactor can be integrated into the box-type transformer as a decoupled winding, so that the modular design of the box-type transformer and the fully tuned filter is realized. Inductive filtering method applied in the grid-connected transformer not only improves the power quality at the point of common coupling, but dampen the harmonic resonance between the passive filter and grid. The hierarchical structure of the PV power plant is introduced firstly. Then, the equivalent circuit model and the mathematical model of the primary and secondary filtering stations are established, respectively. Moreover, the influence of the weak coupling of integrated reactor on the filtering performance is analyzed. At last, the site tests of the PV power plant with transformer integrated filtering method are made, which show that the PV grid-connected system comprised of the two-stage filtering station has the characteristics of low harmonic emission, high power factor and stable operation.
... Thus, the DC-link capacitor might be damaged. Therefore, in order to improve the FRT capability of the PMSG, various solutions have been proposed in the last few years [11][12][13][14][15][16][17][18][19][20][21][22][23][24][25][26][27][28][29]. Most of the presented solutions use external devices to improve the FRT capability of the PMSG. ...
... Most of the presented solutions use external devices to improve the FRT capability of the PMSG. The external devices include braking choppers (BCs) [12][13][14], energy storage devices [15][16][17], flexible AC transmission system (FACTS) devices [18][19][20], series dynamic breaking resistors (SDBRs) [21][22][23], auxiliary parallel grid-side converters [24], and electronic power transformers [25]. The drawbacks of these external devices include high cost and complexity. ...
Article
Full-text available
Currently, the electric power production by wind energy conversion systems (WECSs) has increased significantly. Consequently, wind turbine (WT) generators are requested to fulfill the grid code (GC) requirements stated by network operators. In case of grid faults/voltage dips, a mismatch between the generated active power from the wind generator and the active power delivered to the grid is produced. The conventional approach is using a braking chopper (BC) in the DC-link to dissipate this active power. This paper proposes a fault-ride through (FRT) strategy for variable-speed WECSs based on permanent magnet synchronous generators (PMSGs). The proposed strategy exploits the rotor inertia of the WECS (inertia of the WT and PMSG) to store the surplus active power during the grid faults/voltage dips. Thus, no additional hardware components are requested. Furthermore, a direct model predictive control (DMPC) scheme for the PMSG is proposed in order to enhance the dynamic behavior of the WECS. The behavior of the proposed FRT strategy is verified and compared with the conventional BC approach for all the operation conditions by simulation results. Finally, the simulation results confirm the feasibility of the proposed FRT strategy
... The majority of the presented solutions utilize exterior devices to enhance the LVRT capability of the PMSG. The exterior devices comprise BC [12][13][14], flexible AC transmission system (FACTS) [15][16][17] and energy storage devices [18][19][20]. In [21], a novel control construction is demonstrated corresponding to regulating the DC voltage (Vdc) by the machine-side converter (MSC). ...
Article
Full-text available
With the speedy increase of wind energy in electric networks, many important issues could emerge, where the most important matter is to maintain the connection of wind generators during fault conditions. With different faults in the electrical network, the voltage at the point of common coupling (PCC) decreases causing unwanted transients in the stator currents. This results in substantially increased fluctuations in the DC-link voltage (Vdc). To avoid this negative impact, it is a must to maintain the capability of wind generators to continue linked to the network during faults, which is depicted as low voltage ride through (LVRT) capability. This paper investigates the LVRT enhancement by two techniques, the first is based on Braking Chopper (BC) and the second method is based on electrical double-layer capacitors (EDLC), or Supercapacitor Energy Storage System (SCESS), under abnormal conditions. The full model of the permanent magnet synchronous generator (PMSG) system and FRT technique are performed in MATLAB/Simulink platform. As a consequence of the findings, both the BC and SCESS are capable to provide satisfactory performance with superior FRT capability for the SCESS compared to the BC.
... During grid faults, the transient stator flux sets up a surge current in the rotor circuit which can destroy the Power Electronic Converter (PEC). Voltage dips at the Point of Common Coupling (PCC) also reduce the converter capability to transfer power to the grid, which leads to increased DC link capacitor voltage [6,7]. e PEC is usually protected by a crowbar, which short-circuits the rotor once triggered by a fault. ...
