ArticlePDF Available

Analysis and Validation of Wavelet Transform Based DC Fault Detection in HVDC System

Authors:

Abstract and Figures

Fault detection plays an important role in both conventional AC and upcoming DC power systems. This paper aims to study the application of discrete wavelet transform (WT) for detecting the DC fault in the high voltage DC (HVDC) system. The methods of choosing the mother wavelet suited for DC fault is presented, based on degree of correlation to the fault pattern and the time delay. The wavelet analysis is performed on a multi-terminal HVDC system, built in PSCAD/EMTDC software. Its performance is judged for critical parameter like the fault location, resistance and distance. The analysis is further extended to validation using results from experiment, which is obtained from a lab-scale DC hardware setup. Load change, one of the transient disturbances in power system, is carried out to understand the effectiveness of the wavelet transform to differentiate it from the DC fault. The noise in the experimental result gives rise to non-zero wavelet coefficient during the steady-state. This can be improved by removing the unwanted noise using right filter while still retaining the fault-induced transient. The wavelet transform is compared with short-time Fourier transform to highlight the issue with window size and noise.
Content may be subject to copyright.
Analysis and Validation of Wavelet Transform Based
DC Fault Detection in HVDC System
Yew Ming Yeapa, Nagesh Geddadaa, Abhisek Ukila
aSchool of Electrical and Electronic Engineering, Nanyang Technological University,
SINGAPORE
Abstract
Fault detection plays an important role in both conventional AC and upcoming
DC power systems. This paper aims to study the application of discrete wavelet
transform (WT) for detecting the DC fault in the high voltage DC (HVDC)
system. The methods of choosing the mother wavelet suited for DC fault is
presented, based on degree of correlation to the fault pattern and the time delay.
The wavelet analysis is performed on a multi-terminal HVDC system, built in
PSCAD/EMTDC software. Its performance is judged for critical parameter
like the fault location, resistance and distance. The analysis is further extended
to validation using results from experiment, which is obtained from a lab-scale
DC hardware setup. Load change, one of the transient disturbances in power
system, is carried out to understand the effectiveness of the wavelet transform to
differentiate it from the DC fault. The noise in the experimental result gives rise
to non-zero wavelet coefficient during the steady-state. This can be improved
by removing the unwanted noise using right filter while still retaining the fault-
induced transient. The wavelet transform is compared with short-time Fourier
transform to highlight the issue with window size and noise.
Keywords: DC fault, wavelet transform, multi-terminal HVDC, modular
multi-level converter, PSCAD/EMTDC, DC system experiment,
time-frequency analysis, fault detection
1. Introduction
High voltage direct current system (HVDC) is one of the important technolo-
gies that have taken the conventional power system in a new direction. While a
lot of research efforts are put into the design of controller and control strategy of
the HVDC system, it is equally important to address the protection issue in the
system so that the damage caused by the fault is brought down to minimum.
IThe work was supported by the Start-Up Grant (M4081547.040), Nanyang Technological
University, Singapore.
Email addresses: yeap0022@e.ntu.edu.sg (Yew Ming Yeap), ngeddada@ntu.edu.sg
(Nagesh Geddada), aukil@ntu.edu.sg (Abhisek Ukil)
The traditional high voltage AC circuit breaker (CB) takes advantage of current
zero crossing which enables it to be tripped in a safe manner. Such phenomenon,
however, is not seen in the DC current. The absence of current zero means that
the mechanism of the breaker in the DC system should be completely different.
Due to lack of such technology, most of the present HVDC systems are restricted
to point-to-point connection, where the AC CB is adequate for protection. The
interest was renewed when ABB [1] and Alstom [2] proposed the hybrid DC CB.
It is arguably one of the key enabling technologies that will potentially pave the
way for the deployment of HVDC system with increasing connections, towards
a multi-terminal DC (MTDC) grid.
Development in power electronics converter technology has been critical for
the advancement of the HVDC system. In comparison with the current source
converter (CSC), the voltage source converter (VSC) is relatively more vul-
nerable to the fault on the DC side due to low DC-side inductance. Rapidly
increasing DC current can damage the devices if the fault is not treated im-
mediately. ABB’s hybrid DC CB [3] is capable of isolating the fault within 5
ms, this poses a challenge to the design of protection algorithm to meet such a
stringent requirement. In addition, as the HVDC system is moving towards the
scale of multi-terminal, locating the faulted line has become another important
aspect of the protection system.
In recent times, DC fault detection methods have gained a significant re-
search attention in the HVDC system. Traveling wave is well established me-
thid in conventional AC power system for its effectiveness in locating the fault
point. Its application on the HVDC system had been studied extensively [4].
This technique, however, requires high sampling rate for data collection in order
to accurately capture the wave-front arrival time. Fault detection based on the
DC current measurement was proposed in the works [5, 6], whereby the rate
of change of DC current (di/dt) forms the basis of fault criterion. While it is
simple and computationally efficient, it has difficulty determining the faulted
section independently as the system becomes highly meshed. DC fault can be
also detected by pattern recognition, in which the measured voltage is compared
with already known signal and the degree of similarity is measured by Pearson
correlation coefficient [7]. However, such method might lack generality. Zheng
et al. [8] reported that DC fault transient in CSC-HVDC system resulted in
generation of certain harmonics, which could be leveraged to form a fault basis.
Due to different operating conditions between CSC and VSC, its application on
the latter remains to be investigated.
The wavelet transform (WT) can be regarded as one of suitable techniques
for processing the non-stationary fault signals [9, 10]. This signal processing
technique is capable of interpreting the signal in time and frequency domain.
WT has also been applied to detect disturbance in conventional AC power sys-
tem [11–16]. One of the benefits of using the WT is that it is able to discrim-
inatingly identify the DC fault against non-concerned disturbances (AC fault
and load change) [17]. Using the WT, the faulted line can be determined in
a meshed network without the need of communication channel, hence substan-
tially reducing the detection time [18]. Abu-Elanien [19] in their work showed
2
that this technique is able to withstand the influence of fault location and fault
resistance to certain extent.
This paper presents a detailed analysis of the wavelet-based method for
detecting and locating fault in DC system, with software and hardware valida-
tions. Protection strategy is not of major focus. Rather, this paper attempts
to thoroughly evaluate the performance of the WT using real fault signals. The
influences of fault location, resistance and distance in the modular multilevel
converter-based (MMC) HVDC system, modeled in PSCAD/EMTDC, are stud-
ied. The inter-terminal communication is opted out, as the wavelet detection
scheme only requires the DC current signal which is locally available in each ter-
minal. The influences of fault resistance and distance are also validated, using
the experimental results obtained from the point-to-point hardware DC system
operating at lab-scale voltage level. This paper also presents how capable is the
wavelet transform when it comes to differentiating DC fault from load change,
which is carried out experimentally. The improvement of the smoothened exper-
imental result using properly designed filter will be discussed. Lastly, the per-
formance comparison between the wavelet transform and the short-time Fourier
transform (STFT) will be presented.
The remainder of the paper is structured in the following manner. In Section
2, the background of DC fault is presented, followed by brief introduction of the
wavelet transform and selection of mother wavelet in Section 3. The simulation
and experimental results are covered in Section 4 and 5, respectively. Finally,
the conclusions are given in Section 5.
