Fig 1 - uploaded by Zhe Qu
Content may be subject to copyright.
Locations of hospitals of concern in this report and strong ground motion stations in the earthquake-affected area.

Locations of hospitals of concern in this report and strong ground motion stations in the earthquake-affected area.

Source publication
Article
Full-text available
The seismic performance of medical systems is crucial for the seismic resilience of communities. The report summarizes the observed damage to twelve hospital buildings in the area affected by the MW7.8 and MW7.5 earthquakes on 6 February 2023 in Turkey. They include five base-isolated buildings and seven fixed-base buildings in southcentral Turkey'...

Contexts in source publication

Context 1
... 5 km to the east of the campus of B1 and F1 was another base-isolated hospital building B2 of the Battalgazi State Hospital. It was constructed in 2020 and has 7 stories above ground (Fig. 10). Its superstructure was protected by an isolation layer of 220 FPBs with a design stroke of plus/minus 450 mm (T _ IS, 2023b). The isolation layer was in the underground parking lot, where the FPBs were installed on top of stout RC columns. Unlike the cantilever columns that support the FPBs of Building B1, these columns had flat beams ...
Context 2
... of 220 FPBs with a design stroke of plus/minus 450 mm (T _ IS, 2023b). The isolation layer was in the underground parking lot, where the FPBs were installed on top of stout RC columns. Unlike the cantilever columns that support the FPBs of Building B1, these columns had flat beams framing into them to restrain the rotation of the upper ends ( Fig. 11(a)). No damage, either structural or nonstructural, was observed in the hospital building, and the hospital was allegedly immediately occupiable after the earthquakes. However, along with the satisfying performance of this building there were no signs of considerable sliding of the isolation layer. The scattered paint on the FPBs remained ...
Context 3
... damage, either structural or nonstructural, was observed in the hospital building, and the hospital was allegedly immediately occupiable after the earthquakes. However, along with the satisfying performance of this building there were no signs of considerable sliding of the isolation layer. The scattered paint on the FPBs remained undisturbed ( Fig. 11(b)), the masonry infill that may have blocked the isolation layer remained intact (Fig. 11(c)), and the cover plate at the main entrance seemed to have not moved (Fig. 11(d)). Possible reasons for the satisfactory performance of the building with a seemingly uninitiated base-isolation layer may include the local terrain effect that may ...
Context 4
... hospital was allegedly immediately occupiable after the earthquakes. However, along with the satisfying performance of this building there were no signs of considerable sliding of the isolation layer. The scattered paint on the FPBs remained undisturbed ( Fig. 11(b)), the masonry infill that may have blocked the isolation layer remained intact (Fig. 11(c)), and the cover plate at the main entrance seemed to have not moved (Fig. 11(d)). Possible reasons for the satisfactory performance of the building with a seemingly uninitiated base-isolation layer may include the local terrain effect that may have attenuated the ground motion and the smaller scale of the building as compared to the ...
Context 5
... along with the satisfying performance of this building there were no signs of considerable sliding of the isolation layer. The scattered paint on the FPBs remained undisturbed ( Fig. 11(b)), the masonry infill that may have blocked the isolation layer remained intact (Fig. 11(c)), and the cover plate at the main entrance seemed to have not moved (Fig. 11(d)). Possible reasons for the satisfactory performance of the building with a seemingly uninitiated base-isolation layer may include the local terrain effect that may have attenuated the ground motion and the smaller scale of the building as compared to the partially damaged building F1. Thorough investigation is deemed necessary to ...
Context 6
... was a strong motion station, Station 4408, approximately 3 km from the hospital [ Fig. 12(a)]. According to the response spectra of the 4408 record in Fig. 12(b), the isolated hospital experienced approximately DD2-level shaking during the M W 7.8 event. The DR was 0.92. The hospital building B3 was very likely to have experienced much stronger shaking during the M W 7.5 event that followed. Unfortunately, Station 4408 failed ...
Context 7
... was a strong motion station, Station 4408, approximately 3 km from the hospital [ Fig. 12(a)]. According to the response spectra of the 4408 record in Fig. 12(b), the isolated hospital experienced approximately DD2-level shaking during the M W 7.8 event. The DR was 0.92. The hospital building B3 was very likely to have experienced much stronger shaking during the M W 7.5 event that followed. Unfortunately, Station 4408 failed to obtain a record during the latter event because of the blackout as ...