Article
Full-text available
This paper investigates the utilization of a STATCOM to enhance the LVRT capability of wind power plants (WPPs) during grid faults. The STATCOM under investigation is tuned using the Water Cycle Algorithm (WCA), Particle Swarm Optimization (PSO), and a hybrid algorithm of both WCA and PSO. Simulations are conducted in MATLAB programming software, using the SimScape power system toolbox, where two test systems are investigated: a 9 MW WPP and the IEEE 39 bus test system. Performance analysis is done by investigating the ability of the WPPs to ride through grid voltage sags, with the incorporation of the STATCOM, independently tuned using WCA, PSO, and further with the hybrid WCA-PSO algorithm. To confirm the effectiveness of the proposed algorithm, simulation results for the three scenarios are compared. Results show that the LVRT capability of the German power system was met for L-G faults, for the 9 MW test system, whereas during LLL-G faults, the WPP only remained online for WCA and WCA-PSO tuned STATCOM. For the IEEE 39 bus system, the WPPs were able to ride through the LLL-G fault. In all scenarios, the WCA-PSO tuned STATCOM resulted in the least voltage, active, and reactive power overshoots.
... The majority of the presented solutions utilize exterior devices to enhance the LVRT capability of the PMSG. The exterior devices comprise BC [12][13][14], flexible AC transmission system (FACTS) [15][16][17] and energy storage devices [18][19][20]. In [21], a novel control construction is demonstrated corresponding to regulating the DC voltage (Vdc) by the machine-side converter (MSC). ...
Article
With the speedy increase of wind energy in electric networks, many important issues could emerge, where the most important matter is to maintain the connection of wind generators during fault conditions. With different faults in the electrical network, the voltage at the point of common coupling (PCC) decreases causing unwanted transients in the stator currents. This results in substantially increased fluctuations in the DC-link voltage (Vdc). To avoid this negative impact, it is a must to maintain the capability of wind generators to continue linked to the network during faults, which is depicted as low voltage ride through (LVRT) capability. This paper investigates the LVRT enhancement by two techniques, the first is based on Braking Chopper (BC) and the second method is based on electrical double-layer capacitors (EDLC), or Supercapacitor Energy Storage System (SCESS), under abnormal conditions. The full model of the permanent magnet synchronous generator (PMSG) system and FRT technique are performed in MATLAB/Simulink platform. As a consequence of the findings, both the BC and SCESS are capable to provide satisfactory performance with superior FRT capability for the SCESS compared to the BC.
... One of these stages is the optimization of the reactive power (VAR) compensation locations and sizes, and the other stage is decreasing the total cost. The Fully Tuned (FT) branches and STATCOM have been used to control the reactive power during low voltage or fault events in the grid [15]. Various methods of overcoming the LVRT of the DFIG-driven wind turbine considering grid codes are proposed in [16]. ...
Conference Paper
Full-text available
Wind energy is rapidly growing due to technological development and the rise in global energy demand. Therefore, large-scale wind farms are being directly connected to power grids. However, integration of such wind farms into power systems presents various challenges to be solved. One of these challenges is reactive power capability which has the particular influence on wind farms operation. Another challenge is Low Voltage Ride-Through (LVRT) capability which is one of the most serious challenges in designing wind turbines and their manufacturing technology. This paper explains modern wind power systems and discusses the requirements of wind farm connection. We also investigate various operation and control methods for wind turbines needed to meet these requirements. To analyze the impact of wind energy integration to Egyptian power grid, we utilize DIgSILENT PowerFactory programming to illustrate the present scenario and challenges in reactive power and LVRT capability of Gabel El-Zeit wind farm. The results show that by adding the Static Synchronous Compensator (STATCOM) to the system, it is achieving higher reactive power injection needed for supporting system performance.
Article
Full-text available
The Weibull probability distribution has been widely applied to characterize wind speeds for wind energy resources. Wind power generation modeling is different, however, due in particular to power curve limitations, wind turbine control methods, and transmission system operation requirements. These differences are even greater for aggregated wind power generation in power systems with high wind penetration. Consequently, models based on one-Weibull component can provide poor characterizations for aggregated wind power generation. With this aim, the present paper focuses on discussing Weibull mixtures to characterize the probability density function (PDF) for aggregated wind power generation. PDFs of wind power data are firstly classified attending to hourly and seasonal patterns. The selection of the number of components in the mixture is analyzed through two well-known different criteria: the Akaike information criterion (AIC) and the Bayesian information criterion (BIC). Finally, the optimal number of Weibull components for maximum likelihood is explored for the defined patterns, including the estimated weight, scale, and shape parameters. Results show that multi-Weibull models are more suitable to characterize aggregated wind power data due to the impact of distributed generation, variety of wind speed values and wind power curtailment.