2. DC fault in HVDC System
This section briefly explains the DC fault analysis in the MMC-based HVDC
system. The DC fault can be divided into following types: pole capacitor unbal-
ance, pole-to-ground (PG) and pole-to-pole (PP) fault. DC cable is relatively
more vulnerable to the PG fault caused by insulation breakdown than PP fault
[10]. Due to direct exposure to air, the DC overhead line is prone to the oc-
currence of these two faults. PP fault has the potential to result in extremely
destructive damage to the HVDC system. Therefore, it is always considered as
the most representative DC fault in literatures [20], as well as in this paper.
Modeling of MMC and two-level VSC are fundamentally same, in which the
converter station can be represented as DC current source in the DC side. The
combined submodular capacitance Ceis described in (1), under the balanced
condition, and the derivation can be found in [21, 22].
Ce=6C
n.(1)
The DC side equivalent circuit of single MMC is represented in Fig. 1, at the
instant of PP fault occurrence. Icv is the total current injected to the DC side.
The Ldc and Rdc are the π-model equivalent inductance and resistance of the
positive and negative poles. The fault resistance is denoted by Rf. Immediately
3
Figure 1: Equivalent circuit of MMC DC side during DC fault. (a) Stage 1: DC
capacitor discharge stage, (b) Diode freewheeling stage
as the fault current exceeds the threshold, the IGBTs in the submodule will be
blocked. Then, the current flow switches to the freewheeling diodes, which is
shown in Fig. 1(b). By this time, it is important to clear the fault fast enough
before the current reaches beyond the I2tcapacity of diodes.
The fault analysis can be divided into three stages: 1) DC capacitor dis-
charge stage, 2) diode freewheeling stage, 3) AC infeed stage. The discharge of
capacitor (Icap) dominates the fault current in the first few time-instant of fault.
When the DC voltage drops to zero, the AC side will continue supplying current
to the fault point [23, 24]. The fault analysis here only focuses on stage 1 and
2, as these periods are critical for wavelet transform to make fault decision and
dispatch IGBT block signal, preferably within 2 ms.
The circuit in Fig. 1(a) can be represented by (2).
d2Idc
dt2+Re
Le
dIdc
dt+1
LeCe
Idc = 0 (2)
where Re= 2(Rdc/2) + Rfand Le= 2(Ldc /2).
The under-damped response is met on the condition R2
e<(Le/Ce)1/2. As-
suming that the PP fault happens at t0with the initial conditions of Vdc(t0) = V0
and Idc(t0) = I0, the solution of the second-order RLC differential equation is
given as,
Idc(t) = eδt "I0cos(ωt) +
V0
LeδI0
ωsin(ωt)#,(3)
Vdc(t) = eδt "V0cos(ωt) + δV0I0
Ce
ωsin(ωt)#.(4)
where δ=Re/2Leand ω= (1/LeCe(Re/2Le)2)1/2.
The DC voltage (Vdc) reaches zero when the DC capacitor (Ce) gets dis-
charged. Now, the fault current (I0
dc) is freewheeling within the three-phase
diodes as the corresponding IGBTs are already blocked, depicted in Fig. 1(b).
The line inductor (Ldc) disallows sudden change of current, therefore the initial
4
current for this stage is Idc(t1) = I0
dc(t1) = I0
0. The circuit is now reduced to a
RL circuit, so the expression of the fault current is given as:
Ldc
dI0
dc
dt+RdcI0
dc = 0.(5)
The first order differential equation is solved:
I0
dc(t) = I0
0eRdc
Ldc t.(6)
The I0
dc is equally distributed in three-phase diodes:
ID1(t) = ID2(t) = ID3(t) = I0
dc(t)/3.(7)
3. Wavelet Transform
3.1. Theory
Wavelet transform (WT) is used for fault detection instead of Short Time
Fourier Transform (STFT). While both signal processing techniques are able to
analyze non-stationary signal in time and frequency domain, the window size
of the STFT is fixed. A longer window yields good frequency resolution at
the expense of time resolution, and vice versa. A convenient solution to this
dilemma is the WT, as it automatically changes the window size in response
to the dynamics of the signal. It is able to capture the high frequency abrupt
change, which is specially needed for detecting the fault.
The WT breaks up a signal into the shifted and the scaled versions of the
original (or mother) wavelet, allowing for simultaneous time and frequency anal-
ysis. The continuous wavelet transform (CWT) is defined as the sum over all
time of the signal multiplied by the scaled and shifted versions of the wavelet
function.
CW T (a, b) = Z+
−∞
x(t)ψ
a,b(t)dt. (8)
ψ
a,b(t) = |a|1/2ψ(tb
a).(9)
ψ(t) is the mother wavelet, the asterisk in (8) denotes a complex conjugate, and
a, b R, a 6= 0 (Ris the real continuous number system) are the scaling and
the shifting parameters, respectively. The discrete wavelet transform (DWT)
in (10) is given by choosing a=a
0m/2, b=nam/2
0b0,t=kT in (8) and (9),
where T= 1.0, and k, m, n Z, (Zis the set of positive integers).
DW T (m, n) = am/2
0(Xx[k]ψ[knam/2
0b0
am
0
]).(10)
We apply the multiresolution signal decomposition (MSD) [25, 26] technique
to decompose a given signal into detailed and smoothed versions. Let x[n] be a
5
discrete-time signal, then the MSD technique decomposes the signal in the form
of wavelet coefficient at scale 1 into C1[n], the smoothed (time-domain view)
and D1[n], the detailed (frequency-domain view) coefficients.
The decomposition process can be iterated, with successive approximations
being decomposed in turn, so that the original signal is broken down into many
lower resolution components. This is called the wavelet decomposition tree [25,
26], shown in 2. MSD technique can be realized with the cascaded quadrature
mirror filter (QMF) banks [27, 28].
So, for example, using 4-scale decomposition, the original signal scan be
represented as:
x[n] = C4[n] + D4[n] + D3[n] + D2[n] + D1[n].(11)
x[n] LPF
HPF
LPF LPF
HPF
HPF
C1[n] C2[n] Cj[n]
Dj[n]
D2[n]
D1[n]
2
2
2
2 2
2
QMF-1 QMF-2 QMF-j
Input signal
Figure 2: Multiresolution signal decomposition.
3.2. Wavelet Selection
The wavelet coefficient is the cross-correlation of the signal and the mother
wavelet; the higher the wavelet coefficient, the closer the signal matches with
the chosen mother wavelet. Thus, a suitable wavelet should be selected such
that it presents closest match to the pattern of the fault signal. Ma et al.
[29] presented a method to facilitate the wavelet selection by using the Pearson
product-moment correlation coefficient, as represented in (12).
r=Pn
i=1(Xi¯
X)(Yi¯
Y)
qPn
i=1(Xi¯
X)2(Yi¯
Y)2
(12)
where Xiand Yiare the data sets of the fault signal and the wavelet respectively,
their corresponding averages being ¯
Xand ¯
Y.
In this case, Xiis the fault signal as depicted in Fig. 3, while Yicorresponds
to the chosen Daubechies mother wavelet.