Context 8
... 6-story hospital building B3 was constructed in 2019 ( Fig. 13(a) and (b)). The isolation layer constituted a separate story of small height at the base of the building that did not serve any building function (Fig. 13(c)). The isolator consisted of 122 FPBs of a design stroke of plus/ minus 490 mm ( Fig. 13(d)). Their vertical load-bearing capacities ranged from 730 to 1 250 tons depending on their ...
Context 9
... 6-story hospital building B3 was constructed in 2019 ( Fig. 13(a) and (b)). The isolation layer constituted a separate story of small height at the base of the building that did not serve any building function (Fig. 13(c)). The isolator consisted of 122 FPBs of a design stroke of plus/ minus 490 mm ( Fig. 13(d)). Their vertical load-bearing capacities ranged from 730 to 1 250 tons depending on their diameters (T _ IS, 2023c). The isolation gap around the building was being excavated when we visited (Fig. 14(a) and (b)) allegedly upon the request of the ...
Context 10
... 6-story hospital building B3 was constructed in 2019 ( Fig. 13(a) and (b)). The isolation layer constituted a separate story of small height at the base of the building that did not serve any building function (Fig. 13(c)). The isolator consisted of 122 FPBs of a design stroke of plus/ minus 490 mm ( Fig. 13(d)). Their vertical load-bearing capacities ranged from 730 to 1 250 tons depending on their diameters (T _ IS, 2023c). The isolation gap around the building was being excavated when we visited (Fig. 14(a) and (b)) allegedly upon the request of the structural engineers who inspected the building after the earthquake and found that the ...
Context 11
... the building that did not serve any building function (Fig. 13(c)). The isolator consisted of 122 FPBs of a design stroke of plus/ minus 490 mm ( Fig. 13(d)). Their vertical load-bearing capacities ranged from 730 to 1 250 tons depending on their diameters (T _ IS, 2023c). The isolation gap around the building was being excavated when we visited (Fig. 14(a) and (b)) allegedly upon the request of the structural engineers who inspected the building after the earthquake and found that the moat was improperly refilled and suspected that the isolation layer has been blocked during the earthquakes. The underground isolation layer was partially flooded, suggesting possible leakage of some pipes ...
Context 12
... 14(a) and (b)) allegedly upon the request of the structural engineers who inspected the building after the earthquake and found that the moat was improperly refilled and suspected that the isolation layer has been blocked during the earthquakes. The underground isolation layer was partially flooded, suggesting possible leakage of some pipes (see Fig. 13(c)). A long cable tray in the isolation layer fell because of the failure of its supports of thin steel angles (see Fig. 14(c)). There were also signs of poor construction quality in the isolation layer. At the diagonal construction joints in multiple concrete beams over the isolator, longitudinal rebars were exposed and styrofoam blocks ...
Context 13
... that the moat was improperly refilled and suspected that the isolation layer has been blocked during the earthquakes. The underground isolation layer was partially flooded, suggesting possible leakage of some pipes (see Fig. 13(c)). A long cable tray in the isolation layer fell because of the failure of its supports of thin steel angles (see Fig. 14(c)). There were also signs of poor construction quality in the isolation layer. At the diagonal construction joints in multiple concrete beams over the isolator, longitudinal rebars were exposed and styrofoam blocks were found to remain in the concrete (Fig. ...
Context 14
... isolation layer fell because of the failure of its supports of thin steel angles (see Fig. 14(c)). There were also signs of poor construction quality in the isolation layer. At the diagonal construction joints in multiple concrete beams over the isolator, longitudinal rebars were exposed and styrofoam blocks were found to remain in the concrete (Fig. ...
Context 15
... because of the blocking of the isolation layer, disproportionate nonstructural damage was observed in the superstructure of the building. It included the widespread damage to the suspended ceilings (Fig. 14(c)) and the extensive cracking of masonry infills ( Fig. 14(d)). They are the two types of most commonly seen nonstructural damage often observed in non-isolated buildings ( Kanda et al., 2021). As a result of such nonstructural damage, the occupancy of B3 remained suspended upon our visit on March 30, ...