Article
Full-text available
Aging network assets, forced and unforced outages, and the way the networks are operated in a deregulated market are of significant concerns to integrate large wind farms in a distribution network. In many cases, the constrained network capacity is a potential barrier to the large-scale integration of wind power. This paper probabilistically assesses the steady-state security in a distribution network in the presence of large wind farms. The approach incorporates active distribution network operating conditions, including intermittent power outputs, random outages, demand fluctuations, and dynamic interactions and exchanges, and then assesses the steady state security using Monte Carlo simulation. A case study is performed by integrating large wind farms into a distribution network. The results suggest that intermittent outputs of large wind farms in a distribution network can impact the steady-state security considerably. However, the level of impact of wind farms does not necessarily correlate with the installed capacity of them.
Article
Full-text available
Wind farms can affect the power quality (PQ) of the power supply grid, with subsequent impacts on the safe and stable operation of other electrical equipment. A novel PQ prediction, early warning, and control approach for the common coupling points between wind farms and the network is proposed in this paper. We then quantify PQ problems and provide rational support measures. To obtain predicted PQ data, we first establish a trend analysis model. The model incorporates a distance-based cluster analysis, probability distribution analysis based on polynomial fitting, pattern matching based on similarity, and Monte Carlo random sampling. A data mining algorithm then uses the PQ early warning flow to analyze limit-exceeding and abnormal data, quantify their severity, and output early warning prompts. Finally, PQ decision support is applied to inform both the power suppliers and users of anomalous changes in PQ, and advise on corresponding countermeasures to reduce relevant losses. Case studies show that the proposed approach is effective and feasible, and it has now been applied to an actual PQ monitoring platform.
Article
Full-text available
This paper aims to explore a viable solution for a doubly-fed induction generator (DFIG)-based wind farm to meet the reactive support requirement of the low voltage ride-through (LVRT) grid code with safe grid-connected operation during asymmetrical grid faults. First, the control scheme for the DFIG-based wind energy conversion system (WECS) is designed. Then, the controllability issue is analyzed by means of an optimal method, and the derived controllable regions indicate that the DFIG-based WECS can only remain controllable under mild asymmetrical fault situations. Afterwards, the static synchronous compensator (STATCOM) is introduced as extra equipment to ensure that the DFIG-based wind farm remains controllable under severe asymmetrical fault situations. For this purpose, a voltage compensation control scheme and a corresponding capacity matching method for the STATCOM are proposed. The simulation results verify that, with the proposed coordinated control between the DFIG-based wind farm and the STATCOM, the required positive-sequence reactive current can be supplied to support the power grid. The oscillations on the electromagnetic torque and direct current (DC)-link voltage of the DFIG-based WECS can also be eliminated. Therefore, the control scheme can be helpful to improve the reliability of both the wind farm and the power system during grid faults.
Article
Full-text available
Fixed-speed wind generator (FSWG) technology has an important presence in countries where wind energy started to be developed more than a decade ago. This type of technology cannot be directly adapted to the grid codes, for example those requirements related to the immunity level under voltage dips. That behavior is typically referred as low-voltage ride through (LVRT), and it usually implies certain reactive and active power injection requirements, both during a voltage dip and during the voltage recovery. In this context, a review is presented of the LVRT exigencies present in some of the countries with the most advanced grid codes (Denmark, Germany, Spain and the United Kingdom). In this paper, the capabilities of STATCOM-based devices for fulfilling the LVRT requirements in FSWGs are analyzed. For this purpose, two technologies are considered: a STATCOM with a supercapacitor, which improves its energy storage features; and a STATCOM with a supercapacitor and a DC-DC converter, to achieve higher discharge levels.
Article
Large-scale centralized exploitation of intermittent wind energy resources has become popular in many countries. However, as a result of the frequent occurrence of largescale wind curtailment, expansion of corresponding transmission projects has fallen behind the speed at which installed wind capacity can be developed. In this paper, a coordinated planning approach for a large-scale wind farm integration system and its related regional transmission network is proposed. A bilevel programming model is formulated with the objective of minimizing cost. To reach the global optimum of the bi-level model, this work proposes that the upper-level wind farm integration system planning problem needs to be solved jointly with the lower-level regional transmission planning problem. The bi-level model is expressed in terms of a linearized mathematical problem with equilibrium constraints (MPEC) by Karush-Kuhn- Tucker conditions. It is then solved using mixed integer linear programming solvers. Numerical simulations are conducted to show the validity of the proposed coordinated planning method.