6
0 100 200 300 400 500
4
2
0
2
4
6
8
Fault signal
0 50 100 150 200 250 300 350 400
1.5
1
0.5
0
0.5
1
1.5
2
0 100 200 300 400 500 600 700
1.5
1
0.5
0
0.5
1
1.5
2
0 200 400 600 800 1000
1
0.5
0
0.5
1
1.5
0 200 400 600 800 1000 1200
1.5
1
0.5
0
0.5
1
1.5
0 500 1000 1500
1.5
1
0.5
0
0.5
1
1.5
db2 db3 db4
db5 db6 db7
Figure 3: The cross correlation between the fault signal and Daubechies wavelet
of varying orders.
db2 db3 db4 db5 db6 db7 db8 db9
Daubechies wavelet order
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.55
Pearson correlation coefficient
Figure 4: Correlation coefficient between fault signal and Daubechies wavelet
of order 2-9.
The correlation coefficients between the fault signal and the Daubechies
mother wavelet of varying order (db2db9) are computed and depicted in Fig.
4. It is found that db3 provides the best match among these candidates for the
given fault pattern.
3.3. Mother wavelet and time delay
Besides having adequate sensitivity to the transient caused by the DC fault,
it is equally important to choose the right mother wavelet that yields high-speed
fault detection. Fig. 5 shows the performance of Haar, Daubechies and Coiflet
mother wavelets for providing the maximum wavelet coefficient and correspond-
ing time delay.
7
Figure 5: Time delay introduced by different mother wavelets.
sfis the time the DC fault-induced transient begins to appear. It is noticed
that compact wavelets work well to localize high frequency components in the
transient with minimum time delay. In this case, Haar and db2-3 are the ideal
mother wavelets because they produce the maximum wavelet coefficients with
no delay. For the Daubechies wavelet family, db5 begins to show delay by one
sample. Coiflet wavelet is inappropriate for DC fault detection as far as speed
is concerned. The analysis here agrees with the finding in Santoso’s work [30],
which reported that db4 and db6 are suitable for fast transient in conventional
AC system.
4. Performance evaluation of wavelet transform - simulation result
Fig. 6 shows the MMC HVDC model consisting of four terminals (MMCi,
i=1, 2, 3, 4) developed in PSCAD/EMTDC. Four strong AC systems (ACi ) are
connected with ring and monopole DC network. The DC lines (Lij,i, j = 1, 2,
8
Figure 6: 4-terminal MMC HVDC model.
Table 1: System data
Parameters Values
Rated power 600 MVA
AC frequency 50 Hz
AC system short circuit ratio 10
Number of submodules per arm 100
Module capacitor 1000 µF
Arm inductor 50 mH
Switching frequency 180 Hz
Length L12, L13, L34, L24 100 km
Length L23 200 km
3, 4), consisting of positive and negative poles, are represented as single line in
the figure. The MMC adopts the detailed equivalent modeling (DEM) [31], with
MMC1 working as fixed DC voltage control and the rest as fixed active power
control. Its corresponding functional control structure will not be elaborated
here, the detail can be found in [21, 32]. The full system data is given in Table
1.
The DC currents (Idcij,i, j = 1, 2, 3, 4) are measured at each terminal
(MMCi). The IGBTs will not be blocked in the simulation as the focus is to
identify the signature associated with fault in the DC current signal. The signals
are exported to MATLAB and post-processed with discrete wavelet transform
algorithm to generate the wavelet coefficients.
The fault location (df ) is the distance from the fault to the monitoring termi-
nal. The fault simulated here is the PP fault, with the fault resistance denoted
as Rf. The sampling rate (fs) is selected based on the available frequency range
offered by digital fault recorder [33]. The mother wavelets to be adopted is db3,
since it has been shown in Section 3 that it presents the closest similarity with
9
fault pattern. The application of wavelet transform on the fault identification
in the multi-terminal system is evaluated by considering the three cases below:
To study the influence of DC fault location: PP fault on Lij (i, j =
1,2,3,4), Rf= 0.01Ω, df = 50km,fs= 15360Hz, using db3.
To study the influence of DC fault resistance: PP fault on L12, 0.01 <
Rf<500Ω, df= 50km,fs= 15360Hz, using db3.
To study the influence of DC fault distance: PP fault on L12, Rf= 0.01Ω,
15 < df<85km,fs= 15360Hz, using db3.
230 235 240 245 250 255 260
Sample number
(a)
-0.5
0
0.5
Wavelet coefficient
230 235 240 245 250 255 260
Sample number
(b)
-0.5
0
0.5
Wavelet coefficient
230 235 240 245 250 255 260
Sample number
(c)
-0.5
0
0.5
Wavelet coefficient
230 235 240 245 250 255 260
Sample number
(d)
-0.5
0
0.5
Wavelet coefficient
230 235 240 245 250 255 260
Sample number
(e)
-0.5
0
0.5
Wavelet coefficient
Idc12
Idc21
Idc13
Idc31
Idc34
Idc43
Idc24
Idc42
Idc23
Idc32
Figure 7: Detailed wavelet coefficient for each DC line current in different PP
fault location. a) L12, b) L13, c) L34, d) L24, e) L23.
4.1. Influence of DC fault location
Fig. 7 shows the wavelet coefficient obtained from the PP fault simulated
on the DC lines in the multi-terminal HVDC system. The PP fault is initiated
by shorting the positive and the negative DC lines through a fault resistance.
Therefore, only the wavelet coefficient for positive pole DC current is presented
here.
The wavelet coefficient remains low during the steady-state, approximating
to zero. The occurrence of fault on a DC line is detected when the DC current of
10
the faulted line generates a high wavelet coefficient abruptly. To illustrate, PP
fault on L13 (see Fig. 7(b)) generates large overcurrent in fault current between
MMC1 and MMC3, resulting in high wavelet coefficients for Idc13 and Idc31.
Similar pattern is observed in other cases. With the high wavelet coefficient
obtained at 243th sample, the fault is detected with a time delay of 1.09 ms.
Additionally, the wavelet transform allows the healthy terminals to recognize
that the fault is outside their protection zone, since the wavelet coefficients of
their currents remain consistently low.
The discriminative nature of wavelet transform has been validated. It is a
reliable method for each terminal to independently identify the fault by just
monitoring the DC current.
10-2 10-1 10 010110210 3
Fault resistance ()
0
0.1
0.2
0.3
0.4
0.5
0.6
Maximum wavelet coefficient
Idc12
Idc21
Idc13
Idc31
Idc34
Idc43
Idc24
Idc42
Idc23
Idc32
Figure 8: Effect of PP fault resistance on detailed wavelet coefficient for each
DC line current.
4.2. Influence of DC fault resistance
This subsection studies the robustness of the WT to detect the high resis-
tance fault in a multi-terminal HVDC system. Fig. 8 shows the trend of the
wavelet coefficients of DC currents as the fault resistance on L12 is increased
from 0.01 to 500 Ω.
The wavelet coefficient appears to be constantly high for the PP fault re-
sistance ranging from 0.01 to 5 Ω. Beyond that, however, the value begins
to show downward trend. This can be explained by the fact that fault induced
transient has been dampened by large fault resistor. As a consequence, the
wavelet coefficient decreases with increasing fault resistance. Nevertheless, the
wavelet coefficient of fault current remains vastly above that of healthy DC
current by large margin.
4.3. Influence of DC fault distance
The fault-induced transient is the function of fault location. If a DC fault
happens in close proximity to a terminal, the DC current of that terminal will
experience bigger frequency change and higher magnitude. Fig. 9 shows the
11
Idc12
df=85 km
Idc21
df=15 km
Figure 9: Line current (a) Idc12 , (b) Idc21 and their corresponding detailed
wavelet coefficient (c), (d) under the influence of fault distance. df =15km and
df =85km are represented by black line and red dashed line, respectively.
wavelet coefficients of Idc12 and Idc21 as the location of PP fault (df ) is adjusted
from 15 km to 85 km away from MMC1 along L12.