Context 16
... because of the blocking of the isolation layer, disproportionate nonstructural damage was observed in the superstructure of the building. It included the widespread damage to the suspended ceilings (Fig. 14(c)) and the extensive cracking of masonry infills ( Fig. 14(d)). They are the two types of most commonly seen nonstructural damage often observed in non-isolated buildings ( Kanda et al., 2021). As a result of such nonstructural damage, the occupancy of B3 remained suspended upon our visit on March 30, ...
Context 17
... is a base-isolated building of the Elbistan State Hospital with 378 beds (Elbistan Devlet Hastanesi, 2023). It was constructed in 2017 and had a block of 3 stories in the front and another block of 9 stories above the ground in the back (Fig. ...
Context 18
... strong motion record during the M W 7.5 event. The second closest strong motion station to the hospital was Station 4409. It was approximately 50 km to the northeast of Building B4 and was on the same side of the fault rupture (Fig. 4). Its response spectra suggest a 20% lower-than-the-DD2-level horizontal shaking within the 2-3 s period range [ Fig. 15(b)]. The actual ground shaking experienced by B4 should have been stronger than ...
Context 19
... blocks of B4 rested on top of an isolation layer of 455 FPBs in the basement, which was occupied as administrative offices. Most FPBs in the isolation layer were hidden behind nonstructural elements and only one near a staircase was exposed for visitors to acknowledge the seismic isolation technology (Fig. 16(a)). A first glance gave an impression that the isolator was blocked by a girder, which was in fact a thin gypsum board for decoration (Fig. 16(b)). According to the manager of the hospital, the gypsum board, together with other nearby nonstructural elements, was broken by the deformation of the isolator during the earthquake but has been ...
Context 20
... as administrative offices. Most FPBs in the isolation layer were hidden behind nonstructural elements and only one near a staircase was exposed for visitors to acknowledge the seismic isolation technology (Fig. 16(a)). A first glance gave an impression that the isolator was blocked by a girder, which was in fact a thin gypsum board for decoration (Fig. 16(b)). According to the manager of the hospital, the gypsum board, together with other nearby nonstructural elements, was broken by the deformation of the isolator during the earthquake but has been repaired soon after the earthquake. Despite this alleged nonstructural damage in the basement, the operation of the hospital was recovered ...
Context 21
... isolator during the earthquake but has been repaired soon after the earthquake. Despite this alleged nonstructural damage in the basement, the operation of the hospital was recovered immediately after the earthquake. Other minor damage to the building included the dislocation of some segments of the sealing plates around the isolation interface (Fig. 16(c) and ...
Context 22
... is the base-isolated building of the D€ ortyol State Hospital with 450 beds in Hatay Province (D€ ortyol Devlet Hastanesi, 2023). It was approximately 86 km to the southwest of the epicenter of the M W 7.8 event and approximately 25 km to the east of the fault rupture (see Fig. 1). Only 0.9 km to the east of the hospital was Station 3134, which obtained a strong motion record during the M W 7.8 event [ Fig. 17(a)]. The record had a peak ground velocity (PGV) of 40 cm/s in the horizontal direction. Its spectra suggest that the horizontal shaking was approximately 2.5 times the DD2-level intensity within the ...
Context 23
... with 450 beds in Hatay Province (D€ ortyol Devlet Hastanesi, 2023). It was approximately 86 km to the southwest of the epicenter of the M W 7.8 event and approximately 25 km to the east of the fault rupture (see Fig. 1). Only 0.9 km to the east of the hospital was Station 3134, which obtained a strong motion record during the M W 7.8 event [ Fig. 17(a)]. The record had a peak ground velocity (PGV) of 40 cm/s in the horizontal direction. Its spectra suggest that the horizontal shaking was approximately 2.5 times the DD2-level intensity within the period range of 2-3 s (Fig. 17(b)). The response spectrum in the vertical direction reached the DD1-level around the period of 1 s (Fig. ...
Context 24
... 0.9 km to the east of the hospital was Station 3134, which obtained a strong motion record during the M W 7.8 event [ Fig. 17(a)]. The record had a peak ground velocity (PGV) of 40 cm/s in the horizontal direction. Its spectra suggest that the horizontal shaking was approximately 2.5 times the DD2-level intensity within the period range of 2-3 s (Fig. 17(b)). The response spectrum in the vertical direction reached the DD1-level around the period of 1 s (Fig. ...