Book
Maintaining appropriate power systems and equipment expertise is necessary for a utility to support the reliability, availability, and quality of service goals demanded by energy consumers now and into the future. However, transformer talent is at a premium today, and all aspects of the power industry are suffering a diminishing of the supply of knowledgeable and experienced engineers. Now in print for over 80 years since initial publication in 1925 by Johnson & Phillips Ltd, the J & P Transformer Book continues to withstand the test of time as a key body of reference material for students, teachers, and all whose careers are involved in the engineering processes associated with power delivery, and particularly with transformer design, manufacture, testing, procurement, application, operation, maintenance, condition assessment and life extension. Current experience and knowledge have been brought into this thirteenth edition with discussions on moisture equilibrium in the insulation system, vegetable based natural ester insulating fluids, industry concerns with corrosive sulphur in oil, geomagnetic induced current (GIC) impacts, transportation issues, new emphasis on measurement of load related noise, and enhanced treatment of dielectric testing (including Frequency Response Analysis), Dissolved Gas analysis (DGA) techniques and tools, vacuum LTCs, shunt and series reactors, and HVDC converter transformers. These changes in the thirteenth edition together with updates of IEC reference Standards documentation and inclusion for the first time of IEEE reference Standards, provide recognition that the transformer industry and market is truly global in scale. -- From the foreword by Donald J. Fallon Martin Heathcote is a consultant specializing in power transformers, primarily working for utilities. In this context he has established working relationships with transformer manufacturers on several continents. His background with Ferranti and the UK's Central Electricity Generating Board (CEGB) included transformer design and the management and maintenance of transformer-based systems. *The definitive reference for all involved in designing, installing, monitoring and maintaining high-voltage systems using power transformers (electricity generation and distribution sector; large-scale industrial applications) *The classic reference work on power transformers and their applications: first published in 1925, now brought fully up to date in this thirteenth edition *A truly practical engineering approach to design, monitoring and maintenance of power transformers - in electricity generation, substations, and industrial applications.
Article
Unlike the traditional reactive power compensation and ac passive filtering method for the wind farm, this paper presents a new approach of a static synchronous compensator (STATCOM) and related fully-tuned (FT) branches based on an inductive filtering method for a wind farm equipped with double fed induction generators (DFIGs). First, the main circuit topology of a new wind power integrated system is presented. Then, the mathematical model is established to reveal the reactive compensation and harmonic suppressing performance of the new grid-connected transformer. The control strategy of STATCOM is introduced briefly in this paper. Simulation studies are carried out in the Digsilent/Powerfactory to illustrate the performance of the new grid connected wind power system. The results indicate that the new approach can not only enhance the low-voltage ride-through capability of wind turbines, but also significantly prevent harmonic components flowing into the primary (grid) winding of the new grid connected transformer. Besides, since the new method can compensate reactive power near the grid, the wind farm has a better dynamic stability.
Article
This paper presents the power-quality measurement results of a commercial wind farm (WF) connected to Taiwan Power System. This 46-MW Jang-Bin wind farm with twenty-three 2-MW doubly-fed induction generators (DFIGs) is connected to Jang-Bin extra high-voltage (EHV) substation of Taiwan Power Company (TPC) through six feeders and a step-up main transformer. The measured data were recorded from October 2 to November 6, 2013 for total 35 days. The recorded results include three-phase voltages, currents, active power, reactive power, apparent power, power factor, frequency, current harmonics, voltage flickers, and voltage variations. According to the measured results, it can be clearly observed that the power quality of the studied Jang-Bin wind farm during the measurement period can meet the grid code of TPC.
Article
This paper proposes an individual phase current control method based on optimal zero sequence current separation for star-connected cascade STATCOMs under unbalanced grid voltage. The Individual phase current control (IPCC) is adopted to get better adaptation to unbalanced conditions. Each cluster of the cascade STATCOM has its own phase current control loop and dc voltage feedback loop, and it can generate the necessary negative sequence current automatically to rebalance power. However the zero sequence current which is unnecessary and harmful in star configuration is introduced in the process. An optimal zero sequence current separation (OZSCS) is presented to remove the zero sequence current, by reconstructing the reactive current command. This improved IPCC enables star-connected STATCOMs adapted to unbalanced conditions without the need for any power balancing algorithms. Also the operation range of the proposed control method is analyzed. Simulation researches are performed to verify the operation range analysis, and experimental operation is tested on a 25-level ±10Mvar/10kV STATCOM product installed at a wind farm.