Fig. 9(a)&(b) illustrates the relationship between the change of DC current
and fault location. The current magnitude decreases and the transient becomes
dampened as the fault point increases. This phenomenon is reflected in their
wavelet coefficients. For example, the fault at df =85km yields the wavelet coeffi-
cient about -0.2342 for Idc12 and -1.389 for Idc21. Despite diminished sensitivity,
the fault can be successfully detected for all distances evaluated.
5. Performance evaluation of wavelet transform - experimental result
Laboratory DC system experiment setup is developed to study DC fault
with variation of fault parameters. The schematic block diagram of the setup
is shown in Fig. 10 and various parameters, ratings are given in Table 2.
Experimental studies are performed at input voltage of 85 V (line rms).
Three phase, 30 kVA, (0-450) V, variable transformer was used to set the desired
input voltage of 85 V. Converters (VSC1,VSC2 ) at the DC side are rated at
30 kVA, 415 V.
The voltage and current quantities at power level are converted to signal
level using hall effect voltage (±500 V to ±15 V) and current (±10 A to ±4
V) transducers. These signals are fed to the dSPACE 1103 controller through
12
VSC1 VSC2
DC MCBDC MCB
DC MCB
DC MCB
Pole1
Pole2
2dc
v
ic2
ib2
ia2
2abc
i
1dc
v
idc1
Voltage andCurr ent
TransducerSensor
Board
R
la
R
lb
R
lc
Lf2
2abc
v
idc2
VariablePower
Resistor
R
f2
SwitchingPulses V SC1 SwitchingPulses V SC2
BKR2
Voltage andCurr ent
TransducerSensor
Board
Filter
Inductor
Variable
Transformer
1abc
v
1abc
i
Lf1
R
f1
Three
PhaseAC
Protection
BoardL
MCCB
Upstream
laboratory
MCB1
vsb
ThreePhase
415V50Hz
vsa
vsc
isa
isb
isc
Laboratory
Threephase
Supply Side
Dspace11v3Controller
interfaceto PC
BKR1
Filter
Inductor
T1 T2
1a
i
1b
i
1c
i
2abc
v
f
i
R
1L1L2
R
2
R
3L3
R
f=2
R
4L4
Fdc12
DC Regulated
Supply
VSC2
VSC1
Filter
Inductor
PC for Dspace
Interface
DC line
Resistive Load
Filter
Inductor
Autotr ansformer
Figure 10: Schematic diagram of two-terminal DC system and photograph of
laboratory setup.
Table 2: Experiment Setup Parameters
Parameters Values
Supply voltage 3φ, 85 Vrms , 50 Hz
3φAC Protection Board 40 A, B Type, TP MCB with Shunt trip
3φVariable Transformer 30 kV A, (0-415) V
Converters (VSC1, VSC2) 30 kV A, 400 V
DC Capacitor Cdc = 2350 µF ,
DC Line Paramters Ld= 1.5 mH,Rd= 0.03
DC MCB C60H-DC, C 4 A
Interface Filter Parameters Rf= 0.1 Ω, Lf= 10 mH
Linear Load Rl= 20
Variable Power Resistor 5000 W, (1-16)
DC Solid State Relay D2D40, 200 V, 40 A
analog to digital channels (ADCH) ports. The control algorithm is developed
in MATLAB/Similink and converted for the dSPACE hardware interface by
13
the means of Real Time Interface (RTI) toolbox. The pulse-width modulation
(PWM) gating pulses generated by the controller are fetched to the VSCs for
switching.
Figure 11: (a)Experimental result for 2 DC fault; (b)Wavelet coefficients for
Idc12 and Idc21.
Direct short-circuit across the DC line is not viable as the large fault current
could trigger the tripping of main circuit breaker in the laboratory. In order to
limit the magnitude of the fault current, a power resistor is inserted between
upper and bottom DC line and the connection is controlled by a DC solid-state
relay. During the startup of experiment, the relay remains open. When the sys-
tem has achieved steady-state, the relay will be closed to electrically establish
a connection across DC line via power resistor. The value of the resistance is
adjustable from 1 to 16 Ω.
Fig. 11 shows the measurements of Iac1,Vdc1,Idc12 and Idc21, in that or-
14
der on LeCroy Wavesurfer 3024 oscilloscope, for 2 DC fault. The sampling
frequency used in the measurement is 10 kHz. The signals of interest here are
Idc12 and Idc21. The segment in dashed box is zoomed in to better visualize
the fault-induced transient. The corresponding wavelet analysis using db3 is
presented in the same figure.
One can immediately notice that the steady state DC currents essentially
do not yield zero wavelet coefficient as seen in the simulation results. The value
falls between [w1,w2 ], marked by the dashed line. For now we take [w1,w2 ] as
threshold, it will be discussed in subsection later how removing the noise in the
signal can reduce the steady state wavelet coefficient.
As expected, abrupt increase of current caused by the DC fault registers high
wavelet coefficients for both currents. The fault inception time (3s) is translated
to 1877th sample at 4th level of decomposition. The highest wavelet coefficient
is obtained by one sample delay. Even with the delay introduced by filtering,
the detection time would still be reasonably short.
5.1. Influence of DC fault resistance
Figure 12: Wavelet coefficient for DC fault of varying fault resistance (a) 4 Ω;
(b) 6 Ω; (c) 8 Ω; (d) 10 Ω; (e) 12 Ω; (f) 14 Ω.
Similar to the Section 4.2, repeated experiments are carried out to evaluate
the performance of wavelet transform for different fault resistance, ranging from
4 to 14 Ω. Fig. 12 depicts the result of wavelet analysis on the DC currents
(Idc12 &Idc21).
15
The faults are detected for all fault resistances evaluated. The highest
wavelet coefficient is observed around sample number 1878 (equivalent to 3.0016
s). Despite the presence of noise in the signal, the wavelet coefficients are kept
within the presumed threshold, marked by the dashed line in the figures, during
steady-state. The wavelet coefficient shows downward trend when increasing the
fault resistance. Nevertheless, a reasonably big margin between the threshold
and the wavelet coefficient still justifies the effectiveness of the WT in detecting
the DC fault.
5.2. Influence of DC line length
Figure 13: DC line represented by RL circuit in experiment and different line
length to be investigated.
Similar to the Section 4.3, our interest is to study the effect of fault distance
on the WT at experimental level. Besides the fault location, the frequency
content of the transient is also a function of the DC line length. Three tests
with different combination of inductance representing different fault location
and DC line length are carried out, as shown in Fig. 13. The DC currents are
analyzed with the WT and the result is shown in Fig. 14.
The WT successfully detects the DC fault with the wavelet coefficient ex-
ceeding the threshold by large margin. One can observe that the terminal closer
to the fault has current yielding the higher wavelet coefficient than its counter-
part. For example, in Test 3, smaller L2and L4implicates the fault to be closer
to the VSC2, and the fault at this location results in higher wavelet coefficient
for Idc21 compared to Idc12. Nevertheless, the two terminals are able to rec-
ognize the occurrence of DC fault as their maximum wavelet coefficients are
consistently higher than threshold for all fault locations evaluated.