Context 25
... event [ Fig. 17(a)]. The record had a peak ground velocity (PGV) of 40 cm/s in the horizontal direction. Its spectra suggest that the horizontal shaking was approximately 2.5 times the DD2-level intensity within the period range of 2-3 s (Fig. 17(b)). The response spectrum in the vertical direction reached the DD1-level around the period of 1 s (Fig. ...
Context 26
... base-isolated B5 building was constructed in 2019 and had two 3-story blocks in the front and another 10-story block above ground in the back (Fig. 18(a)). The building was seismically isolated by 340 FPBs of a design stroke of plus/minus 400 mm. Their vertical load-bearing capacities range from 400 to 4110 tons depending on their diameters (T _ IS, 2023d). The isolation layer was not occupied for any other functions (Fig. 18(b)). A video showed that the shaking of the building was felt ...
Context 27
... in the front and another 10-story block above ground in the back (Fig. 18(a)). The building was seismically isolated by 340 FPBs of a design stroke of plus/minus 400 mm. Their vertical load-bearing capacities range from 400 to 4110 tons depending on their diameters (T _ IS, 2023d). The isolation layer was not occupied for any other functions (Fig. 18(b)). A video showed that the shaking of the building was felt by the occupants during the earthquake, who fled form the building with fear (Habertürk, 2023). Nonetheless, the building received little damage during the earthquake, and the operation was immediately resumed after the earthquake. The only sign of damage was the crushed edges ...
Context 28
... was felt by the occupants during the earthquake, who fled form the building with fear (Habertürk, 2023). Nonetheless, the building received little damage during the earthquake, and the operation was immediately resumed after the earthquake. The only sign of damage was the crushed edges of some tiles on the cover plate over the isolation gap (Fig. 18(b)). In addition, there were also signs of residual deformation of several millimeters in multiple FPBs [ Fig. ...
Context 29
... the building received little damage during the earthquake, and the operation was immediately resumed after the earthquake. The only sign of damage was the crushed edges of some tiles on the cover plate over the isolation gap (Fig. 18(b)). In addition, there were also signs of residual deformation of several millimeters in multiple FPBs [ Fig. ...
Context 30
... rupture of the M W 7.8 event was in a region of dense strong motion stations. The survey team visited four hospitals along the fault rupture. They were all fixed-base buildings constructed after 2001 and were within 2 km from the fault rupture of the M W 7.8 event. They are labeled as F2 to F5 according to their locations along the fault rupture (Fig. 1). This section introduces their post-quake occupancy status and observed damage if there was ...
Context 31
... F2 building of the Nurda gi State Hospital in Gaziantep Province was approximately 31 km to the east of the epicenter of the M W 7.8 event, the closest to the epicenter among the four hospitals of concern in this section (Fig. 1). The small city of Nurda gi was almost destroyed by the strong shaking of the earthquake (Haberler, 2023). The town was known to have a high seismic risk before the earthquake. The DD1-level maximum spectral acceleration is as high as 2.1g for site class ZB as per the seismic code (TBDY-2018(TBDY- , 2018. Although very strong, the ...
Context 32
... The DD1-level maximum spectral acceleration is as high as 2.1g for site class ZB as per the seismic code (TBDY-2018(TBDY- , 2018. Although very strong, the ground motion record by the nearby Station 2712 exhibited a horizontal spectral acceleration lower than the expected DD1-level spectrum at the estimated fundamental period of Building F2 [ Fig. 19(b)]. Nonetheless, it exceeded the DD2-level spectrum by 1.59 times. Despite the high demand ratio, the 4-story RC frame building F3 [ Fig. 22(a)] sustained no visible damage to its structural elements and minimal damage to its nonstructural elements. The hospital remained operational after the earthquake. A surface rupture went through ...
Context 33
... F5 of the Hatay Education and Research Hospital was close to the southwestern end of the fault rupture of the M W 7.8 earthquake (see Fig. 1). It was approximately 9 km to the northeast of the city center of Hatay. The city was among the most badly damaged areas in the earthquake. The building damage there was especially heavy on the alluvial plain along the ...