16
Figure 14: Wavelet coefficient for DC fault of varying fault location (a) Test 1;
(b) Test 2; (c) Test 3.
5.3. Influence of other type of power system disturbance
Figure 15: Experimental result and wavelet analysis for (a) DC fault; (b) Load
change.
17
Load change in power system results in current increase that could be mis-
taken for DC fault. This subsection aims to study the feasibility of the WT
in differentiating between DC fault and load change. To reproduce this phe-
nomenon at experimental level, the resistive load at receiving end is reduced
abruptly such that it generates a transient that reaches the same peak as fault-
induced transient. The results from the experiment and the corresponding
wavelet coefficients are shown in Fig. 15.
As expected, the Idc12 in DC fault produces high wavelet coefficient. Al-
though the load change causes transient in the DC current, its wavelet coeffi-
cient appears to increase not very much, barely crossing the presumed threshold.
Thus, it is now clear that the DC fault can be differentiated from the load change
using the WT.
5.4. Influence of signal noise
Figure 16: (a) Raw and denoised signal for DC fault at 14 Ω; (b) Wavelet
coefficient for denoised signal.
The signal measured directly from the experiment contains the noise amount-
ing to 11.421 dB signal-to-noise ratio (SNR). The noise gives rise to non-zero
wavelet coefficient during steady state. However, the wavelet coefficient appears
to stay within the presumed threshold in all the studies so far. This subsection
investigates on filtering the noise.
The Idc12 for DC fault at 14 is smoothened with bandstop filter so as to re-
tain the fault-induced transient which is of high frequency and critically needed
18
for detection. The denoised signal now has 27.658 dB SNR during steady-state.
Fig. 16 depicts the difference between raw and denoised signal. When ana-
lyzed with the WT, it is noticed that the steady-state wavelet coefficient has
decreased substantially (see Fig. 16(b)), compared to that in Fig. 12(f). Fur-
thermore, the maximum wavelet coefficient does not deviate much as a result of
filtering, proving that the fault transient in the denoised signal is still preserved.
Hence, an appropriate filtering is highly recommended if one wants to keep the
steady-state wavelet coefficient as low as possible.
5.5. Comparison with short-time Fourier transform method
Figure 17: Frequency spectrum of experimental fault current for window length
(a) 16, (b) 32 and (c) 64. Zero-crossing frequency bin is marked by dash line.
The problem with choosing the window size for STFT has been discussed in
Section 3. For the purpose of fast fault detection, small window is preferable
at the expense of frequency resolution. The STFT analysis of high frequency
components in transient signals was reported in [34]. During steady-state, the
frequency spectrum of constant DC current should resemble a sinc function,
with the main-lobe concentrated at 0 Hz, with side-lobes uniformly distributed.
A key feature in the frequency spectrum is the zero-crossing frequency bin. Con-
sidering nas window size in term of sample number, the zero-crossing frequency
bin appears at 2fs/n, 3fs/n, 4fs/n and so on. When the DC fault happens, the
high-frequency transient will have its signal energy leak into other frequencies,
causing visible distortion across the side-lobes. Based on this phenomenon, the
fault can be detected by tracking the magnitude of zero-crossing frequency bin,
which will increase under the fault condition.
The frequency spectra of experimental fault current (Idc12) for 16, 32 and
64-sample window lengths using Hanning window are shown in Fig. 17.
1. 16-sample: The first zero-crossing frequency bin for this window is 1250
Hz. It can be seen that the side-lobes has already experienced slight
distortion caused by signal noise even before the fault occurrence. The
zero-crossing frequency bin increases above 0 dB (threshold) at 0.8 ms
after the fault inception. At which time, the fault is successfully detected.
19
2. 32-sample: The influence of noise is comparatively less significant for this
window size, given that the side-lobes retain equiripple-like pattern dur-
ing pre-fault. The first zero-crossing frequency bin (625 Hz) exceeds the
threshold with a time delay of 1.6 ms.
3. 64-sample: Similar to 16-sample window, the side-lobes are heavily dis-
torted by the noise during pre-fault. The fault is detected when the first
zero-crossing frequency bin (312.5 Hz) increases above threshold after 3.2
ms.
It is observed that the detection time is very much dependent on the window
size. 16-sample window provides the fastest detection. However, the signal
noise can cause significant distortion making the tracking of frequency difficult.
The influence of noise is also observable in 64-sample window while 32-sample
window is minimally affected. The STFT is met with the difficulty of choosing
the window size. The wavelet transform, on the other hand, can adjust the
window size automatically to suit the fault signal. In addition, as part of the
process of cascaded filtering, the wavelet transform is able to preserve the critical
signal while eliminating noise, but this cannot be done by the STFT.
6. Conclusion
The application of the wavelet transform to detect and identify the DC
fault in HVDC system has been analyzed and validated using simulation and
experimental results. db3 is adopted in the wavelet analysis as it presents the
closest match to the fault pattern and is able to detect fault with minimal delay.
The simulation result shows that the wavelet transform is able to indepen-
dently detect the faulted line in a 4-terminal HVDC system, only using the
wavelet coefficient for the DC line current at each terminal as criterion. The
detection time is approximately 1 ms. The value of the wavelet coefficient de-
creases as the fault resistance and the fault distance are increased, however it
is still well above the threshold by large margin.
From the experimental results, it can be inferred that the wavelet transform
also presents reasonable robustness to the influence of fault resistance and dis-
tance. It is not sensitive to the transient caused by load change, allowing to
classify the DC fault from other types of disturbances. The inherent noise in
the experimental result yields a non-zero wavelet coefficient, thus the threshold
needs to be set above that so as to avoid wrong detection. The steady-state
wavelet coefficient can be vastly reduced by smoothening the raw signal. The
filter has to be properly designed so that only the unwanted noise is removed
while the fault-induced transient, which is of high frequency, is still preserved.
Compared to the short-time Fourier transform (STFT), the wavelet transform
provides better flexibility when it comes to selecting window size and tolerance
against noise.
20
References
[1] M. Callavik, A. Blomberg, J. afner, B. Jacobson, The hybrid hvdc
breaker, ABB Grid Systems Technical Paper.
[2] A. Grid, Hvdc connecting the future, Alstom Grid publishers.
[3] C. Franck, Hvdc circuit breakers: A review identifying future research
needs, IEEE Transactions on Power Delivery 26 (2) (2011) 998–1007.
[4] S. Azizi, S. Afsharnia, M. Sanaye-Pasand, Fault location on multi-terminal
dc systems using synchronized current measurements, International Journal
of Electrical Power & Energy Systems 63 (2014) 779 786.
[5] L. Tang, B. Tang, Locating and isolating dc faults in multi-terminal dc
systems, IEEE Transactions on Power Delivery 22 (3) (2007) 1877–1884.
[6] M. Farhadi, O. Mohammed, Event-based protection scheme for a multi-
terminal hybrid dc power system, IEEE Transactions on Smart Grid 6 (4)
(2015) 1658–1669.
[7] M. Farshad, J. Sadeh, A novel fault-location method for hvdc transmission
lines based on similarity measure of voltage signals, IEEE Transactions on
Power Delivery 28 (4) (2013) 2483–2490.
[8] X. Zheng, N. Tai, J. Thorp, G. Yang, A transient harmonic current pro-
tection scheme for hvdc transmission line, IEEE Transactions on Power
Delivery 27 (4) (2012) 2278–2285.