Context 34
... 2001 ( € Ozden and Erkılıç, 2015). All the hospital buildings introduced in the proceeding sections were built after 2001. In this last section, we introduce the observed damage to two older hospital buildings that were constructed before 2001. Both buildings were low-rise RC frame structures in Hatay Province. They are labeled as F6 and F7 in Fig. 1 Fig. 27(a)]. Although poor in very short-period contents, the record exhibited a horizontal spectral acceleration between the DD2 and DD1 levels in a wide range of period [ Fig. 27(b)]. F6 sustained severe structural damage under the strong shaking. A block in the middle of the building collapsed and was being demolished during the ...
Context 35
... a horizontal spectral acceleration between the DD2 and DD1 levels in a wide range of period [ Fig. 27(b)]. F6 sustained severe structural damage under the strong shaking. A block in the middle of the building collapsed and was being demolished during the earthquake (Fig. 28). The whole building was to be demolished according to the local staff. (Fig. 1). As shown in Fig. 29, the spectral acceleration of the 3134 record at the estimated fundamental period of F7 was close to the DD2-level spectrum. It was prohibited to access the building when we visited it. From outside the building, the observed damage included the collapsed wooden roof, RC column hinging at the bottom end, and ...

Similar publications

Article
Full-text available
The aim of this study is to investigate the performance of isolated structures by considering the possibility of impact under severe earthquakes. In the design of isolated structures, the required displacement capacity is determined based on the considered earthquake hazard level. However, there is a possibility of an impact caused by moat walls or...
Conference Paper
Full-text available
The new codes have recently introduced seismic detailing for new structures, but there are still older reinforced concrete structures without proper ductile detailing for earthquake resistance. These structures are further impacted by the corrosion of their embedded rebars which further reduces the strength and ductility under loading. This paper p...
Article
Full-text available
In response to the frequent occurrence of earthquakes in Chengdu, which poses a great threat to the economy, social development, production, and people’s lives, in this study, we construct an index evaluation system and a system dynamics model for urban seismic resilience based on an analysis of the interaction between earthquake disasters and the...

Citations

... [8][9][10] Observation of the post-quake status of medical systems in the 2023 Turkey seismic sequence, for example, highlighted that new base-isolated hospital buildings can provide better protection of non-structural elements than fixed-base ones. 12 This is confirmed in the case of hospitals first designed according to out-of-date seismic codes and then retrofitted with base-isolation, representing a cost-effective solution for the reduction of the seismic vulnerability of non-structural elements also taking into account the long-time frame related to the construction of new buildings. 13,14 Starting from experimental investigations on the seismic response from individual component testing, [15][16][17][18] attention has also addressed the interaction between structural and non-structural systems, involving shaking table tests of fixed-base [19][20][21][22] and base-isolated [22][23][24] testing facilities and two-level shake platforms simulating the motions of the upper levels of multi-storey buildings. ...
Article
Base‐isolated hospitals are frequently preferred to fixed‐base ones because of their improved seismic structural performance. Despite this, the question remains open on the advisability of using this modern seismic protection technology in preference to other conventional solutions, on the grounds of a holistic approach based on limiting non‐structural damage as well as continuity of service to the community in the aftermath of an earthquake. Two full‐scale four‐storey (fixed‐base) and three‐storey (base‐isolated) hospital buildings have been recently built and subjected to three‐dimensional shaking table tests at the National Research Institute for Earth Science and Disaster Prevention (Japan), with particular attention to evaluating and classifying functionality of non‐structural components and vital medical equipment. A two‐phase experimental campaign was carried out considering two earthquakes scaled at different intensity levels and applied along the horizontal and vertical directions. The current study aims to provide results of a numerical structural and non‐structural blind prediction of these hospital settings. A homemade numerical code is developed to account for lumped plasticity modelling of steel frame members and variability of the friction coefficient of spherical sliding bearings. Moreover, three non‐structural components are modelled in the fixed‐base structure: that is, elastic single degree of freedom systems representing two tanks filled with sand at the top floor; elastic beam elements for piping at the third floor; five‐element macro‐model for the in‐plane‐out‐of‐plane nonlinear response of partition walls at the first floor. The identification of predominant vibration periods of the fixed‐base structure is carried out using a homemade numerical code based on the continuous wavelet transforms in combination with the complex Morlet wavelet. Finally, the sliding and rocking motion of three items of medical equipment (i.e., incubator at third floor, dialysis machine at second floor and surgical bed at first floor) are analysed by means of a homemade numerical code, considering acceleration time histories of selected structural nodes of the fixed‐base structure.
... Seismic isolation technology has undergone decades of development and has been confirmed by numerous researchers as a dependable and highly efficient method for seismic resistance [1,2]. In particular, in strong earthquake events such as the Chi-Chi (1999), Wenchuan (2008), Lushan (2013), and Turkey (2023) earthquakes, buildings that have adopted seismic isolation technology have displayed excellent seismic performance [3][4][5][6]. By incorporating various types of bearings, seismic isolation technology can prolong the natural vibration period of a structure and thereby reduce its seismic response. ...
Article
Full-text available
Rubber bearings are composite components consisting of rubber layers and steel shims, which have been widely used in seismic isolation structures. The vertical stiffness of rubber bearings reduces significantly under lateral displacement. Previous studies have not clarified the vertical stiffness reduction for bearings with different dimensions. The focus of this study is to comprehensively explore the influence of the first and second shape factors (S 1 and S 2) on the vertical stiffness reduction of bearings with different shapes and to develop a prediction method. On the basis of the two-spring model, an improved theoretical formula for predicting the vertical stiffness of bearings under a lateral displacement was derived considering the influence of the S 1. Subsequently, a series of finite element (FE) models were developed. The parameters of rubber material were calibrated using experimental data. A parametric FE study was conducted to investigate the influence of different S 1 and S 2 on the vertical stiffness reduction of bearings under lateral displacements. The effectiveness of the proposed formula was evaluated by comparing the results with those obtained from the FE analyses. Finally, based on the improved formula, an empirical formula for vertical stiffness reduction that can consider the influence of both S 1 and S 2 was developed. The predicted results of the empirical formula showed good agreement with the experimental and numerical results.
... The earthquake led to the collapse of hospitals, destruction of infrastructure, and immediate homelessness for 1·5 million people in Türkiye. 5 Displaced Syrians faced worsening discrimination in accessing services, given the stark and overwhelming emergency and health-care needs and the existing challenges they already faced; the social and political atmosphere worsened subsequent to the earthquake, with political actors exploiting the issue, leading to an increase in anti-Syrian sentiment. 6 Due to the earthquake, there were also economic impacts, shortages of housing and shelter, and job losses exacerbating the situation for Syrian refugees; these had wider impacts, such as on health-care access. ...
... In 1939 (27 December 1939, Mw = 7.8), approximately 33,000 people died in Eastern Anatolia from the Erzincan earthquake. This event triggered the first Turkish Earthquake Regulation [5]. After the first regulation in 1940 and the Tosya-Lâdik earthquake in 1943 (27 November 1943, Mw = 7.7), a second earthquake regulation was followed in 1944. ...
Article
Full-text available
On 6 February 2023, near Kahramanmaraş in south-central Türkiye, an event underscored the vulnerability of cities to seismic activity, revealing a lack of preparedness for substantial shocks. The contributing factors are manifold, yet fundamentally, the collapse of buildings and infrastructure can be attributed to an underestimated capacity for meticulous settlement planning (location) and the adoption of advanced techniques for resilient construction (structure). Regrettably, as has been investigated by many research works, ordinary urban planning in Türkiye hardly finds ways to integrate the vulnerability analysis for settlement expansion, which includes the full integration of geological characteristics with the analysis of building sensitivity. With this work, we wanted to build a composite risk index based on earthquake vulnerability, hazard amplification map, and exposure. We designed the composite index in Izmir’s basin, Türkiye’s third most populated city, to answer the question: What if a destructive earthquake strikes this densely settled area? The results illustrates how the coupled integration of digital data on geology with settlements and infrastructure in a Geographic Information System environment can be used to produce risk maps and plan the anthropic system’s adaptation carefully. Findings demonstrate the city is highly vulnerable to earthquakes and identify priority areas for planning intervention, relocation, and renovation of buildings.