[9] R. Keswani, Identification of fault in hvdc converters using wavelet
based multi-resolution analysis, in: 2008 First International Conference
on Emerging Trends in Engineering and Technology, 2008, pp. 954–959.
doi:10.1109/ICETET.2008.150.
[10] S. Niaki, H. Karegar, M. G. Monfared, A novel fault detection method for
vsc-hvdc transmission system of offshore wind farm, International Journal
of Electrical Power & Energy Systems 73 (2015) 475 483.
[11] H. Fathabadi, Two novel proposed discrete wavelet transform and filter
based approaches for short-circuit faults detection in power transmission
lines, Applied Soft Computing 36 (2015) 375 382.
[12] M. Jamil, A. Kalam, A. Ansari, M. Rizwan, Generalized neural network
and wavelet transform based approach for fault location estimation of a
transmission line, Applied Soft Computing 19 (2014) 322 332.
[13] M. Suganyadevi, C. Babulal, Support vector regression model for the pre-
diction of loadability margin of a power system, Applied Soft Computing
24 (2014) 304 315.
21
[14] P. Kanirajan, V. S. Kumar, Power quality disturbance detection and clas-
sification using wavelet and rbfnn, Applied Soft Computing 35 (2015) 470
481.
[15] S. Ekici, S. Yildirim, M. Poyraz, A transmission line fault locator based on
elman recurrent networks, Applied Soft Computing 9 (1) (2009) 341 347.
[16] S. Valsan, K. Swarup, Wavelet transform based digital protection for trans-
mission lines, International Journal of Electrical Power & Energy Systems
31 (78) (2009) 379 388.
[17] Y. Yeap, A. Ukil, Wavelet based fault analysis in hvdc system, in: IECON
2014 - 40th Annual Conference of the IEEE Industrial Electronics Society,
2014, pp. 2472–2478.
[18] K. Kerf, K. Srivastava, M. Reza, D. Bekaert, S. Cole, D. V. Hertem, R. Bel-
mans, Wavelet-based protection strategy for dc faults in multi-terminal vsc
hvdc systems, IET Generation, Transmission Distribution 5 (4) (2011) 496–
503.
[19] A. Abu-Elanien, A. Elserougi, A. Abdel-Khalik, A. Massoud, S. Ahmed,
A differential protection technique for multi-terminal hvdc, Electric Power
Systems Research 130 (2016) 78 88.
[20] P. Wang, X.-P. Zhang, P. F. Coventry, R. Zhang, Z. Li, Control and pro-
tection sequence for recovery and reconfiguration of an offshore integrated
mmc multi-terminal hvdc system under dc faults, International Journal of
Electrical Power & Energy Systems 86 (2017) 81 92.
[21] S. Liu, Z. Xu, W. Hua, G. Tang, Y. Xue, Electromechanical transient mod-
eling of modular multilevel converter based multi-terminal hvdc systems,
IEEE Transactions on Power Systems 29 (1) (2014) 72–83.
[22] J. Peralta, H. Saad, S. Denneti`ere, J. Mahseredjian, S. Nguefeu, Detailed
and averaged models for a 401-level mmc hvdc system, IEEE Transactions
on Power Delivery 27 (3) (2012) 1501–1508.
[23] M. Bucher, C. Franck, Contribution of fault current sources in multiter-
minal hvdc cable networks, IEEE Transactions on Power Delivery 28 (3)
(2013) 1796–1803.
[24] M. Bucher, C. Franck, Analysis of transient fault currents in multi-terminal
hvdc networks during pole-to-ground faults, in: Proc. International Con-
ference on Power Systems Transients (IPST), Vancouver, Canada, 2013.
[25] S. Mallat, A theory for multiresolution signal decomposition: the wavelet
representation, IEEE Transactions on Pattern Analysis and Machine Intel-
ligence 11 (7) (1989) 674–693.
[26] S. Mallat, A wavelet tour of signal processing, Academic press, 1999.
22
[27] A. Ukil, R. Zivanovic, Automated analysis of power systems disturbance
records: Smart grid big data perspective, in: 2014 IEEE Innovative Smart
Grid Technologies - Asia (ISGT ASIA), 2014, pp. 126–131.
[28] G. Strang, T. Nguyen, Wavelets and filter banks, SIAM, 1996.
[29] X. Ma, C. Zhou, I. Kemp, Automated wavelet selection and thresholding
for pd detection, IEEE Electrical Insulation Magazine 18 (2) (2002) 37–45.
[30] S. Santoso, E. Powers, W. Grady, P. Hofmann, Power quality assessment
via wavelet transform analysis, IEEE Transactions on Power Delivery 11 (2)
(1996) 924–930.
[31] U. N. Gnanarathna, A. M. Gole, R. P. Jayasinghe, Efficient modeling of
modular multilevel hvdc converters (mmc) on electromagnetic transient
simulation programs, IEEE Transactions on Power Delivery 26 (1) (2011)
316–324.
[32] J. Beerten, S. Cole, R. Belmans, Modeling of multi-terminal vsc hvdc sys-
tems with distributed dc voltage control, IEEE Transactions on Power Sys-
tems 29 (1) (2014) 34–42.
[33] A. Ukil, B. Deck, V. Shah, Current-only directional overcurrent protection
for distribution automation: Challenges and solutions, IEEE Transactions
on Smart Grid 3 (4) (2012) 1687–1694.
[34] Y. M. Yeap, A. Ukil, N. Geddada, Stft analysis of high frequency compo-
nents in transient signals in multi-terminal hvdc system, in: IECON 2016 -
42nd Annual Conference of the IEEE Industrial Electronics Society, 2016,
pp. 4008–4013.
23
... However, the response from the healthy lines could cause the false trip and the accuracy is easily influenced by the system disruption [9]. The current differential protection detects the fault based on the DC-link capacitor current rate, while its effectiveness is easily affected by the high frequency noise interference [10]. In [11], the voltage derivative protection is presented based on the derivatives of DC terminal voltage. ...
... Vulnerable to noise iii. affected by network disturbance Current differential protection [10] i.simple and easy i.Influnced by communication error ii.affected by time delay. Voltage derivative protection [11] i. Fast to detect faults i. dv/dt affected by the fault loop impedance ii. ...
Article
Full-text available
In voltage source converter (VSC) based low voltage DC systems (LVDC), the fault current of the DC-link capacitor is considerably high and destructive to system infrastructure. It is necessary to develop effective fault detection methods with sufficient sensitivity and accuracy. To achieve these targets, a complex domain analysis based fault detection method is proposed in this paper. Specifically, the proposed method firstly fits the transient current into a linear combination of exponential functions, which is solved in the Z-domain based on the Padé approximation. Secondly, exponents of the fitted function are projected into the complex plane. A state circle centered on the origin is defined on the complex plane to detect DC faults according to the position of projection points relative to the state circle. The proposed method can differentiate several typical situations via theoretical analysis, including fault line transients, healthy line transients and load switching. The performance of proposed method is validated with an experimental multi-terminal LVDC system to reveal its effective performance compared with present frequency domain based methods, including the wavelet transform, the short-time Fourier transform, the S transform and the Hilbert-Huang transform.
... Influenced by the noise iii. Restricted in real time its ability in real time Frequency domain analysis i. WT [14] i. Accurate i. High computation burden ii. Robust against noise ii. ...
... The WT is an accurate method in distinguishing different types of transients [14]. Since its base function is changed automatically, its time-frequency resolution is high even if the particular mother wavelet and the iterated extraction will increase the calculation burden. ...
Article
Full-text available
Due to the lack of zero-crossing in dc current and the rapid discharging of the dc-link capacitor, a typical fast-growing transient current will be generated after the dc fault inception in VSC interfaced dc power system, which may affect the dc grid operation and damage power electronics equipment. Therefore, a novel fault detection method with fast response speed and high robustness is urgently-needed. In this paper, a high pass filter (HPF) circuit based transient analysis method is proposed, detecting faults within 1 ms. Since dc faults have high frequency components when passing through a HPF, the high-frequency components are retained while low pass components are suppressed. This theoretical background of the HPF circuit based transient analysis method is presented in detail. In this regard, the HPF circuit is designed; the validity of the proposed method is tested on a seven bus multi-terminal dc (MTDC) system in the simulation and a four bus MTDC system in the experiment. A comparative analysis of the proposed method with some popular methods for fault identification, which includes wavelet transform (WT), the short-time Fourier Transform (STFT), the S transform (ST), and the Hilbert–Huang transform (HHT), emphasizes the comprehensive performance of the proposed method.
... High-frequency components arise when fault occurs in the system and these components are efficiently extracted by wavelet. The wavelet transform [18][19][20][21] method is more reliable in comparison to the rate of change of current method [22] for detection of fault. The internal and external faults are identified [23] by calculating the low-frequency voltage and tuning frequency voltage using a synchro-squeezing wavelet transform. ...
... Wavelet based [16][17][18][19][20][21][22][23][24] Efficient extraction of high frequency CWT has higher computations. components. ...
... Based on the electrical quantities of the DC reactor (i.e., reactor voltage (RV) [48], rate of change of reactor voltage (RRV) [46] and reactor power (RP) [49]), several protection methods have been proposed in the literature [46], [48]- [49]. The wavelet transform based signal processing method [141] is also a prevalent tool for fault detection. In this section, the performance of the proposed RVG method is compared with the aforementioned protection schemes for an external DC bus fault F 11 at bus-3, and an internal DC line fault F 12 in line-C. ...
... Considering the Daubechies3 (db3) wavelet and a 4-level decomposition, the desired frequency band of the given DC faults (F 11 and F 12 ) is localized in (312.5 -625) Hz for the WT based protection method [141]. With a sampling frequency of 10 kHz, the DC reactor voltage as shown in Fig.6.22(e) is used as the non-stationary input (fault) signal for the WT method. ...
... Interphase short circuits refer to power supply short circuits caused by the connection between the end lines with no passing of the load. Interphase short circuits only have positive sequence current [39] and negative sequence current, and no zero sequence current. The device includes two-phase short circuits and three-phase short circuits. ...
Article
Full-text available
This study aims to achieve intelligent decision making in HVDC systems in the framework of knowledge graphs (KGs). First, the whole life cycle KG of an HVDC system was established by combining intelligent decision making. Then, fault diagnosis was studied as a typical case study, and an intelligent decision-making method for HVDC systems based on XGBoost that significantly improved the speed, accuracy, and robustness of fault diagnosis was designed. It is noteworthy that the dataset used in this study was extracted in the framework of KGs, and the intelligent decision making of KG and HVDC systems was accordingly combined. Four kinds of fault data extracted from KGs were firstly preprocessed, and their features were simultaneously trained. Then, sensitive weights were set, and the pre-computed sample weights were put into the XGBoost model for training. Finally, the trained test set was substituted into the XGBoost classification model after training to obtain the classification results, and the recognition accuracy was calculated by means of a comparison with the standard labels. To further verify the effectiveness of the proposed method, back propagation (BP) neural network, probabilistic neural network (PNN), and classification tree were adopted for validation on the same fault dataset. The experimental results show that the XGBoost used in this paper could achieve accuracy of over 87% in multiple groups of tests, with recognition accuracy and robustness being higher than those of its competitors. Therefore, the method proposed in this paper can effectively identify and diagnose faults in HVDC systems under different operation conditions.
... Using the PSCAD/EMTDC software, a multi-terminal HVDC system is subjected to wavelet analysis. To illustrate the problem with window size and noise, the wavelet transform is further contrasted with the short-time Fourier transform [14]. The authors conducted a thorough investigation and analysis to look at a method for locating the defect in a long HVDC transmission line, say up to 1000 km in length. ...
Article
Full-text available
HVDC transmission has become a cost-effective option for transferring high voltage over greater distances. Protecting an HVDC transmission line is more challenging than protecting an AC transmission line due to its low impedance and absence of zero crossing DC current. Power electronic devices have finite overload capability, and standard relays are ineffective for HVDC line protection. Heavy current is generated by DC faults in HVDC (T/L), hence it is necessary to treat DC line faults in short, medium, and long HVDC (T/L) systems with different fault resistance. It is crucial to research fault detection methods based on time-frequency analysis by choosing appropriate algorithms using various (MW) methodologies for short, medium, and long HVDC transmissions at various fault resistances in order to protect the HVDC system. In this work, we examine how the length of an HVDC transmission line and fault resistance at both sides (inverter and rectifier) affects the selection of suitable mother wavelets for DC fault, using mean parameter and time-frequency transformation. SimPower System of Matlab is used to evaluate the impact of HVDC transmission line length and fault resistance on the selection of suitable mother wavelets. Simulation results show that Coif3 is an ideal wavelet for fault detection in medium transmission lines at different fault resistances. On the other hand, Rbio3.1 is more suitable for fault detection in long transmission lines at various fault resistances. For short and medium HVDC transmission lines, different mother wavelets were found to be suitable at different fault resistances. Therefore, it is essential to carefully consider the specific characteristics of the transmission line and the fault scenario when selecting a mother wavelet for accurate fault location.
... Nevertheless, developing these switches for high-voltage implementations was a task for decades because, unlike A.C. networks, D.C. networks don't have a fundamental current zero, so a circuit breaker had to drive the current to zero and waste the energy trapped in the inductor. Yeap, Y.M., et al. (2017) [3]. The fault features and cause assessment are required for adequate protection layout since the D.C. line failure will substantially impact the functioning of the VSC-HVDC. ...
Article
Full-text available
A comprehensive process of the control and protection against a DC fault in a voltage source converter (VSC) based high-voltage direct current (HVDC) system typically includes fault detection, fault isolation and system recovery. Regarding an offshore wind farm (OWF) integrated modular multilevel converter (MMC) based multi-terminal HVDC (MTDC) system with two control paradigms, i.e. master-slave control and droop control under DC faults, this paper presents the fault isolation, including the isolation of the faulted line section, with detailed control and protection sequence, which would be useful for practical engineering. The control and protection sequence at the system recovery/reconfiguration phase is comprehensively investigated, which includes: (1) when to start the recovery/reconfiguration control; (2) the sequence between deblocking the MMCs and reclosing the AC circuit breakers (AC CBs); and (3) the recovery sequence of each HVDC terminal. Based on the analysis of the system characteristics, a preferred recovery/reconfiguration scheme is proposed. Simulation results on the real-time digital simulator (RTDS) validate the proposed scheme and demonstrate the advantages through comparison with a different recovery sequence. The impact of transient and permanent DC faults on the system recovery/reconfiguration control is discussed. In addition, the recovery/reconfiguration control of the MTDC in radial and meshed topologies is compared and demonstrated. Based on the analytical and simulation studies, a general guideline on the recovery/reconfiguration control of MMC MTDC systems is proposed.