... Several reports and papers, such as (Alhawamdeh et al., 2023;EMSC -European-Mediterranean Seismological Centre, 2023;Lekkas et al., 2023;Mertol et al., 2023;OZTURK et al., 2023;Qu et al., 2023), have studied the casualties and damage individually or collectively. ...
Article
This paper reviews the performance of the buildings in Syria and Turkey during the February 6, 2023, Turkey-Syria earthquake. The damage and performance levels of buildings in the earthquake zones varied from minor or no damage to complete collapse. The damaged buildings are classified as seismic and non-seismic-designed buildings according to the earthquake codes. It has been found that there are many reasons for building collapses, such as non-consideration of seismic requirements in design or construction, poor quality of used materials, the possibility of exceeding the earthquake intensity than the design intensity level, insufficient foundations, and soil-related collapses. Based on the reasons mentioned above, general recommendations and future visions are highlighted to avoid the recurrence of such damages and collapses in future earthquakes.
... In the southern part of the EAFZ on the Karasu segmen ( Fig. 7 1a), a smaller slip-rate of 4.5±1.1 mm.year −1 is determined 3,5 . Large historical earthquakes also occurred more recently in 8 1822 CE (Ms 7.0) and in 1872 CE (Ms 7.2) along this segment leading to a strain accumulation of 0.6-1.1 m 3 . Potentially, 9 earthquakes of Mw 6.8-7.2 were expected in the future in this segment of the EAFZ 4 . ...
... A first mainshock of Mw7.8 was followed 8 hours later by a Mw7.6. The Mw 7.8 rupture initiated on 12 the Narli fault, 15 km south of the main strand of the EAF (Fig. 3a) and later propagated bilaterally along the main strand of 13 the EAF along the Erkenek segment towards the northeast and along the Pazarcik and Karasu/Amanos segments towards the 14 southwest [6][7][8][9][10][11] . The second earthquake initiated on the Çardak fault ( Fig. 1a) and propagated bilaterally west-and eastward 15 toward the east and west extremities of the Çardak fault (Fig. 3a). ...
Preprint
Full-text available
On February 6, 2023, southern Türkiye was hit by two major earthquakes at 01:17 UTC (Mw=7.8, Pazarcık, Kahramanmaraş) and at 10:30 UTC (Mw=7.6, Elbistan, Kahramanmaraş) leading to severe damages at the complex junction of the Dead Sea Fault (DSF), the Cyprus arc and the East Anatolian fault zone (EAFZ). The ruptures propagated along several known strands of the southwestern termination of the EAFZ, the main Pazarcık and Karasu valley faults and the Çardac-Sürgü fault. Here, we present the high-resolution mapping of the entire coseismic surface rupture and an estimation of the rupture width, the total and on-fault offset, and of the diffuse deformation obtained a few days after the two mainshocks. The mapping is derived from image correlation of optical Sentinel-2 satellite imagery and is validated with offset measurements collected on the ground. We found that the ruptures extend over lengths of 310 km and 140 km for the Mw 7.8 and Mw 7.6 mainshocks, respectively. The maximum offsets reach 7.5 ± 0.8 m and 8.7 ± 0.8 m, near the epicenters of the Mw 7.8 and Mw 7.6, respectively. We propose a segmentation of the two ruptures based on these observations, and further discuss the location of potential supershear rupture. The use of optical image correlation complemented by field investigations along earthquake faults provides new insights into the seismic hazard assessment.
... The hospital located at a minimum distance of 30 m west of the surface rupture was not affected by the left-lateral offset and remained operational during the aftershock period suffering only slight non-structural damage [51]. It is very important to mention here that theİslahiye hospital was constructed to the strictest seismic standards with the aim to remain unaffected and operational even in the aftermath of destructive events. ...
Article
Full-text available
On 6 February 2023, East Anatolia was devastated by two major earthquakes resulting in hundreds of thousands of collapses and tens of thousands of human casualties. This paper investigates the factors related to building properties and earthquake environmental effects (EEEs) that contributed to the building damage grade and distribution in southeastern Turkey. In regards to the building construction properties, the loose enforcement of the building code, the random urban planning solutions and the poor construction standards are the main construction deficiencies that led to one of the largest disasters in Turkey’s recent history. Regarding geological factors, the triggering of primary and secondary EEEs largely shaped the grade and distribution of damage. Where coseismic surface ruptures intersected with the built environment, heavy to very heavy structural damage was observed. This was evident in many cases along the ruptured segments of the East Anatolian Fault Zone (EAFZ). Liquefaction observed close to waterbodies caused damage typical of building foundation load-bearing capacity loss. The earthquake-triggered landslides affected mainly mountainous and semi-mountainous settlements characterized with pre-earthquake high related susceptibility. The high susceptibility to generation of EEEs was extensively confirmed in many cases resulting in extensive damage. The provided information highlights the importance of such studies for hazard mitigation and disaster risk reduction.