Conference Paper
Full-text available
High voltage DC (HVDC) system is important transmission technology, with several advantages over the AC transmission system. Transient analysis plays an important role in the power systems, in particular for the multi-terminal DC (MTDC) system. In DC systems, the DC line fault can result in extremely fast rising current compared to its AC counterpart due to absence of the line inductance. Therefore, the analysis of fast transients is of great interest in the HVDC system, in particular for MTDC system. In this paper, the application of Short Time Fourier Transform (STFT) in transient analysis of current signals in the MTDC system has been investigated. Because of uncertainty principle with the STFT, finer time resolution has been chosen at the expense of frequency resolution, allowing for faster detection. The CIGRE B4 multi-terminal DC grid system has been modeled in PSCAD/EMTDC, and transient events are simulated. The steady-state and the transient currents in the different terminals are monitored and analyzed using the STFT.
Article
Full-text available
VSC-HVDC transmission system is going to become the most economical way of power delivery for large and remote offshore wind farms. An accurate and fast fault detection method is necessary to protect sensitive devices of these systems and maintain uninterrupted power delivery. This paper investigates an innovative technique for recognizing DC zone faults including HVDC cable faults and unbalancing of DC capacitor bank. Sheath voltage is presented as a novel criterion for detecting abnormal situations in the system. Transient voltage of cable sheath and Wavelet transform are used to identify different types of DC faults. Extensive simulation examples are performed on EMTDC–PSCAD platform and post-processed using MATLAB. The results illustrate that the proposed technique gives a robust performance and can be applied to protection scheme of offshore wind farms.
Book
Mallat's book is the undisputed reference in this field - it is the only one that covers the essential material in such breadth and depth. - Laurent Demanet, Stanford University The new edition of this classic book gives all the major concepts, techniques and applications of sparse representation, reflecting the key role the subject plays in today's signal processing. The book clearly presents the standard representations with Fourier, wavelet and time-frequency transforms, and the construction of orthogonal bases with fast algorithms. The central concept of sparsity is explained and applied to signal compression, noise reduction, and inverse problems, while coverage is given to sparse representations in redundant dictionaries, super-resolution and compressive sensing applications. Features: * Balances presentation of the mathematics with applications to signal processing * Algorithms and numerical examples are implemented in WaveLab, a MATLAB toolbox * Companion website for instructors and selected solutions and code available for students New in this edition * Sparse signal representations in dictionaries * Compressive sensing, super-resolution and source separation * Geometric image processing with curvelets and bandlets * Wavelets for computer graphics with lifting on surfaces * Time-frequency audio processing and denoising * Image compression with JPEG-2000 * New and updated exercises A Wavelet Tour of Signal Processing: The Sparse Way, third edition, is an invaluable resource for researchers and R&D engineers wishing to apply the theory in fields such as image processing, video processing and compression, bio-sensing, medical imaging, machine vision and communications engineering. Stephane Mallat is Professor in Applied Mathematics at École Polytechnique, Paris, France. From 1986 to 1996 he was a Professor at the Courant Institute of Mathematical Sciences at New York University, and between 2001 and 2007, he co-founded and became CEO of an image processing semiconductor company. Includes all the latest developments since the book was published in 1999, including its application to JPEG 2000 and MPEG-4 Algorithms and numerical examples are implemented in Wavelab, a MATLAB toolbox Balances presentation of the mathematics with applications to signal processing.
Conference Paper
The fault current development in a circuit breaker during a pole-to-ground fault is analyzed for a generic multi- terminal HVDC system based on Voltage Source Converters. The paper aims to contribute to the current discussion of which requirements on breaking time and peak current HVDC circuit breakers need to fulfill in such networks either based on OHLs or cables. Therefore, the fault current is broken down into the individual contributions of the different network components and their influence on the development of the fault current in the circuit breaker of the faulted line is illustrated. In doing so, the emphasis is on the comparison of the sensitivities in cable and OHL systems
Article
This paper introduces a novel approach to detect and classify power quality disturbance in the power system using radial basis function neural network (RBFNN). The proposed method requires less number of features as compared to conventional approach for the identification. The feature extracted through the wavelet is trained by a radial basis function neural network for the classification of events. After training the neural network, the weight obtained is used to classify the Power Quality (PQ) problems. For the classification, 20 types of disturbances are taken into account. The classification performance of RBFNN is compared with feed forward multilayer network (FFML), learning vector quantization (LVQ), probabilistic neural network (PNN) and generalized regressive neural network (GRNN). The classification accuracy of the RBFNN network is improved, just by rewriting the weights and updating the weights with the help of cognitive as well as the social behavior of particles along with fitness value. The simulation results possess significant improvement over existing methods in signal detection and classification.
Article
In this study, two approaches are presented to detect short-circuit faults in power transmission lines. The two proposed methods are completely novel from both theoretical and technical aspects. The first approach is a soft computing method that uses discrete wavelet transform with Daubechies mother wavelets db1, db2, db3, and db4. The second approach is a hardware based method that utilizes a novel proposed two-stage finite impulse response filter with a sampling frequency of 32 kHz, and a very short process time about three samples time. The two approaches are analyzed by presenting theoretical results. Simulated results obtained by simulating a three-phase 230 kV, 50 Hz power transmission line are given that validate the theoretical results, and explicitly verify that the filter based approach has an accuracy of 100% in presence of 10% disturbance while the accuracy of the wavelet transform based approach is maximally 97%, but it has less complication and implementation cost. Another comparative study between this work and other works shows that the two proposed methods have higher accuracy and very shorter process time compared to the other methods, especially in presence of 10% disturbance that actually occurs in power transmission lines.
Article
This paper presents a technique for differential protection of Multi-terminal High Voltage Direct Current (MTHVDC) transmission lines. The proposed technique depends on the electrical current data at both ends of each line section. Discrete Wavelet Transform (DWT) is used to detect DC faults as well as filter out the high frequency transients superimposed on the current signals. An operating signal and a restraining signal are used in this technique to discriminate between internal faults and external faults through their ratio in each section of the MTHVDC. The operating and restraining signals depend on energy contents of the de-noised current signals at both ends of each line section. MTHVDC modeling and relay design are carried out in the MATLAB environment. The results demonstrate the high reliability of the proposed relay in the zonal protection of MTHVDC.
Article
In this paper, we investigate an event-based protection scheme for a multiterminal dc power system, which includes hybrid energy resources and various loading schemes. The proposed protection scheme transfers less data when compared with commonly used data-based protection methods, and does not require high-speed communication and synchronization. Each protection unit is able to autonomously identify the type of event using the current derivative fault identification method, employing an artificial inductive line impedance. In order to accurately set the protection relays, detailed fault current analysis considering low pass resistor capacitor filter effects are presented. The decision for fault isolation is made based on the unit judgment and the data received through high-level data communication from other interconnected units. The performance of the proposed protection scheme was evaluated under different dc feeder and bus faults. The results show that this scheme is able to accurately identify the type of fault, isolate the faulted area, and restore the system quickly while limiting the load voltage drop to its preset limit.