... Public buildings comprise hospitals, police and fire departments, and other administrative structures. Some of them, particularly health facilities including base-isolated and fixed-base buildings, demonstrated superior performance in terms of achieving the goal of immediate occupancy and providing better protection for nonstructural elements, whereas the latter achieved the goal of collapse prevention despite being very close to the coseismic surface fault ruptures and subjected to higher-than-design-level ground motion [50]. As regards the historical masonry mosques and minarets, their majority were heavily and very heavily damaged or completely collapsed after the earthquakes' occurrence. ...
Article
Full-text available
On 6 February 2023, southeastern Turkey was struck by two major earthquakes that devastated 11 provinces. Tens of thousands of buildings collapsed and more were later demolished. During post-event field surveys conducted by the authors, several disposal sites set up in the most affected provinces were detected and checked for suitability. Based on field observations on the properties of sites and their surrounding areas as well as on the implemented debris management activities, it is concluded that all sites had characteristics that did not allow them to be classified as safe for earthquake debris management. This inadequacy is mainly attributed to their proximity to areas, where thousands of people reside. As regards the environmental impact, these sites were operating within or close to surface water bodies. This situation reveals a rush for rapid recovery resulting in serious errors in the preparation and implementation of disaster management plans. In this context, measures for effective debris management are proposed based on the existing scientific knowledge and operational experience. This paper aims to highlight challenges during earthquakes debris management and related threats posed to public health and the environment in order to be avoided in future destructive events.
Conference Paper
Data collection concerning the operational conditions of the non- structural elements plays a crucial role to assess the seismic risk of healthcare facilities. In this context, Operational Modal Analysis (OMA) technique applied to non-structural components represents a valid procedure to identify the behavior of such components in service conditions and to detect anomalies of the system. In this paper, the potentialities offered by OMA for monitoring of non- structural elements and to support seismic risk assessment purposes are discussed. A glass partition wall, located in Campobasso’s Hospital (Southern Italy) has been considered as a case study. It has been monitored for a time interval of 19 days. Moreover, the influence of vibrational behavior of the building structure on the response of the glass partition has been assessed by a basic sensor layout to record the dynamic response of the floor. Research outcomes proved that (i) OMA is effective in providing information about the monitored system; (ii) building struc- ture dynamics can be discriminated, and the continuous dynamic identification of the glass partition accomplished; (iii) the dataset of the modal properties can be effectively used to identify changes in the performances and support the workplace safety of critical facilities.
Preprint
Full-text available
M w 7.8 and 7.5 strong earthquakes struck the Kahramanmaras province, southeastern Turkey on 6 February 2023. More than 50,000 and 8,400 lives were lost in Turkey and Syria, and approximately 230,000 buildings were destroyed or heavily damaged. 379 and 387 strong-motion stations in Turkey observed the M w 7.8 and M w 7.5 strong ground motions, nineteen and one of them recorded the east-west peak ground acceleration (PGA) larger than 500 cm/s ² , respectively. Referring to the building damage assessment map of 2023 Turkey earthquakes, we calculated the averaged damage ratio of 24 strong-motion stations with a circle of 100m in radius. Site effects in several specific southern Turkey cities may lead to a very irregular distribution of building damage. Based on the reinforced concrete (RC) analysis model of building damage probability created from the building damage data of the 1995 Hyogo-ken Nanbu (Kobe) earthquake, we estimated the building damage probability of these southeast Turkey strong-motion stations. The optimal seismic vulnerability functions of residential RC buildings in southeast Turkey were obtained. The shear strength might be set to 60% of OLD-RC structure or 40% of NEW-RC structure in the Nagato-Kawase model for Kobe earthquake when build the building seismic damage probability model of southeastern Turkey.